RWF ROTARY SCREW COMPRESSOR UNITS
MAINTENANCE
S70-600 IOM
Page 28
6. Measure the voltage of PE-1 on connector P4 (termi-
nals WHT and BLK) on the SBC.
7. The voltage reading should be between 1.1 VDC and
1.29 VDC at standard atmospheric pressure. PE-1, PE-2,
and PE-3 all have a span of 500 PSI as compared to PE-4
with a span of 200 PSI. Therefore, atmospheric pressure
changes have a lesser effect which is 0.0067 VDC per 1000
feet of elevation and 0.00067 VDC per 0.1 inch Hg baromet-
ric deviation.
8. Isolate transducer PE-2 from the package and depres-
surize. NOTE: Recover or transfer all refrigerant vapor,
in accordance with local ordinances, before opening to
atmosphere.
9. Measure the voltage of PE-2 on connector P4 (termi-
nals WHT and BLK) on the SBC.
10. The voltage reading should be between 1.1 VDC and
1.29 VDC at standard atmospheric pressure (see Step 12).
11. Since the discharge pressure, PE-3, cannot be closed
off from its sensing point (code requirements), close all trans-
ducers from atmosphere and open them to their sensing
points so all transducers can equalize to separator pres-
sure.
12. Measure the voltage of PE-3 on connector P4 (termi-
nals WHT and BLK) on the SBC.
13. Measure the voltage of PE-1 on connector P4 (termi-
nals WHT and BLK) on the SBC.
14. These two voltages should be within .04 VDC of one
another.
15. Test is complete.
PRESSURE TRANSDUCERS -
REPLACEMENT
1. Shut off control power.
2. Close the applicable transducer isolation valve. NOTE:
To change the discharge pressure transducer (PE-3), it
will be necessary to depressurize the entire compres-
sor package. Follow "General Instructions For Replac-
ing Compressor Unit Components" before going to
step 3.
3. Refer to the WIRING HARNESS section, External Trans-
ducers for Board #1, to identify the wiring har ness
connectors.
4. Loosen screw and disconnect wiring harness connector
from transducer.
5. Unscrew the transducer using a wrench on the metal hex
at the base of the transducer. DO NOT ATTEMPT TO
LOOSEN OR TIGHTEN TRANSDUCERS BY THEIR TOP
CASING.
6. Install new transducer.
7. Reconnect the wiring harness to the transducer.
8. Reopen the transducer isolation valve.
9. Turn on control power.
*
Below 0 PSIG measured in inches of mercury.
PRESSURE TRANSDUCER CONVERSION DATA
200 psi
500 psi
Sensor
Range - PSI
Range - PSIG*
Voltage
low
high
low
high
1.0
29.92"
9.57"
29.92"
4.10
1.1
29.92"
0.30
29.92"
16.60
1.2
29.92"
5.30
17.10"
29.10
1.3
19.74"
10.30
4.10
41.60
1.4
9.57"
15.30
16.60
54.10
1.5
0.30
20.30
29.10
66.60
1.6
5.30
25.30
41.60
79.10
1.7
10.30
30.30
54.10
91.60
1.8
15.30
35.30
66.60
104.10
1.9
20.30
40.30
79.10
116.60
2.0
25.30
45.30
91.60
129.10
2.1
30.30
50.30
104.10
141.60
2.2
35.30
55.30
116.60
154.10
2.3
40.30
60.30
129.10
166.60
2.4
45.30
65.30
141.60
179.10
2.5
50.30
70.30
154.10
191.60
2.6
55.30
75.30
166.60
204.10
2.7
60.30
80.30
179.10
216.60
2.8
65.30
85.30
191.60
229.10
2.9
70.30
90.30
204.10
241.60
3.0
75.30
95.30
216.60
254.10
3.1
80.30
100.30
229.10
266.60
3.2
85.30
105.30
241.60
279.10
3.3
90.30
110.30
254.10
291.60
3.4
95.30
115.30
266.60
304.10
3.5
100.30
120.30
279.10
316.60
3.6
105.30
125.30
291.60
329.10
3.7
110.30
130.30
304.10
341.60
3.8
115.30
135.30
316.60
354.10
3.9
120.30
140.30
329.10
366.60
4.0
125.30
145.30
341.60
379.10
4.1
130.30
150.30
354.10
391.60
4.2
135.30
155.30
366.60
404.10
4.3
140.30
160.30
379.10
416.60
4.4
145.30
165.30
391.60
429.10
4.5
150.30
170.30
404.10
441.60
4.6
155.30
175.30
416.60
454.10
4.7
160.30
180.30
429.10
466.60
4.8
165.30
185.30
441.60
479.10
4.9
170.30
190.30
454.10
491.60
5.0
175.30
195.30
466.60
504.10
At 0 psig
1.094 V
1.494 V
0.968 V
1.268 V
Содержание RWF
Страница 37: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 37 P I DIAGRAM ...
Страница 40: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 40 P I DIAGRAM LIQUID INJECTION BOOSTER ...
Страница 47: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 47 OPERATING LOG SHEET ...
Страница 53: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 53 ...
Страница 54: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 54 ...
Страница 55: ...RWF ROTARY SCREW COMPRESSOR UNITS MAINTENANCE S70 600 IOM Page 55 ...