Page 13 of 49
Ceiling cassette Fan Coil Unit, 4-pipe system
Model: FP-KM
HEATING CAPACITY TABLE
FP-204KM4
TAI 18
℃
TAI 20
℃
TAI 22
℃
TAI 24
℃
Twi
[℃]
Qw
[
1/h
]
DPw
[
kPa
]
Qa
[
m3/h
]
Pf
[
kW
]
Tad
[℃]
Pf
[
kW
]
Tad
[℃]
Pf
[
kW
]
Tad
[℃]
Pf
[
kW
]
Tad
[℃]
173
0.75
1209
2.11
23.4
1.84
24.7
1.73
26.4
1.54
27.9
201
0.98
1569
2.45
22.8
2.13
24.2
2.01
26
1.78
27.5
40
232
1.27
2041
2.85
22.1
2.46
23.7
2.32
25.5
2.06
27.1
318
2.23
1210
3.7
27.5
3.37
28.6
3.24
30.3
3.01
31.7
370
2.93
1570
4.31
26.5
3.92
27.7
3.77
29.4
3.5
30.9
50
429
3.82
2042
5.0
25.6
4.54
26.9
4.38
28.6
4.06
30.1
464
4.41
1211
5.29
31.5
4.92
32.6
4.78
34.2
4.53
35.6
541
5.81
1570
6.16
30.1
5.73
31.3
5.57
33
5.28
34.4
60
629
7.61
2038
7.15
28.8
6.66
30.1
6.47
31.8
6.13
33.3
612
7.26
1210
6.87
35.5
6.49
36.6
6.34
38.2
6.08
39.5
714
9.56
1570
8.01
33.8
7.56
34.9
7.4
36.6
7.09
38
70
830
12.54
2039
9.32
32.1
8.79
33.3
8.6
35.0
8.24
36.5
Pf: total heating capacity Tai: in flow air temperature
dpw: pressure drop standard coil Twi: in flow fluid temperature
Qw: fluid flow rate in heat exchanger Qa: air flow
Tad: discharge air temperature
Note
: For heating condition: temperature different between incoming/outgoing water is 10 degree Celsius.
Design and specification are subject to change without prior notice for product Improvement.
HEATING CAPACITY TABLE
FP-238KM4
TAI 18
℃
TAI 20
℃
TAI 22
℃
TAI 24
℃
Twi
[℃]
Qw
[
1/h
]
DPw
[
kPa
]
Qa
[
m3/h
]
Pf
[
kW
]
Tad
[℃]
Pf
[
kW
]
Tad
[℃]
Pf
[
kW
]
Tad
[℃]
Pf
[
kW
]
Tad
[℃]
189
0.87
1409
2.31
23.1
2.00
24.4
1.89
26.1
1.68
27.7
219
1.14
1830
2.67
22.5
2.32
23.9
2.18
25.7
1.94
27.3
40
233
1.28
2380
2.99
21.9
2.47
23.2
2.44
25.2
2.17
26.8
318
2.23
1210
3.7
27.5
3.37
28.6
3.24
30.3
3.01
31.7
403
3.42
1831
4.7
25.9
4.27
27.2
4.11
28.9
3.82
30.4
50
467
4.46
2379
5.44
25.1
4.95
26.4
4.76
28.2
4.42
29.8
508
5.19
1410
5.78
30.7
5.38
31.8
5.23
33.5
4.96
34.8
591
6.81
1832
6.73
29.4
6.26
30.6
6.09
32.3
5.77
33.7
60
685
8.89
2379
7.8
28.1
7.26
29.4
7.06
31.2
6.68
32.7
670
8.54
1410
7.52
34.5
7.10
35.6
6.94
37.2
6.65
38.6
780
11.22
1830
8.75
32.8
8.26
34
8.08
35.6
7.74
37.1
70
905
14.67
2378
10.16
31.2
9.59
32.5
9.37
34.2
8.99
35.7
Pf: total heating capacity Tai: in flow air temperature
dpw: pressure drop standard coil Twi: in flow fluid temperature
Qw: fluid flow rate in heat exchanger Qa: air flow
Tad: discharge air temperature
Note
: For heating condition: temperature different between incoming/outgoing water is 10 degree Celsius.
Design and specification are subject to change without prior notice for product Improvement.