![frako EMG 1500-PN Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/frako/emg-1500-pn/emg-1500-pn_operating-manual_2326329004.webp)
Quick start
EMG 1500 Operating Manual
4
1. Quick start
•
Before installation:
The EMG 1500-PN only requires the serial interface in order to
assign the IP address. It can therefore make life easier to do this
before the instrument is installed in the control cabinet.
⇒
The instrument is connected according to the wiring diagram
Figure 1 on page 6. Only the connection to the power supply is
needed.
⇒
The EMG 1500-PN is connected to the PC by a null-modem
(crossover) cable (see Section 3.2.4, page 8).
The software EMG-SW is used to carry out all network settings
i.e. IP address, subnet mask and gateway.
(see Section4.3, page 9)
⇒
The supply voltage must then be removed from the instrument.
•
Installation:
⇒
The instrument is mounted by snapping it over a DIN rail.
⇒
The instrument is connected according to the wiring diagram
Figure 1 on page 6.
Important:
The instrument must be disconnected from the power supply
when being installed or serviced.
•
Commissioning:
If the instrument has not yet been assigned an IP address, this
procedure must be carried out as described above under
“ Before installation”.
⇒
If appropriate, the bus address must be adapted for the FRAKO
Starkstrombus
®
. The factory default setting is Bus Address 1
(see Section 4.4, page 11).