QUICK INSTALLATION GUIDE (FHP)
3
Installation Method
aPower X supports floor-mounted installation and wall-mounted installation. A mounting bracket
is required to hold the equipment to the wall.
aGate X may be wall mounted or embedded in the wall.
Installation Space
•
aGate X:
There should be a minimum clearance of 5D (D is the outer diameter of electrical conduits)
from the aGate X bottom to the floor and from the top of the aGate X to the ceiling. The
recommended distance between the bottom of the aGate X and the ground is 48 in. (1.22m)
and should not exceed 64 in. (1.63m). The maximum distance between the power switch
button on the aGate X and the ground shall not exceed 90 in. (2.29m). Please finalize the
installation height in accordance with the specific site conditions.
•
aPower X:
There should be a minimum clearance of 5D (D is the outer diameter of electrical conduits)
from the top of aPower X to the ceiling.
When the aPower X is mounted on the wall, the recommended distance between the bottom
of mounting bracket and the ground is 19.7 in. (0.5m), but not exceed 54.25 in. (1.38m). The
maximum distance between the switch button on the aPower X and the ground shall not
exceed 90 in. (2.29m).
The recommended distance between multiple aPower X units is 12 in. (0.3m), with a minimum
of at least 6 in. (0.15m).
•
The recommended space distance in front of the wall in the installation area is 72 in.(1.83m).
Recommended
72in.(1.83m)
aGate X
aPower X
aPower X
aPower X
Recommended
12in.(0.3m)
Minimum
6in.(0.15m)
≥
5D (D is the outer diameter of electrical conduits)
Recommended
48in.(1.22m)
≥
5D (D is the outer diameter of electrical conduits)
Recommended
12in.(0.3m)
Minimum
6in.(0.15m)
Recommended
12in.(0.3m)
Minimum
6in.(0.15m)
The distance between the bottom
of mounting bracket and the ground
is not exceed 54.25 in. (1.38m).