frako EM-PQ 2300 Скачать руководство пользователя страница 17

Installation 

 

Operating Manual EM-PQ 2300 

 
 
 

17 

 

 

DANGER! 

Live current transformer circuits must never be interrupted. There is a danger that arcing may 
occur, which could cause burns or electric shock. 

The secondary-side connections of the current transformers must be short-circuited at the 
transformers before the circuits to the EM-PQ 2300 are interrupted!  
Exceptions: If the current transformers in use are equipped with internal open circuit protectors in 
good working order in the secondary circuits, or if a test switch that automatically short-circuits the 
current transformer secondary side is fitted. In the latter case, it is essential that the correct 
functioning of the short-circuiting switch has been verified before it is then left in the 

‘Test’ position 

for any work on the circuit. 

Note: Modern current transformers installed in power systems are, as a rule, equipped with an 
internal open circuit protector, which acts to protect the secondary circuit upon this being opened. 
However, it is absolutely essential that the presence of an open circuit protector in good working 
order be verified before a current transformer secondary circuit is opened. 

A safe procedure is to short-circuit the secondary side on the current transformer side of the 
terminals to be opened. 

 

 

DANGER! 

Live current transformer circuits must never be interrupted. There is a danger that arcing may 
occur, which could cause burns or electric shock. 

The retaining screws on the sides of the connectors for the current transformer circuits must 
always be tightened before the instrument is put into service.  

Tightening these retaining screws prevents the connectors from accidentally working loose and 
therefore reduces the risk of arcing. 

 

DANGER! 

If an earth terminal is provided at the secondary side of the current transformer, this must be 
connected to an earthing conductor! 

 

 

CAUTION!  

The following must be observed to ensure safe and reliable operation: 

 

The connection of the current measurement inputs must be via an external, electrically 
isolating current transformer. 

 

Overloading of the current transformers incorporated in the instrument must be avoided. 
The maximum allowable continuous current is 6 A AC; transient peaks 10 A. 

These measures must be taken to ensure that the instrument is not damaged.

 

The EM-PQ 2300 can measure five AC currents, whose respective inputs are electrically isolated from each 
other. See 

Section 2, Technical data, page 7

 for the measurement ranges. 

The currents in the phases L1, L2 and L3, plus those in the neutral conductor N and the protective earth 
conductor PE, are measured via external current transformers. Instead of the protective earth another conductor 
can also be connected, provided that its parameters are within the range specified in 

Section 2, Technical data, 

page 7

The terminals 

L1 

– S1-S2

L2 

– S1-S2,

 

L3 

– S1-S2, 

–S1-S2

 and 

Lx 

– S1-S2

 must be connected as shown in the connection 

diagram Fig. 5 on page 14. This shows the 3-phase connections with the 
additional measurements in the N and PE conductors. 

Unassigned current measurement inputs can be left unconnected. 

Содержание EM-PQ 2300

Страница 1: ...Power Quality Analyzer EM PQ 2300 Operating Manual FRAKO Kondensatoren und Anlagenbau www frako com Figure 1 Front view of the EM PQ 2300 with the optional EM FD 2500 Display...

Страница 2: ...1 5 1 7 Analog OUT 1 2 21 5 1 8 Digital IN 1 2 Trigger IN tariff switching 21 5 1 9 Temperature IN 22 5 1 10 Alarm 22 6 Commissioning initial start up 23 6 1 Safety precautions before start up 23 6 2...

Страница 3: ...ement page 32 8 1 9 Display Energy meter page 32 8 1 10 Display Big display page 32 8 1 11 Display big display page Current page 32 8 1 12 Display big display page Voltage page 32 8 1 13 Display big d...

Страница 4: ...Article No 2278555 page 10 Figure 3 Dimensions page 11 Figure 4 Retracting the retaining clips page 12 Figure 5 3 phase connection diagram page 14 Figure 6 Single phase connection diagram page 14 Fig...

Страница 5: ...must again be isolated from the power supply Do not expose the instrument to direct sunlight or high temperatures as these could damage it or shorten its service life Do not install the instrument nea...

Страница 6: ...ted If the EM PQ 2300 is used in a way not specified in this operating manual the protection supported by the instrument may be adversely affected 1 4 Repair Repairs may not be carried out by the cust...

Страница 7: ...easurement range 50 200 C resolution 1 C Earth connection commoned with the digital outputs digital inputs and analogue outputs Active from hardware v1 8 and firmware v1 72 Outputs Digital outputs 2 S...

Страница 8: ...mm min 0 14 mm 2 Insulation rating 50 V DC 80 C Digital IN 1 2 Conductor cross section max 1 4 mm min 0 14 mm 2 Insulation rating 50 V DC 80 C Analog OUT 1 2 Conductor cross section max 1 4 mm min 0...

Страница 9: ...0 4 6 immunity to conducted disturbances level 10 V RMS 150 kHz 80 MHz EN 61000 4 4 burst immunity 1 kV capacitive coupling 2 kV injection into power supply cable and voltage measurement inputs EN 610...

Страница 10: ...EM MC 2200 Maximum Optimizer instruments mounted next to each other on the same DIN rail to be automatically connected to each other It is therefore no longer necessary to wire these connections sepa...

Страница 11: ...the Ethernet cable and the type of connector used 4 2 Installing the instrument The EM PQ 2300 is intended for fixed installation in control cabinets or enclosures see Section 4 1 Suitable location pa...

Страница 12: ...It is therefore not permitted to connect with other types of DIN rail bus connectors from other manufacturers 5 Installation Prerequisite the instrument has been correctly fitted to the DIN rail as de...

Страница 13: ...adequate for the purpose Suitable measures must be taken to prevent cables operating at the power supply voltage being inadvertently pulled out and twisted A disconnecting device such as an isolator o...

Страница 14: ...14 Figure 5 3 phase connection diagram Figure 6 Single phase connection diagram...

Страница 15: ...ency 45 65 Hz or 100 360 V DC absolute limits It is connected to terminals L and N as shown in the diagrams Figure 5 or Figure 6 page 14 CAUTION The cables leading to the instrument must be permanentl...

Страница 16: ...y advisable when the phases are symmetrically loaded since as a rule the phase neutral voltages here are near to each other in value NOTE The voltage measurement inputs not in use must be commoned wit...

Страница 17: ...screws on the sides of the connectors for the current transformer circuits must always be tightened before the instrument is put into service Tightening these retaining screws prevents the connectors...

Страница 18: ...n between a PC and the EM PQ 2300 using either an EMIS 1500 Central Unit data collector and bus coupler or an EMG 1500 PN Gateway Ethernet bus coupler This is a practical solution if the FRAKO Starkst...

Страница 19: ...nded cable types Surge impedance 100 120 0 5 mm shielded twisted pairs Types IBM Twinax EIB bus cable Lapp Unitronic J 2Y ST Y Siemens YCYM 4 2 0 8 or PYCYM 4 2 0 8 NOTE A mixing of different cable ty...

Страница 20: ...p lines and star topologies are not permitted The total length of the bus must not exceed 40 m See Section 5 1 5 2 Cable types below for the cable types to be used and their limitations At the beginni...

Страница 21: ...pulses as per DIN 43864 which can be used to transmit status codes The assignment of status codes to the digital outputs is carried out using the FRAKO configuration software Device Manager For techni...

Страница 22: ...nfiguration being possible If a 2 wire configuration is used each outer connection must be commoned with the inner connection next to it For technical data see Section 2 Technical data page 7 for conf...

Страница 23: ...tarts flashing at 1 second intervals If an EM FD 2500 Display instrument is connected a red LED located on the base near the Display connector serves as an overcurrent annunciator If it lights up or f...

Страница 24: ...e an IP address Even if a network cable is connected later depending on the firmware version there is no automatic IP address assignment Only after switching the EM PQ 2300 off and on with the network...

Страница 25: ...r incorporated in the EM FD 2500 is activated and deactivated using that instrument s keys Please refer to the EM FD 2500 operating manual for the procedure NOTE In the EM FD 2500 Display as delivered...

Страница 26: ...eds a unique IP address The simplest way to set this is via the optional EM FD 2500 Display If this instrument is not installed the IP address can be assigned by DHCP or by using the Device Manage sof...

Страница 27: ...th a crossover cable If not yet done install FRAKO Device Manager on the PC Move DIP switch 3 on the EM PQ 2300 to ON The instrument now has the IP address 192 168 0 57 Note the IP settings of the PC...

Страница 28: ...play bus It is possible to interrogate for the assigned address at the EM FD 2500 Display The procedure is described in the EM FD 2500 operating manual 7 1 3 1 Terminating resistors on the Display bus...

Страница 29: ...ice name so that it can be identified uniquely just by its first 16 characters After the device has been selected the keys have the following functions Taste Function F1 SET UP Opens the Display Set u...

Страница 30: ...ils it sends can be switched between German and English Please note that after the language has been changed at the Display or via EMPQ SW the Display language does not change until the Unit key is pr...

Страница 31: ...f current harmonics in the neutral conductor N 8 1 6 Display Harmonics page Selecting the menu item Harmonics in Display opens this page Pressing the ESC key will close the page and return the user to...

Страница 32: ...supply Q ind Inductive reactive energy in kvarh Q cap Capacitive reactive energy in kvarh Q eff RMS reactive energy in kvarh S Apparent energy in kVAh 8 1 10 Display Big display page Selecting the me...

Страница 33: ...e Selecting the menu item Active alarms in Display opens this page Pressing the ESC key will close the page and return the user to the next higher menu level The alarms currently present are displayed...

Страница 34: ...ings Events Recorded events System log System messages Configuration Download SNMP MIB Operating manual Modbus address table Firmware Firmware update 8 2 2 Operation The measurement readings are prese...

Страница 35: ...life threatening If the above instructions are followed the risk of endangering life and limb can be significantly reduced The instrument may only be cleaned with a dry cloth When this is done the ab...

Страница 36: ...threatening Observing the above safety precautions can significantly reduce the risk to life and limb An internal fuse is fitted in the EM PQ 2300 It is mounted in a fuseholder underneath the hinged c...

Страница 37: ...disconnected from the instrument All disconnected cables must be individually isolated and insulated and measures must be taken to prevent their inadvertent contact with live components or electricall...

Страница 38: ...11 General operating notes The following points must be observed when operating the instrument The instrument must always be operated in a closed control cabinet as described in Section 4 Mounting th...

Страница 39: ...ess already assigned to another device Disconnect the EM PQ 2300 from the bus and check the bus addresses with Device Manager Is the address assigned to the EM PQ 2300 still displayed If yes assign a...

Страница 40: ...omponents Measuring Instruments and Power Quality Analysers Power Quality EMS ISO 50001 FRAKO 55 02675 08 18 9893 Technische nderungen vorbehalten FRAKO Kondensatoren und Anlagenbau GmbH Tscheulinstra...

Отзывы: