QUICK INSTALLATION GUIDE (FHP)
13
Power Wiring Diagram
•
Solar Inverter Connections to the aGate X
•
Smart Circuit Connections to the aGate X (Optional)
NOTE:
All breakers are to be provided by installer or customer.
L1
L2
Neutral
Ground
L1
L2
Ground
Neutral
According to NFPA 70-250 Grounding and
Bonding Part V, when installed as service
equipment, the neutral and ground should be
bonded together as shown in the picture on
the left. The Neutral-Ground Bonding Jumper
must only be removed if not installed as
service equipment or for test purposes.
WARNING:
➢
The solar circuit breaker is
the only interface for the
solar inverter to be
connected to the aGate X.
➢
The aGate X has a built-in
solar CT.
2 pole
2 pole
L2
L2
L1
L1
Neutral
Ground
L2
L2
Neutral
Ground
L1
L1
1 pole
1 pole
2 pole
or