3.2.3 Remote humidistat connections
Remote humidistat connection must be realised according with electric diagram.
Connections must be done according to the electric wiring diagram specifications.
3.3 CONNECTION TO THE CONDENSED WATER DRAINAGE FITTING
Connect condensed water drainage fitting (¾’’ M) to a draining pipe.
It should be always avoided to form a doubble siphon, which could obstruct the water flowing with the
consequent risk of flooding the area.
3.4
DUCTWORK UNIT CONNECTION (see pag.5 for airflow performances)
All the units are provided with a centrifugal fan that can be ducted.
If only one side should be ducted, a flanged connection with overall dimensions larger than discharge hole
should be used.
If either suction side should be ducted, remove suction air filter and its panel, use a flanged connection with
overall dimensions larger than suction hole located on the front of the unit and install an air filter into the
suction ductwork.
It is very important to install an air filter into the suction ductwork if the filter of the machine
itself has been removed . If this filter should not be present, serious damage could occur to the
units.