background image

2.4.

The chimney

The chimney must be in good condition free from cracks

and blockages and should not have an excessive cross

sectional area. If problems are encountered expert

advice should be sought regarding the necessity of

having the chimney lined. Should it be found necessary

to line the chimney, a lining suitable for solid fuel must

be used. If the appliance is to be fitted in a room where

there is no existing chimney a prefabricated block

chimney or a twin walled insulated stainless steel flue to

B.S 4543 can be used either internally or externally. The

internal diameter must not be less than 150 mm (6

inches). These flues must be fitted in accordance with

the manufacturers instructions and Building

regulations.

Before connecting the appliance to an existing flue, the

flue must be swept and checked. In order for the

appliance to perform satisfactorily the chimney height

should not be less than 5 metres measured vertically

from the outlet of the stove to the top of the flue terminal.

Should there be excessive draught in the chimney it

may be necessary to fit a draught stabliliser.

2.5.

Chimney connection

No combustible materials may be set closer than at

least 450 mm clearance.

A 150 mm diameter flue pipe will be required to connect

the stove to the chimney. Make sure the flue pipe is

suitable for solid fuel (cast iron, stainless steel, vitreous

enamelled steel). Under no circumstances should

flexible or asbestos pipe be used.

Too long horizontal smoke pipe may dangerously

restrain the running of the appliance (do not exceed 0,3

m in length). The connecting flue should not exceed 1,8

m in length. Greater lengths should be completed by

using twin-walled insulated chimney.

Ensure the flue pipe extends into the chimney but not so

far that it blocks air flow.

Ceiling or wall penetration should always be made with

insulated pipe and the proper accessories.

Allow fire cement to dry properly before lighting the

stove. Stove running and chimney being hot, check if

chimney draught is at least 10 Pa (1 mm w.g.) at normal

rate and 15 Pa (1,5 mm w.g.) at maximum rate.

If chimney draught is too excessive, a flue stabiliser

should be installed on the flue pipe or on masonry

chimney so as to avoid the introduction of cold air into

the chimney.

2.6.

Water connections

With add-in boiler C 22.03.01 or C 22.07.01

FRANCO-BELGE recommends that the installation is

carried out by a qualified heating engineer who is fully

experienced in solid fuel heating installations.

Must be provided (fig. 5) :

-

an expansion tank open to the atmosphere,

-

an indirect cylinder,

-

a gravity circulation to one radiator to dissipate heat

when the pump is off,

-

the fitting of a low limit thermostat to the primary return

to ensure the pump does not operate when return

water temperatures are less than 50 ° C,

-

a drainage tap in the return flow.

2.7.

Check list before lighting stove

-

check that all firebox parts (grates, flue baffle and

refractory bricks) are correctly fitted and that the

oscillating grates move correctly when operated

-

check the appliance for soundness of seals between

casting (flue collar, blanking plates, loading doors,

etc...)

-

check the connection between the appliance and the

chimney flue for air tightness

-

check if there is enough water in the heating system

and check the connections for water leaks

-

after lighting up the stove, check if it operates correctly

under fire, check for soundness of seals, leave the

appliance operational with the heating system

correctly balanced, hand over user instructions.

2.8.

Adjustment of the thermostat

The thermostat has been set in the factory. If it becomes

necessary to make adjustments or fit a new thermostat,

the following procedure should be followed (see fig. 6) :

-

ensure the appliance is cold,

-

remove the rear metal heat shield,

-

set the thermostat adjustment lever at position «

8

»

(fully open),

-

adjust the position of the screw on the lever arm to

provide a gap of 50 mm,

-

set the thermostat adjustment lever at position «

1

»

(fully closed),

-

refit the rear metal heat shield.

Notice de référence “316”

5

Lorraine MF/Alsacien - réf. 124 13 01

Installation instructions

Figure 5 - Water connections

Figure 6 - Adjustment of the thermostat

Lever arm

Screw

Damper

Содержание Lorraine MF 124 13 01

Страница 1: ...E Head Office Address 2 rue Saint Gilles 68230 TURCKHEIM RC Colmar SIREN 439 330 325 Address Administration and manufacturing BP 73 59660 MERVILLE FRANCE Telephone 00 333 28 43 43 43 Fax 00 333 28 43...

Страница 2: ...collar and the blanking plates 4 Installation 4 Siting the stove 4 The chimney 5 Chimney connexion 5 Water connections 5 Check list before lighting stove 5 Adjustment of the thermostat 5 Instructions...

Страница 3: ...on The Lorraine MF is designed for operation with the door closed Heat is mainly diffused by radiation through the window and body of the appliance Adjustable air controls with thermostat for controll...

Страница 4: ...fire cement contacting the skin The material is caustic and in the event of contact being made wash off immediately with clean water Electrical If electrical components are to be used in the installat...

Страница 5: ...mney draught is at least 10 Pa 1 mm w g at normal rate and 15 Pa 1 5 mm w g at maximum rate If chimney draught is too excessive a flue stabiliser should be installed on the flue pipe or on masonry chi...

Страница 6: ...etc pollutes the environment pollution and smell etc and cause the fire to burn too quickly and overheat Green wood and recovered wood can eventually cause a chimney fire Prohibited fuel Any form of b...

Страница 7: ...t replace broken glass with substitute materials Consult your usual FRANCO BELGE supplier 3 7 Flue cleaning and summer time The chimney and the connecting flue pipe must be swept a least once a year A...

Страница 8: ...ntry offcuts plywood pallets etc Smokes when lighting up Flue duct is cold Burn paper and kindling wood to increase heat Room is in decompression In houses equipped with mechanical ventilation partly...

Страница 9: ...L K 14 300105 59 Leg 02 Y 14 300105 77 Leg 02 L 14 300105 76 Leg 02 K 15 300217 59 Leg 02 Y 15 300217 77 Leg 02 L 15 300217 76 Leg 02 K 16 300462 Base Plate 01 Y L K 17 301146 Ash pan door 01 Y 17 30...

Страница 10: ...01 Y 37 988737 Left door complete 01 L 37 988738 Left door complete 01 K 38 303508 Right door 01 Y 38 303508 77 Right door 01 L 38 303508 76 Right door 01 K 39 309944 Left door 01 Y 39 309944 77 Left...

Страница 11: ...Notice de r f rence 316 11 Lorraine MF Alsacien r f 124 13 01 List of components...

Страница 12: ...ident or wear tear 6 In the event of a problem before making any claim on this guarantee please ensure that the appliance has been installed and commissioned correctly and that the chimney is operatin...

Страница 13: ...eption of closed combustion fireplace and inserts for which our guarantee is 5 five years excluding the following 1 Indicator lights fuses electrical elements and fans 2 Parts subject to wear or in co...

Отзывы: