PAEC4000

23

EN

Installation and operating instructions

General Instructions 

Read these instructions carefully prior to 
installation and use. Keep this manual for 
future reference.

The product may only be used as set out in 
the assembly and operating instructions. The 
guarantee is only valid should the product 
be used in the manner intended and in 
accordance with the instructions. 

Application area 

PAEC4000 is developed to fit all entrances. 
Recommended installation height up to 
4 meters/13.1 feet. The air curtain is available 
without heat, with electrical heating and with 
water heating.  
Protection class for units with electrical 
heating: IP20.  
Protection class for units without heating and 
units with water heating: IP21. 

Mounting

The air curtain range can be adapted for 
vertical or horizontal installation. The 
units can also be installed by recessing into 
suspended ceilings.
 

Horizontal mounting 

The air curtain unit is installed horizontally 
with the supply air grille facing downwards 
as close to the door as possible. Minimum 
distance from outlet to floor for electrically 
heated units is 1800 mm/70.9 in. For other 
minimum distances, see fig. 3.

For the protection of wider openings, several 

units can be mounted next to each other 
using a joining kit (fig. 9). 

A design kit for a neat installation that 

conceals cables, pipes and mountings 
is available for both wall and ceiling 
installations, se accessories pages.

 

Mounting with wall brackets

1. Remove the plastic covers on the wall 

brackets. (Fig. 6A)

2. Mount the brackets on the wall according to 

measures in fig. 6B.

3. Fasten the hammer head screws on the unit 

in the holes M8. (Fig. 5 and 6C)

4. Lock the nuts so that the hammer head 

screws are at 20 mm/0.79 in height. Note the 
direction of the screw heads. (Fig. 6C)

5. Slide the unit on the consoles. (Fig. 6D)
6. Lock the nuts against the bracket and put the 

plastic covers on again. (Fig. 6E)

 

Horizontal mounting on the ceiling 

Threaded rods, wire suspension kits and 
ceiling brackets for ceiling mounting are 
available as accessories, see fig. 7 and 8 and 
separate manuals.
  

Horizontal recessed mounting in false ceilings

Outlet extension used for recessed installation 
is available as an accessory, see fig. 10 and 
separate manual.
 

Operation 

Air is drawn in at the top/rear of the unit and 
blown downwards/outwards shielding the door 
opening and minimizing heat loss. To achieve 
the optimum air curtain effect the unit must 
extend the full height/width of the door 
opening.

The grille for directing the outlet air is 

adjustable and is normally angled outwards to 
achieve the best protection against incoming 
air. 

The efficiency of the air curtain depends on 

the air temperature, the pressure differencial 
across the doorway and any wind load. 

NOTE! Negative pressure in the building 

considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced. 

Содержание PAEC4000 NA Series

Страница 1: ...tings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program The AMCA...

Страница 2: ...of totally 3 fan steps 2 Values shown are for total sound power levels for InstallationType A free inlet free outlet The Sound power level ratings shown are in decibels referred to 10 12 watts calcula...

Страница 3: ...llationType A free inlet free outlet The Sound power level ratings shown are in decibels referred to 10 12 watts calculated per AMCA Standard 301 3 FLA total amperage for motor and heat 4 Applicable a...

Страница 4: ...19 6 2 23 4 38 0 28 12 2 PAEC4020W NA max 4250 28 3 35 0 27 5 5 32 9 38 0 40 10 7 Metric chart Imperial chart 1 Recommended outlet air temperature for good comfort and optimized output 2 Nominal outp...

Страница 5: ...f pictures For translation of the English texts used see the respective language pages EN Les pages de pr sentation contiennent principalement des images Pour la traduction des textes en anglais consu...

Страница 6: ...80 Q 36 1 44 R 1572 62 88 PAEC4015x S 2062 82 48 PAEC4020x T 2572 102 88 PAEC4025x U 1515 60 60 PAEC4015x V 2004 80 16 PAEC4020x W 2515 100 60 PAEC4025x X 23 0 92 Y 40 1 60 Z 611 24 44 611 L 295 36 40...

Страница 7: ...position with the front hatch hook Fig 2 Control card SIRe is integrated in the air curtain at delivery SIRe Fig 1B When the front has been removed it it important to be sure it is firmly seated in th...

Страница 8: ...PAEC4015x PAEC4020x PAEC4025x Ref Metric mm Imperial in Product type A 127 5 08 PAEC4010 15 20 25x B 102 4 08 PAEC4010 15 20 25x C 235 9 40 PAEC4010 15 20 25x D 750 30 00 PAEC4010x E 1260 50 40 PAEC40...

Страница 9: ...15x 2 pcs 400 15 75 Fig 6 PA34WB20 PAEC4020x 3 pcs 400 15 75 Fig 6 PA34WB30 PAEC4025x 4 pcs 400 15 75 Fig 6 PAWBL15 PAEC4015x 2 pcs 560 22 05 Fig 6 PAWBL20 PAEC4020x 3 pcs 560 22 05 Fig 6 PAWBL30 PAEC...

Страница 10: ...tric Length Imperial PA34CB15 PAEC4010 15x 4 pcs PA34CB20 PAEC4020x 6 pcs PA34CB30 PAEC4025x 8 pcs PA34WS15 PAEC4010 15x 4 pcs 3 m 9 8 ft PA34WS20 PAEC4020x 6 pcs 3 m 9 8 ft PA34WS30 PAEC4025x 8 pcs 3...

Страница 11: ...24x2516 3 48x16 96x100 64 Type Product type Length Metric mm Length Imperial in PA4XT10 PAEC4010x 130 200 5 20 8 00 PA4XT15 PAEC4015x 130 200 5 20 8 00 PA4XT20 PAEC4020x 130 200 5 20 8 00 PA4XT25 PAEC...

Страница 12: ...PAEC4000 12 Accessories Note The air curtain must be secured in the wall or ceiling Fig 11 See separate manual for PA4JK PA4VDW PA4JK...

Страница 13: ...W PAEC4000 AXP300 PAEC4000 Accessories Type Product type Length Metric Length Imperial PA34EF10 PAEC4010W NA PA34EF15 PAEC4025W NA PA34EF20 PAEC4020W NA PA34EF25 PAEC4025W NA DTV200S PAEC4000W NA FHDN...

Страница 14: ...8 ft SIReCC605 5 m 16 4 ft SIReCC610 10 m 32 8 ft SIReCC615 15 m 49 2 ft SIReCC640 40 m 131 2 ft SIReCC403 3 m 9 8 ft SIReCC405 5 m 16 4 ft SIReCC410 10 m 32 8 ft SIReCC415 15 m 49 2 ft Accessories C...

Страница 15: ...4000 15 PAEC4000A W H1 H2 N Id SIRe B1EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M 4010WA 4025WA 4020WA 4015WA 20...

Страница 16: ...B1EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo K2 K1 4010E 4015E 4010E 4015E TS1 TS2 Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M 208V3 L1L2 L3 L1 K2 L2 K2 L3...

Страница 17: ...L N Heating L N L Trafo K2 K1 K2 K1 4020E 4025E 2 X 208V3 TS2 TS1 Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M PAEC AREC 4020E 4025E 161123 208V3 L1 L2 L3 4025E 4020E 4020 6 motors...

Страница 18: ...C Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo K2 K1 4010E 4015E 4010E 4015E TS1 TS2 Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M 600 480V 230V Transformer 2 x 1...

Страница 19: ...V PE L N Heating L N L Trafo K2 K1 K2 K1 4025E 4020E 4020E 4025E 2 X 600V3 480V3 TS2 TS1 TS3 TS4 Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M 600V3 480V3 PAEC AREC 4020E 4025E 2152...

Страница 20: ...C1 X4 ROOM X3 Pot Unit ID ACTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReCC6XX max 50 m SIReCC6XX max 50 m C SIReUB1 SIReRTX optional L 2m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC L 2 m...

Страница 21: ...CTUATOR SUPPLY N L N L PE L 230V SIReCC6XX max 50 m SIReB1 B2 B1EC SIReB1 B2 B1EC SIReB1 B2 B1EC SIReCC6XX max 50 m SIReCC6XX max 50 m C SIReUB1 SIReRTX optional SD230 SD230 SD230 L 1 5m L 2m L 2 m 6...

Страница 22: ...er l unit ou d en effectuer l entretien L installation ou l entretien de l unit doivent tre effectu s par un technicien qualifi seulement L unit ne doit pas tre install e et utilis e l ext rieur ou da...

Страница 23: ...ountings is available for both wall and ceiling installations se accessories pages Mounting with wall brackets 1 Remove the plastic covers on the wall brackets Fig 6A 2 Mount the brackets on the wall...

Страница 24: ...primary terminal box 2 208V3 Control supply is connected internally through 2x 10A fuses in the primary terminal box The largest cable diameter for the terminal block is 16 mm 0 025 in The cable gland...

Страница 25: ...eriod of non use smoke or an odour may result from dust or dirt which has collected on the element This is completely normal and disappears after a short time Connecting the water coil W The installat...

Страница 26: ...ct the electricity supply with the fully isolated switch 2 Allow the electrical coil to cool 3 Determine the cause of overheating and rectify the fault 4 Reconnect the air curtain All motors are equip...

Страница 27: ...r attention has to be given where children and vulnerable people are present Residual current circuit breaker E When the installation is protected by means of a residual current circuit breaker which...

Страница 28: ...s suspendues Voir la page des accessoires Installation avec des consoles pour montage mural 1 Retirer les couvercles en plastique des consoles Fig 6A 2 Monter les consoles sur le mur en respectant les...

Страница 29: ...ation est pr install dans le rideau d air l aide d une carte de r gulation int gr e voir fig 2 SIRe est pr programm avec des raccords rapides Les c bles modulaires sont raccord s au circuit imprim Voi...

Страница 30: ...similaire pour maintenir la connexion entre le rideau d air et les tuyaux afin d viter de tendre ces derniers et donc ne pas cr er de fuite R glage de l appareil et du d bit d air La direction et la v...

Страница 31: ...r de produits de nettoyage tr s alcalins ou acides Surchauffe Le mod le chauffage lectrique est dot d un dispositif anti surchauffe Si ce dispositif se d clenche il convient de le r initialiser de la...

Страница 32: ...l appareil ne doivent pas tre confi s aux enfants sans surveillance Tenez les enfants g s de moins de 3 ans loign s de l appareil moins qu ils ne soient constamment surveill s Les enfants g s de 3 8 a...

Страница 33: ...iante Temp rature de l air de sortie Temp rature de l eau Position ventilateur D bit d air Puissance Temp rature retour d eau D bit hydraulique Perte de charge Filetage ext rieur Quantit inclue Pi ces...

Страница 34: ...amme de classification certification AMCA Le sceau de classification certifi AMCA s applique au d bit d air la vitesse moyenne de sortie l uniformit de la vitesse de sortie la projection de vitesse et...

Страница 35: ......

Страница 36: ...18 December 2020 Main o ce Frico AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local conta...

Отзывы: