DFA400 Rev0708

26

CALIRBRATION

The  flowmeter  is  precalibrated  and  tested  at  the  factory.  Plumbing  systems 

are always unique and may cause small deviations in the factory calibration. It is 

recommended that the flowmeter is checked after installation for accuracy and calibrated 

when necessary.

Review  the  Programming  Section  procedures  for  using  the  Program Access 

Mode.

Error Code E204

If error code E204 is shown, there is no signal from the flow sensor. This code 

is displayed only when in a calibration program. Troubleshoot the sensor and the 

associated wiring.

Note:

 To calibrate the flowmeter, use a precalibrated water flow test kit 

(connected to the discharge according to the instructions provided) or a 

pitot gauge as a reference.

Flow Calibration, Single Point (Code 321)

Select a flow rate for calibration that is within the most commonly used discharge 

flow range.

1.  Enter code 321.
  Result: The digital display shows flow rate with the last digit flashing.
2.  Flow water through the discharge at the flow rate selected for calibration. 

Ensure a constant pressure is maintained to obtain a steady flow rate.

3.  Adjust the displayed flow rate to match the reference flow rate.
  The 

MODE

 button selects the digit to change. The digit will flash.

  The 

TOTAL

 button changes the value of the flashing digit.

4.  To exit the calibration program:
  Press both the 

MODE

 and 

TOTAL

 buttons and hold them until the display 

shows four dashes. Release the buttons and enter a new code, or after five 

seconds the program  times out and returns to normal operation.

5.  Vary the water flow through the discharge and ensure the flow rate displayed 

matches the reference. If there are differences at other flow rates, the multiple 

point calibration may be necessary.

Содержание DFA400

Страница 1: ...ev0708 1 FIRE RESEARCH CORPORATION www reresearch com 26 Southern Blvd Nesconset NY11767 TEL 631 724 8888 FAX 631 360 9727 TOLL FREE 1 800 645 0074 DIGITAL FLOWMETER MODEL DFA400 Document Number XE DF...

Страница 2: ...8 Install Display Module 8 Install Flow Sensor 10 OPERATION 16 Datalink Interface 16 Program Features 17 TOTAL Button 17 PROGRAMMING 18 Inputs 18 Display Module Identi cation Mode 18 Program Access M...

Страница 3: ...List of Figures Figure 1 Controls and Indicators 7 Figure 2 Display Module Mounting Dimensions 8 Figure 3 Flow Sensor Location Guide 11 Figure 4 Saddle Clamp Installation 13 Figure 5 Weldment Installa...

Страница 4: ...processed and shown on the digital display There are two operator selectable modes display module identi cation and program access In the display module identi cation mode the digital display shows th...

Страница 5: ...Module SupplyVoltage 9 to 30 VDC Current 1 5 Amps Maximum Dimensions Height 3 1 4 Width 3 1 4 Depth 2 Flow Sensor Model Number XE MF15P Type Paddlewheel Sensor Material Acetal Delrin with Stainless St...

Страница 6: ...ocated on the front of the display module Refer to Controls and Indicators Paddlewheel Flow Sensor The ow sensor provides an input signal to the display module proportional to discharge ow rate It is...

Страница 7: ...on The MODE button accesses the display module identi cation mode It is used with the TOTAL button to input data when in the program access mode Refer to Programming Section for more information TOTAL...

Страница 8: ...d mark mounting location for display module panel cutout and mounting screw holes Make sure there is clearance behind the panel for the display and cables before cutting holes Refer to Figure 2 for la...

Страница 9: ...DFA400 Rev0708 9 This page intentionally left blank...

Страница 10: ...stream to stabilize into a uniform ow Guidelines for selecting ow sensor locations are outlined in Figure 3 Turbulent Water When the ow sensor is mounted after an area in the plumbing that tends to in...

Страница 11: ...after the pipe diameter is reduced length L must be at least 2 times the pipe diameter When mounting a sensor after a valve length L must be at least 14 times the pipe diameter When mounting a sensor...

Страница 12: ...osition It is not meant to be removed 3 Place saddle clamp over hole with sensor housing centered 4 Tighten saddle clamp nuts until gasket makes a tight seal 5 Insert ow sensor into sensor housing Ali...

Страница 13: ...e sure the ow sensor engages the alignment tab and does not rotate Note Dimensions are typical and are an aid to determine ow sensor mounting locations Pipe Size Dimensions Sch 40 A B C 2 5 5 3 9 2 9...

Страница 14: ...the pipe centerline Refer to Figure 5 4 Set sensor housing to dimension A in Figure 5 Make sure alignment tab is centered on the pipe as shown it can be on upstream or downstream side 5 Install tru s...

Страница 15: ...ke sure the ow sensor engages the alignment tab and does not rotate Note Allow a minimum of 2 inches clearance above the sensor for connector removal installation Make sure that the alignment tab is c...

Страница 16: ...datalink When programmed with Id 1 to Id 99 it provides information via the datalink to remote summing and accumulator displays Remote Display Module Remote displays are programmed with the module fu...

Страница 17: ...harge or reset the totalized ow value to 0 if totalizer reset function is set to YES Display Total Flow When the TOTAL button is pressed and released the digital display shows the total accumulated ow...

Страница 18: ...changes the digit or option choice Display Module Identi cation Mode When in the module identi cation mode the digital display shows the module serial number manufactured date software revision funct...

Страница 19: ...ssed the number increments by 1 Set the rst digit to the desired number 3 Press the TOTAL button The second digit ashes Each time the TOTAL button is pressed the number increments by 1 Set the second...

Страница 20: ...ltiple Point 9 Calibration Points 340 CAN Terminator On Off E202 Invalid Program Code Entered Re Enter Code E204 No Flow Sensor Signal Check Water Flow and Wiring E206 Invalid Calibration Point Select...

Страница 21: ...DFA400 Rev0708 21 This page intentionally left blank...

Страница 22: ...Options 0 to 99 This code sets the datalink identi cation ID number for the display module The display is programmed with an ID number between 0 and 99 When a display module is programmed with Id 0 no...

Страница 23: ...inues to accumulate and does not reset to 0 even when power is removed Code 318 Flow Cutoff Frequency Factory programmed value c 30 Options 0 to 99 9 Hz This code sets a cutoff frequency for the ow se...

Страница 24: ...ctory programmed value No Values Entered Options 9 Calibration Points This code starts the calibration program for multiple ow rates This function is used when the ow sensor is installed in a dif cult...

Страница 25: ...less than 5 difference between two calibration points Select a different point to continue with the calibration procedure Error Code E208 There is a failure with the internal memory of the module Cont...

Страница 26: ...le Point Code 321 Select a ow rate for calibration that is within the most commonly used discharge ow range 1 Enter code 321 Result The digital display shows ow rate with the last digit ashing 2 Flow...

Страница 27: ...ure a constant pressure is maintained to obtain a steady ow rate 3 Press the MODE button Result The display shows ow rate with the last digit ashing 4 Adjust the displayed ow rate to match the referen...

Страница 28: ...and the datalink connection pins 7 and 8 to the primary display A remote display must be programmed with the same ID number as the primary display Figure 6 Display Module Wiring 8 Pin Connector Cable...

Страница 29: ...nsor Figure 7 Flow Sensor Wiring Sensor Cable 3 Pin Connector Pin Wire Description A Black Ground B Red Supply Voltage C White Signal Signal Output Supply Voltage Ground Sensor Cable from 8 Pin Connec...

Отзывы: