COOLING CAPACITY TABLE
FP-85KM4
TAI DB25
℃
-WB17.8
℃
TAI DB27
℃
-WB19
℃
TAI DB27
℃
-WB19.5
℃
TAI DB29
℃
-WB21.1
℃
Twi
[℃]
Qw
[
1/h
]
DPw
[
kPa
]
Qa
[
m3/h
]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
604
10.4
501
2.71
2.24
12
12
3.1
2.48
12.6
12.6
3.2
2.4
13.0
13.0
3.85
2.63
13.6
13.6
750
15.4
651
3.35
2.81
12.4
12.3
3.84
3.02
13.4
12.9
3.98
2.96
13.7
13.3
4.82
3.12
14.9
13.9
5.0
950
23.5
850
4.23
3.35
13.5
12.5
4.86
3.62
14.5
13.1
5.03
3.5
14.9
13.5
6.12
3.68
16.2
14.1
534
8.3
500
2.36
2.06
13
12.8
2.73
2.25
13.8
13.4
2.83
2.18
14.2
13.8
3.47
2.33
15.3
14.4
673
12.6
652
2.95
2.47
13.9
13
3.42
2.7
14.8
13.6
3.56
2.59
15.3
14
4.38
2.75
16.5
14.6
7.0
846
19.0
850
3.7
2.95
14.8
13.2
4.32
3.2
15.9
13.8
4.48
3.08
16.3
14.2
5.56
3.24
17.7
14.8
448
7.5
502
1.91
1.79
14.5
13.8
2.27
1.97
15.4
14.4
2.37
1.89
15.9
14.8
2.8
2.08
16.7
15.8
544
10.7
650
2.36
2.12
15.4
14
2.83
2.34
16.4
14.6
2.88
2.26
16.7
15.1
3.5
2.45
17.8
16
9.0
680
12.8
850
2.93
2.54
16.2
14.2
3.53
2.78
17.3
14.8
3.6
2.69
17.6
15.3
4.41
2.88
18.9
16.2
329
4.33
502
1.35
1.32
17.2
15
1.7
1.66
17.2
15.6
1.74
1.63
17.4
16.1
2.15
1.77
18.5
17.1
400
6.18
650
1.64
1.61
17.7
15.2
2.08
2.01
17.8
15.8
2.12
1.94
18.1
16.3
2.65
2.09
19.4
17.3
11.0
493
9.0
851
1.98
1.92
18.3
15.4
2.56
2.4
18.6
16
2.61
2.31
18.9
16.5
3.29
2.5
20.2
17.5
244
2.53
502
0.93
0.91
19.6
15.9
1.26
1.22
19.7
16.5
1.29
1.26
19.5
17.0
1.52
1.49
20.1
18.3
291
3.47
651
1.08
1.05
20.2
16.1
1.51
1.48
20.2
16.7
1.54
1.5
20.1
17.2
1.84
1.8
20.7
18.5
13.0
348
4.79
850
1.25
1.19
20.8
16.3
1.81
1.76
20.8
16.9
1.84
1.78
20.7
17.4
2.22
2.15
21.4
18.7
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: in flow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
Note
: For cooling condition: temperature different between incoming/outgoing water is 5 degree Celsius.
Design and specification are subject to change without prior notice for product Improvement.
COOLING CAPACITY TABLE
FP-102KM4
TAI DB25
℃
-WB17.8
℃
TAI DB27
℃
-WB19
℃
TAI DB27
℃
-WB19.5
℃
TAI DB29
℃
-WB21.1
℃
Twi
[℃]
Qw
[
1/h
]
DPw
[
kPa
]
Qa
[
m3/h
]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
Pf
[
kW
]
Pfs
[
kW
]
Tad
[℃]
Taw
[℃]
702
13.6
600
3.15
2.64
12.2
12.2
3.55
2.9
12.9
12.9
3.72
2.81
13.3
13.2
4.46
2.97
14.5
13.9
886
20.6
780
3.95
3.18
13.1
12.4
4.47
3.44
14.1
13.1
4.69
3.322
14.5
13.4
5.63
3.52
15.7
14.1
5.0
1122
31.6
1020
4.98
3.76
14.2
12.6
5.65
4.06
15.3
13.3
5.94
3.95
15.6
13.6
7.16
4.14
17
14.3
620
10.8
600
2.78
2.32
13.7
12.9
3.16
2.55
14.5
13.6
3.28
2.47
14.9
14.0
3.89
2.67
15.9
14.9
778
16.3
781
3.46
2.76
14.6
13.1
3.97
3.02
15.6
13.8
4.12
2.94
15.9
14.2
4.89
3.16
17
15.1
7.0
980
24.7
1021
4.34
3.29
15.5
13.3
5.0
3.6
16.6
14
5.19
3.45
17
14.4
6.19
3.71
18.2
15.3
502
9.29
600
2.19
2.03
15.1
14
2.56
2.22
16.1
14.7
2.66
2.15
16.4
15.1
3.24
2.31
17.6
16
625
13.8
781
2.69
2.41
15.9
14.2
3.17
2.66
16.9
14.9
3.31
2.56
17.3
15.3
4.05
2.75
18.5
16.2
9.0
780
16.3
1022
3.33
2.87
16.7
14.4
3.95
3.16
17.8
15.1
4.13
3.02
18.2
15.5
5.09
3.21
19.6
16.4
393
5.97
601
1.63
1.59
17.2
15.0
1.98
1.92
17.5
15.7
2.08
1.84
17.9
16.1
2.51
2.03
18.9
17.2
481
8.61
781
1.96
1.92
17.7
15.2
2.42
2.28
18.3
15.9
2.55
2.18
18.7
16.3
3.1
2.4
19.8
17.4
11.0
591
12.5
1021
2.37
2.3
18.3
15.4
2.97
2.74
19
16.1
3.13
2.6
19.4
16.5
3.85
2.84
20.7
17.6
280
3.23
600
1.11
1.09
19.6
15.9
1.46
1.43
19.9
16.6
1.48
1.44
19.8
17.1
1.83
1.71
20.5
18.3
334
4.46
781
1.3
1.26
20.2
16.1
1.74
1.7
20.5
16.8
1.77
1.72
20.4
17.3
2.21
2.03
21.2
18.5
13.0
399
6.12
1023
1.5
1.47
20.7
16.3
2.07
2.00
21.1
17
2.11
2.04
21
17.5
2.67
2.37
22
18.7
Pf: total cooling capacity Tal: in flow air temperature dpw: pressure drop standard coil
Twi: in flow fluid temperature Qw: fluid flow rate in heat exchanger Qa: air flow
Pfs: sensible cooling capacity Tad: discharge air dry temperature Taw: discharge air wet temperature
Note
: For cooling condition: temperature different between incoming/outgoing water is 5 degree Celsius.
Design and specification are subject to change without prior notice for product Improvement.