RWF ROTARY SCREW COMPRESSOR UNITS
MAINTENANCE
S70-600 IOM
Page 26
MAINTENANCE SCHEDULE
OPERATING LOG
The use of an operating log as included in this manual (see Table of Contents) permits thorough analysis of the operation of a
refrigeration system by those responsible for its maintenance and servicing. Continual recording of gauge pressures, tempera-
tures, and other pertinent information, enables the observer and serviceman to be constantly familiar with the operation of the
system and to recognize immediately any deviations from normal operating conditions. It is recommended that readings be taken
at least every four hours.
This schedule should be followed to ensure trouble-free operation of the compressor unit.
CLEAN OIL STRAINERS
CLEAN LIQUID
STRAINERS
REPLACE FILTER
REPLACE COALESCER
CHECK AND CLEAN
SUCTION STRAINER
95000
90000
85000
80000
75000
70000
65000
60000
55000
50000
45000
40000
35000
30000
25000
20000
15000
10000
8000
5000
1000
200
MAINTENANCE
FREQUENCY OR HOURS OF OPERATION (MAXIMUM)
CHANGE OIL
As directed by oil analysis
OIL ANALYSIS
Then every 6 months
VIBRATION ANALYSIS
Every 6 months, more frequently if levels increase
REPLACE SEAL
When leak rate exceeds 7 - 8 drops per minute
CHECK COUPLING
Содержание RWF
Страница 37: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 37 P I DIAGRAM ...
Страница 40: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 40 P I DIAGRAM LIQUID INJECTION BOOSTER ...
Страница 47: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 47 OPERATING LOG SHEET ...
Страница 53: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 53 ...
Страница 54: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 54 ...
Страница 55: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 55 ...