RAR3500
12
*
1
) Lowest/highest airflow of totally 5 fan steps.
*
2
) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m². At lowest/highest
airflow.
*
3
)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*
4
) Applicable at water temperature 60/40 °C, air temperature, in +18 °C.
*
5
) Applicable at water temperature 40/30 °C, air temperature, in +18 °C.
RAR3500 A without heat
Type
Output
[kW]
Airflow*
1
[m
3
/h]
Sound
level*
2
[dB(A)]
Voltage
Amperage
(control)
Length
[mm]
Weight
[kg]
RAR3510A
0
1100/2300
42/62
230V~/2,45 A
1057
38
RAR3515A
0
1550/3400
43/63
230V~/3,5 A
1567
51
RAR3520A
0
2200/4800
45/64
230V~/5,2 A
2073
70
RAR3500 E with electrical heat
Type
Output
steps
[kW]
Airflow*
1
[m
3
/h]
∆
t*
3
[°C]
Sound
level*
2
[dB(A)]
Voltage
Amperage
(control)
Voltage
Amperage
(heat)
Length
[mm]
Weight
[kg]
RAR3510E09
4,5/9
1100/2300 25/12
42/62
230V~/2,45 A
400 V3~/13 A
1057
42
RAR3515E14
7/13,5
1550/3400 27/13
43/63
230V~/3,5 A
400 V3~/19,5 A
1567
58
RAR3520E18
9/18
2200/4800 25/11
45/64
230V~/5,2 A
400 V3~/26 A
2073
78
RAR3500 W with water heat, coil for low water temperature (
4
80 °C)
Type
Output*
4
[kW]
Airflow*
1
[m
3
/h]
∆
t*
3,4
[°C]
Water
volume
[l]
Sound
level*
2
[dB(A)]
Voltage
[V]
Amperage
[A]
Length
[mm]
Weight
[kg]
RAR3510W
9,4
1100/2300
16/12
1,3
42/61
230V~
2,6
1057
42
RAR3515W
14
1550/3400
16/12
2,1
42/62
230V~
3,6
1567
58
RAR3520W
21
2200/4800
16/13
2,9
44/63
230V~
5,3
2073
78
RAR3500 WLL with water heat, coil for very low temperature water (
4
60 °C)
Type
Output*
5
[kW]
Airflow*
1
[m
3
/h]
∆
t*
3,5
[°C]
Water
volume
[l]
Sound
level*
2
[dB(A)]
Voltage
[V]
Amperage
[A]
Length
[mm]
Weight
[kg]
RAR3510WLL
9,2
1100/2300
14/12
2,6
42/61
230V~
2,55
1057
45
RAR3515WLL 14
1550/3400
15/12
4,2
42/62
230V~
3,6
1567
61
RAR3520WLL 20
2200/4800
15/12
5,8
44/63
230V~
5,1
2073
83
Protection class: IP20.
Approved by SEMKO and CE compliant.
Tehnical specifications