RWF ROTARY SCREW COMPRESSOR UNITS
MAINTENANCE
S70-600 IOM
Page 32
TROUBLESHOOTING THE HYDRAULIC SYSTEM
SYMPTOM
PROBABLE CAUSES and CORRECTIONS
SLIDE VALVE WILL NOT LOAD OR
Solenoid coils may be burned out. Replace.
UNLOAD
Valve may be closed. Open hydraulic service valves.
Solenoid spool may be stuck or centering spring broken. Replace.
Check outputs 2 and 3 and fuses.
Check LED on coil. If lit, there is power to the coil. Check coil.
Solenoid may be actuated mechanically by inserting a piece of 3/16" rod
against armature pin and pushing spool to opposite end. Push A side to
confirm unload capability. If valve works, problem is electrical.
SLIDE VALVE WILL LOAD BUT
A side solenoid coil may be burned out. Replace.
WILL NOT UNLOAD
Dirt inside solenoid valve preventing valve from operating both ways. Clean.
Check LED on coil. If lit, valve is functioning mechanically. Problem is electrical.
Solenoid may be actuated mechanically by inserting a piece of 3/16" rod
against armature pin and pushing spool to opposite end. Push A side to
confirm unload capability. If valve works, problem is electrical.
SLIDE VALVE WILL UNLOAD BUT
A side solenoid coil may be burned out. Replace.
WILL NOT LOAD
Dirt inside solenoid valve preventing valve from operating both ways. Clean.
Check LED on coil. If lit, valve is functioning mechanically. Problem is electrical.
Solenoid may be actuated mechanically by inserting a piece of 3/16" rod
against armature pin and pushing spool to opposite end. Push A side to
confirm unload capability. If valve works, problem is electrical.
SLIDE STOP WILL NOT FUNCTION
Solenoid coils may be burned out. Replace.
EITHER DIRECTION
Solenoid service valves may be closed. Open.
Manually actuate solenoid. If slide stop will not move mechanical problems
are indicated. Consult Frick factor or Frick service.
TROUBLESHOOTING THE LIQUID INJECTION OIL COOLING SYSTEM
SYMPTOM
PROBABLE CAUSES and CORRECTIONS
HIGH OIL TEMPERATURE
Insufficient liquid supply. Check receiver level and pressure drop at injection solenoid.
Equalizer pressure too high. Lower.
Suction superheat too high. Correct system problem.
Thermal valve power head lost charge. Replace.
Liquid strainer blocked. Clean.
Liquid solenoid coil failed. Replace.
Excessive load. Thermovalve undersized. Reduce load or install larger thermovalve.
LOW OIL TEMPERATURE
Equalizing pressure too low. Raise.
Suction superheat too low or liquid coming back on compressor. Correct
system problem.
Low load conditions. Valve oversized. Increase load or use smaller thermovalve.
OIL TEMPERATURE FLUCTUATES
System conditions rapidly fluctuate causing liquid injection system to overrespond.
Stabilize system operation.
Содержание RWF
Страница 37: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 37 P I DIAGRAM ...
Страница 40: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 40 P I DIAGRAM LIQUID INJECTION BOOSTER ...
Страница 47: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 47 OPERATING LOG SHEET ...
Страница 53: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 53 ...
Страница 54: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 54 ...
Страница 55: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 55 ...