2201 Cantu Court Suite 215 Sarasota, FL 34232 Page 10 of 23
(941) 378-4242 (800-237-3928 Fax (941) 378-2765
Stewartsigns.com
5.
Configuring the “IP Setup” for the RF MODEM that will be installed in your Sign.
See figure #14.
a.
Click on “
IP Setup
”. The IP Setup Window will be displayed. See figure #14.
b.
Enter the IP Address as 192.168.1.51.
c.
Enter the Subnet Mask as 255.255.255.0.
d.
Enter the Default Gateway as 192.168.1.1.
e.
Leave the “Web Page Port” unchanged at 80.
f.
Click on “
Save/Apply
” to save your settings
g.
Record the IP Addresses for each Transceiver on a piece of paper and tape it to the
Transceiver for future reference.
Figure #14 IP Setup Window (Sign Unit)
Configuring the “Serial Setup 1”. See figure #15.
1.
Open your Web Browser and type the IP Address into in the address bar of this
Transceiver.
(You programmed this in the previous step).
See figure #2.
1.
You will be prompted for a user name and password the default username for the
Administrator login is ‘
admin
’, the password is ‘
admin
.’ See figure #3.
2.
Click on “
Serial Setup 1
”. The Serial Setup 1 window will be displayed.
3.
Under “
Mode
” Select “TCP
Server
”
4.
Enter
“3001”
in the box Labeled “
Port”.
5.
Change the “
Baud Rate
” to
115,200.
6.
Click on “
Modbus RTU
” to Enable.
7.
Click on “
Save/Apply
” to save your settings.