CHAPTER 8: TROUBLE SHOOTING
In the following pages are reported the most common troubles that can cause the unit to stop or to operate in
an uncorrect way.
Concerning the solutions, it is necessary to take an extreme care on the actions to adopt: an
excessive confidence may cause serious accidents to inexperienced people. It is advisable, once
the cause is detected, to contact our servicing people or trained people only.
8.1 UNIT UNDER ALARM
When red light is lit up, the unit is stopped and set under alarm condition.
To restore normal operating mode, it is necessary to detect and remove the cause of the alarm
PROBLEM
LED ON
PROBABLE CAUSE
CORRECTIVE ACTION
A
Unit does not
start
but alarm green
led
is off
None
Power supply missing
Provide power supply,
replace fuses
Power supply
led
Humidistat on set
Set a lower set point
Power supply
led,
Compressor thermal
protection enabled,
compressor defective
Let the compressor cool
down, replace compressor
defective
Power supply
led,
Compressor thermal
protection enabled,
compressor defective
fan defective
Let the compressor cool
down, replace compressor
defective, replace fan
defective
Any led
Electronic board or led
Board defective
Replace defective board