Note! The unit needs to be further secured if 
suspended from chains.

Electrical installation

The air curtain(s) must only be connected by 
a competent electrician, and in accordance 
with the applicable regulations.

Electrical installation can be carried out 

from the top/bottom for vertical mounting and 
from the left/right for horizontal mounting.

For AD Corinte A the wiring can be run 

internally through the unit to the terminal 
block. Secure the wiring inside the unit with 
cable ties to prevent it being sucked into the 
fans.

For AD Corinte E  the wiring should be run 

directly to the connection box. The radiation 
protection plate need to be removed to enter 
the connection box, see Fig. 9. The protection 
plate protects the connection box from 
radiant heating from the elements and must 
be put back after the installation. 

The motors are wired as standard for a 

three phase 230 V supply, but they can be 
reconfigured for a three-phase 400 V supply, 
see page 10. Frequency inverter ADCF15N or 
similar should be used for speed control. Each 
frequency inverter can be fused using a 10A 
fuse. The group should not be connected to a 
safety cut-out. See wiring diagrams pages 10-
12. When another make of frequency inverter 
is used, the max. frequency should be 43 Hz 
and the min. frequency 16 Hz.

Use only braided, twinned copper cable 

with 85% coverage, for example type RKFK,  
for supply of the motors from the frequency 
inverter. Foil screen has a higher capacitance 
than the copper braid and is therefore not 
suitable for use. See CE-EMC installation 
guidelines for the frequency inverter.

Suitable cable area is 1.5 mm². Max. cable 

length 50 m. For longer cable please contact 
Frico.

Note! Before securing the front panel, check 

that the fans rotate in the direction indicated 
by the arrows on the fans, (see Fig. 6). If 
not, swap two phases in the motor supply to 
change the direction of rotation.

When installing ADEA please note that 

the parameter FANC should be set to 1, see 
instruction for ADEA for more information.

Adjustment of air flow

The direction and speed of the air flow 
should be adjusted considering the load on 
the opening. Pressure forces affect the air 
stream and make it bend inwards into the 
premises (when the premises are heated and 
the outdoor air is cold). The air stream should 
therefore be directed outwards to withstand 
the load. (Generally speaking, the higher the 
load, the greater the angle is needed.)

Use a hexagon key to loosen the three 

screws supporting the outlet grille. Angle the 
grille outwards so that the air flow obstructs 
the incoming cold air.

Overheating

The air curtain unit is equipped with an 
overheat protector, which deploys when the 
temperature is too high. Reset as follows, see 
figure 4:
1 Disconnect the power supply.
2 Loosen the two screws of the air intake 

grille with a hexagon key and remove the 
grille.

3 Determine what caused the overheating.
4 Locate the red button positioned on the 

overheat protection, which are mounted on 
the long side of the electrical coil.

5 Press the red button until a click is heard.
6 Reinstall the air intake grille and switch on 

the power.

The motors of all air curtain units are 
equipped with integrated thermo contacts 
to protect against overheating, where the 
cables are routed to connection blocks TK-
TK. See wiring diagrams pages 10-13. The 
cut-out will automatically reset when the 
motor temperature has returned to within the 
motor’s operating limits.

Trouble shooting

If the fans are stationary, check the following:
1 The operating power supply to the unit; 

check fuses, circuit-breaker, time switch/
thermostat (if any) that starts and stops the 
unit.

Содержание ADCH17A Series

Страница 1: ...Thermozone ADC A E 18 GB 15 SE 21 RU...

Страница 2: ...Thermozone AD Corinte A E 2 125 60 150 45 150 Min 220 Min 220 30 20 3x Doorway Wall Top Bottom seen from above Wall Top Bottom seen from above Fig 1 M6 M6...

Страница 3: ...Thermozone AD Corinte A E 3 500 350 1700 2200 2450 Fig 2...

Страница 4: ...Thermozone AD Corinte A E 4 1 2 3 4 5 6 2 6 7 Fig 3...

Страница 5: ...Thermozone AD Corinte A E 5 Fig 4...

Страница 6: ...Thermozone AD Corinte A E 6 80 12 35 35 180 40 Fig 7 Fig 8 Fig 6 360 243 22 10 15 5 10 Fig 5...

Страница 7: ...Thermozone AD Corinte A E 7 Min 220 mm Min 220 mm 50 376 75 1700 2200 1670 2170 75 30 20 3x Left connection Right connection Wall Fig 7 Fig 8 Fig 9...

Страница 8: ...Thermozone AD Corinte A E 8 A C A C B B ADCEH 8 12 2x 2 alternatives for securing at the top 1 8 for securing at the air curtain 2...

Страница 9: ...Thermozone AD Corinte A E 9 Extra ADEAEB ADEAR ADEAOS MDCDC FC15A M ADCEH ADEA ADEAR ADEAOS MDCDC ADEAIS...

Страница 10: ...L2 L3 B2 TK Blue Brown TK TK L2 L1 PE B1 B3 B2 L3 TK TK Blue Green Yellow Yellow Black White Green Grey Grey Grey Grey Grey M3 M1 M2 M4 PE L1 L2 L3 TK TK Brown TK TK TK L3 L1 L2 B5 B4 PE Green Grey G...

Страница 11: ...Thermozone AD Corinte A E 11 P1 P3 P2 C C N 8 9 K1 K2 11...

Страница 12: ...Thermozone AD Corinte A E 12 AD Corinte A Regulation...

Страница 13: ...Thermozone AD Corinte A E 13 AD Corinte E Regulation...

Страница 14: ...25 Technical specifications Thermozone AD Corinte A without heat 1 Type Output kW Airflow m3 h Sound level 6 dB A Output motor W Voltage 3 motor V Amper age motor 400V3 230V3 A Length mm Weight kg ADC...

Страница 15: ...ter eller h ger vid horisontellt montage F r AD Corinte A kan kablaget dras internt i apparaten fram till kopplingsplinten Bunta d Allm nna anvisningar L s noga igenom denna bruksanvisning f re instal...

Страница 16: ...Luftstr mmen b r d r f r riktas ut t f r att st emot belastningen Generellt kan s gas att ju st rre belastning desto st rre vinkel kr vs Lossa med hj lp av insexnyckel de tre skruvarna som h ller utb...

Страница 17: ...S kerst ll att omr det kring apparatens insugs och utbl sgaller h lls fritt fr n ma terial som kan hindra luftstr mmen genom apparaten Apparaten har vid drift heta ytor Jordfelsbrytare g ller aggrega...

Страница 18: ...octite 270 3 ml to the screws supplied 3 Lift the unit into place and fix the brackets to the pendulums General instructions Read these instructions carefully before installation and use Keep this man...

Страница 19: ...the front panel check that the fans rotate in the direction indicated by the arrows on the fans see Fig 6 If not swap two phases in the motor supply to change the direction of rotation When installing...

Страница 20: ...is necessary Undertake cleaning at least twice a year A sample of Fingerprint remover is inclu ded on delivery The product gives a clean and dry surface To order please state no 11631 Fingerprint rem...

Страница 21: ...Thermozone AD Corinte A E 21 RU 3 1 2 3 4 5 5 6 1 7 6 220 AD Corinte A E 3 5 IP20 10 15 1 FC15 Thermozone AD Corinte A E...

Страница 22: ...ne AD Corinte A E 22 RU 1 7 8 2 M8 Loctite 270 3 1 7 8 2 M8 Loctite 270 3 3 AD Corinte A AD Corinte E 230 3 400 3 10 FC15M FC15A 10 10 12 FC15 43 16 85 RKFK CE EMC 50 1 5 2 Frico 6 AD Corinte ADEA FAN...

Страница 23: ...Thermozone AD Corinte A E 23 RU 10 13 1 2 2 3 4 5 6 1 2 3 4 6 2 1 2 3 4...

Страница 24: ...Thermozone AD Corinte A E 24 RU...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...United Kingdom Frico Limited Tel 44 0 1213220854 72 Cheston Road Fax 44 0 1213220858 B7 5EJ info uk frico se UK Birmingham www frico co uk United Kingdom Russia Frico repr office in Russia Tel 7 495...

Отзывы: