Thermozone AD Corinte A/E

18

GB

secure it using expander bolts or similar in 
the countersunk holes (see fig. 5). Stand the 
air curtain on the edging.

6. Flat bar for fixing of the air curtain is 

supplied. Fix the air curtain through the 
quadratic hole, to secure it sideways. Make 
sure that the flat bar is not bent when 
securing.

7. Secure the top with an angle bracket or 

similar to prevent the air curtain from 
toppling over. There is a hole in the centre 
of the top of the air curtain with an internal 
M6 thread for securing the bracket.

  Please observe that the unit can not be 

turned because the overhetating protector 
is placed at the top.

Horizontal mounting

The unit is mounted with the outlet facing 
downwards. Do not remove the protective 
plastic until mounting is completed. Take care 
not to damage the surfaces.

For optimal performance it is recommended 

that a minimum gap of 220 mm to the ceiling 
is maintained above the air curtain. Closer 
mounting might cause over heating.

Two brackets are delivered with the unit 

for mounting on the wall or hanging from the 
ceiling.

Horizontal mounting on the wall

1. Mount the brackets on the wall according to 

measurements in Fig. 7 and 8.

2. Lift the unit into place and lock it using a 

hexagon key and the M8 screws supplied.  
Apply Loctite 270 (3 ml) to the screws 
(supplied).

Horizontal mounting on the ceiling

1. Mount pendulums or similar (not included 

in delivery) on the ceiling with c-c distance 
according to Fig. 7 and 8.

2. Mount the brackets on the unit with a 

hexagon key and the M8 screws supplied. 
Apply Loctite 270 (3 ml) to the screws 
(supplied).

3. Lift the unit into place and fix the brackets 

to the pendulums.

General instructions

Read these instructions carefully before 
installation and use. Keep this manual for 
future reference.

Application area

The Thermozone AD Corinte air curtain is 
supplied with or without an electric heater 
coil and is intended for permanent installation 
above or beside entrance doors and other 
openings up to 3,5 metres in height.
Protection class IP20

Operation

Air is drawn in at the top/rear of the unit and 
blown out downwards/outwards so that it 
shields the door opening and minimizes heat 
loss. To achieve the optimum curtain effect 
the unit must extend the full height/width of 
the door opening.

During installation the exhaust grille is 

normally directed outwards slightly so that 
the airflow obstructs incoming cold air. (See 
fig 1).

The fan speed should be controlled using a 

frequency converter.

The efficiency of the air curtain(s) depends 

on the air temperature, pressure differences 
across the doorway and any wind pressure. 
NOTE! Negative pressure in the building 
considerably reduces the efficiency of the air 
curtain. The ventilation should therefore be 
balanced.

Vertical mounting

The unit is mounted vertically on the floor 
with the exhaust opening facing outwards.

Before installation, decide whether any 

electrical connections are to be made from 
below.

Do not remove the protecting plastic until 

mounting is completed. Be careful so the 
surfaces are not damaged. 
For installation see figure 3.
1. Undo the screws in the front panel.
2. Undo the screws that secure the front panel 

to the exhaust grille.

3-4. Take off the front panel.
5. Place the edge on the floor and if necessary 

Assembly and operating instructions

Содержание ADCH17A Series

Страница 1: ...Thermozone ADC A E 18 GB 15 SE 21 RU...

Страница 2: ...Thermozone AD Corinte A E 2 125 60 150 45 150 Min 220 Min 220 30 20 3x Doorway Wall Top Bottom seen from above Wall Top Bottom seen from above Fig 1 M6 M6...

Страница 3: ...Thermozone AD Corinte A E 3 500 350 1700 2200 2450 Fig 2...

Страница 4: ...Thermozone AD Corinte A E 4 1 2 3 4 5 6 2 6 7 Fig 3...

Страница 5: ...Thermozone AD Corinte A E 5 Fig 4...

Страница 6: ...Thermozone AD Corinte A E 6 80 12 35 35 180 40 Fig 7 Fig 8 Fig 6 360 243 22 10 15 5 10 Fig 5...

Страница 7: ...Thermozone AD Corinte A E 7 Min 220 mm Min 220 mm 50 376 75 1700 2200 1670 2170 75 30 20 3x Left connection Right connection Wall Fig 7 Fig 8 Fig 9...

Страница 8: ...Thermozone AD Corinte A E 8 A C A C B B ADCEH 8 12 2x 2 alternatives for securing at the top 1 8 for securing at the air curtain 2...

Страница 9: ...Thermozone AD Corinte A E 9 Extra ADEAEB ADEAR ADEAOS MDCDC FC15A M ADCEH ADEA ADEAR ADEAOS MDCDC ADEAIS...

Страница 10: ...L2 L3 B2 TK Blue Brown TK TK L2 L1 PE B1 B3 B2 L3 TK TK Blue Green Yellow Yellow Black White Green Grey Grey Grey Grey Grey M3 M1 M2 M4 PE L1 L2 L3 TK TK Brown TK TK TK L3 L1 L2 B5 B4 PE Green Grey G...

Страница 11: ...Thermozone AD Corinte A E 11 P1 P3 P2 C C N 8 9 K1 K2 11...

Страница 12: ...Thermozone AD Corinte A E 12 AD Corinte A Regulation...

Страница 13: ...Thermozone AD Corinte A E 13 AD Corinte E Regulation...

Страница 14: ...25 Technical specifications Thermozone AD Corinte A without heat 1 Type Output kW Airflow m3 h Sound level 6 dB A Output motor W Voltage 3 motor V Amper age motor 400V3 230V3 A Length mm Weight kg ADC...

Страница 15: ...ter eller h ger vid horisontellt montage F r AD Corinte A kan kablaget dras internt i apparaten fram till kopplingsplinten Bunta d Allm nna anvisningar L s noga igenom denna bruksanvisning f re instal...

Страница 16: ...Luftstr mmen b r d r f r riktas ut t f r att st emot belastningen Generellt kan s gas att ju st rre belastning desto st rre vinkel kr vs Lossa med hj lp av insexnyckel de tre skruvarna som h ller utb...

Страница 17: ...S kerst ll att omr det kring apparatens insugs och utbl sgaller h lls fritt fr n ma terial som kan hindra luftstr mmen genom apparaten Apparaten har vid drift heta ytor Jordfelsbrytare g ller aggrega...

Страница 18: ...octite 270 3 ml to the screws supplied 3 Lift the unit into place and fix the brackets to the pendulums General instructions Read these instructions carefully before installation and use Keep this man...

Страница 19: ...the front panel check that the fans rotate in the direction indicated by the arrows on the fans see Fig 6 If not swap two phases in the motor supply to change the direction of rotation When installing...

Страница 20: ...is necessary Undertake cleaning at least twice a year A sample of Fingerprint remover is inclu ded on delivery The product gives a clean and dry surface To order please state no 11631 Fingerprint rem...

Страница 21: ...Thermozone AD Corinte A E 21 RU 3 1 2 3 4 5 5 6 1 7 6 220 AD Corinte A E 3 5 IP20 10 15 1 FC15 Thermozone AD Corinte A E...

Страница 22: ...ne AD Corinte A E 22 RU 1 7 8 2 M8 Loctite 270 3 1 7 8 2 M8 Loctite 270 3 3 AD Corinte A AD Corinte E 230 3 400 3 10 FC15M FC15A 10 10 12 FC15 43 16 85 RKFK CE EMC 50 1 5 2 Frico 6 AD Corinte ADEA FAN...

Страница 23: ...Thermozone AD Corinte A E 23 RU 10 13 1 2 2 3 4 5 6 1 2 3 4 6 2 1 2 3 4...

Страница 24: ...Thermozone AD Corinte A E 24 RU...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...United Kingdom Frico Limited Tel 44 0 1213220854 72 Cheston Road Fax 44 0 1213220858 B7 5EJ info uk frico se UK Birmingham www frico co uk United Kingdom Russia Frico repr office in Russia Tel 7 495...

Отзывы: