140.960-IOM (JUN 2016)
Page 10
IDCF & IDC3 EVAPORATIVE CONDENSERS
INSTALLATION
MODEL NUMBER
H (DISTANCE FROM LIFT
POINT TO LIFTING DEVICE)
IDCF-0406
4’
IDCF-0412
6’
TABLE 3. DISCHARGE SOUND ATTENUATION LIFT DIMENSIONS
Discharge
Sound
Attenuation
Detail A
Figure 15 – Discharge Sound Attenuation Installed
3/8” x 1 1/4” Bolt
3/8” Flatwasher
3/8” Locknut
NOTICE
Discharge sound attenuation can be added at the time of
order or as an aftermarket item.
Fan Cowl Extensions
Each fan cowl extension is 10 1/2” tall and up to four fan cowl
extensions may be installed.
1. Fasten the fan cowl extensions through the large diameter
pre-punched holes using the provided hardware as shown
in Figure 16, Detail A.
2. Follow “Fan Guard Installation” instructions to install the
fan guard.
NOTICE
Fan cowl extensions can be added at the time of order or
as an aftermarket item.
OPTIONAL ACCESSORY INSTALLATION
Bottom Water Outlet
1. The bottom connection seal, Figure 13, is typical for all bot-
tom remote sump outlets, and bypasses. Flange mounting
hardware and gasket to be supplied by others.
2. Bottom connection seal kit(s) ship in plastic tubs.
NOTICE
Some parts that ship loose are labeled with unique three
key codes for identification purposes. These three key
codes are referenced throughout this guide to identify
parts to be assembled in the field.
Cold
Water
Basin
Backup
Ring
2 1/4” OD
Gasket
Gasket Provided by Others
Hardware Provided
by Others
Figure 13 – Bottom Water Outlet
Discharge Sound Attenuation (IDCF Option Only)
1. Verify the mounting frame and clips are factory installed as
shown in Figure 14.
2. Lower the attenuator into position by aligning the bolt
holes on the attenuator with the pre-existing bolt holes on
the mounting clips. Be sure to follow the minimum height
restrictions H found in Table 3 between the top of the dis-
charge sound attenuation and the apex of the crane cables
supporting the load.
Lift image
not to scale
Mounting
Clips
Mounting
Frame
H
Figure 14 – Sound Attenuation Clip Placement And Lift