Ceiling cassette Fan Coil Unit, 4-pipe system

Model:  FP-KM

 
 

WIRED WALL PAD CONTROL (OPTIONAL) 
 

ENTER

AM/ PM

1

- -

ON/OFF Button

      Press the button, the unit will be turned on or off.
2

- -

LED signal

3

- -

Room temperature Sensor

4

- -

Real time o'clock

5

- -

Unit Number

      No.00 is the master unit. You can set slave units(No.01--31) 

parametres on the  master wall pad.
6

- -

Mode: Auto,Cool, Dehumidification, Ventilation and Heat

        Auto mode                  Cool mode          
        Dehumidification       Ventilation mode         Heat mode 
     
7

- -

Setting Time

8

- -

Timer ON and OFF

        Cycle Timer             Timer ON              Timer OFF

9

- -

Error Mark

     01_ Room temperature sensor is damaged;
     02_ Drainage system is damaged;
     03_ Coil temperature sensor is damaged;  
     04_ Auto restart function is damaged.
     05_ Outdoor coil temperature sensor is damaged;
     06_ High or low pressure switch is opened;
     08_ The unit is shortage of refrigerant.

10

- -

Error Alarm

11

- -

Room temperature

12

- -

Setting temperature

13----Fan Speed Icon:  Auto,Low,Medium and High
14----Sleep Mode Icon
15----Louver Swing Icon
16----Communication Icon
17----Connecttion check Icon
18----Mode Select Button

         Press the button to select Auto, cool, dehumidification, 
ventilation or heat mode.    

19----Fan Speed Select Button

          Press the button to select Auto,low,medium or high 
speed.
20----Sleep Mode Button. 
         It will automatically adjust temperature and save             
energy when you are sleeping in cool mode or heat mode. 
        If the wall pad is the master,press it for 3s,commumication 
icon appears, you can select slave unit from 1 to 31 by pressing 
Time up or down button,all parameters appear on the wall pad 
will be sent to unit you selcted or all slave units when you  press 

Enter Button.

21----Timer ON/OFF Button
        1) Press TIMER button,         or         appears in LCD;
        2) Press TIME (up) or (down) to select TIMER ON or                          
TIMER OFF or SET;
        3) If TIMER ON or TIMER OFF is selected. "h" and          or        
blink in LCD; Press the TIMER(up) or (down) to set time by 10 
minutes step; Press the TIMER button to confirm it. Repeat step 
2) and 3) to set TIMER OFF or ON;
        4) After setting TIMER ON and OFF, Press the TIME (up) 
or (down). When          and SET appear in LCD, then press 
TIMER button to confirm it.        ,        and        appear in LCD at 
the same time. Then press ENTER button to confirm it.
        5) When you cancel cycle timer on and off, press TIMER 
button for 30s.          disappears in LCD. When you cancel timer 
on or/and off, press TIMER button first, then press the TIME 
(up) or (down) to select SET only in LCD. Press the TIMER 
button again, then cancel timer on or/and off.
 
22----Clock Button
         Press it first, then press Time up or down button to set real 
time o'clock
23----Enter Button
         In order to avoid misoperation ,all setting(except ON/OFF 
Button)is valid after pressing  the button.
24----Time up/down
         Press Timer ON/OFF Button or Clock Button first,then 
press it to set timer time or clock time
25----Swing Button,
26----Temperature Up/Down Button
         Press Up Button to increase temperature 1

 step 

(MAX:30

          Press Down Button to decrease temperature 1

 step 

(MIN:16

)

UNIT NO.

FOR SETTING MASTER-SLAVE UNIT USING WALL PAD

1.Please see the back of wall pad. The unit No. can be set using dip switchs.

  

UNIT NO.

dip switches

UNIT NO.

UNIT NO.

h

dip switches

dip switches

dip switches

 

 

 
 

Содержание FP-102KM4

Страница 1: ...Installation and Operation Manual Hydronic Ceiling Cassette Fan Coil Units FP KM 4 pipe system Last update 10 04 2009...

Страница 2: ...MOUNTING FRONT PANEL k FILTER REMOVAL l PRELIMINARY CHECKS BEFORE START UP m MAINTENANCE n FRESH AIR RENEWAL AND BRANCH DUCTING o BRANCH DUCT AND FRESH AIR DUCT INSTALLATION p BRANCH DUCT AND FRESH AI...

Страница 3: ...Page 3 of 49 Ceiling cassette Fan Coil Unit 4 pipe system Model FP KM MODEL ASSIGNMENTS FP 34 KM4 S Fan Coil Unit Model KM4 4 way cassette KM6 6 way cassette A 220 240V 1PH 50HZ S 230V 1PH 50HZ...

Страница 4: ...Current Amp 0 759 0 792 Operation Control Thermostat Remote Controller and wiring controller Chiller Water Flow Rate 1 h 610 700 Heat Water Flow Rate 1 h 300 315 Chilled Water Pressure Drop KPa 9 7 12...

Страница 5: ...80 5 100 150 192 241 Fan Motor Running Current Amp 0 305 0 367 0 435 0 652 0 844 1 079 Fan Motor Starting Current Amp 0 915 1 1 1 31 1 956 2 532 3 237 Operation Control Thermostat Remote Controller a...

Страница 6: ...incoming outgoing water is 5 degree Celsius Design and specification are subject to change without prior notice for product Improvement COOLING CAPACITY TABLE FP 80KM4 TAI DB25 WB17 8 TAI DB27 WB19 T...

Страница 7: ...outgoing water is 5 degree Celsius Design and specification are subject to change without prior notice for product Improvement COOLING CAPACITY TABLE FP 102KM4 TAI DB25 WB17 8 TAI DB27 WB19 TAI DB27...

Страница 8: ...coming outgoing water is 5 degree Celsius Design and specification are subject to change without prior notice for product Improvement COOLING CAPACITY TABLE FP 170KM4 TAI DB25 WB17 8 TAI DB27 WB19 TAI...

Страница 9: ...water is 5 degree Celsius Design and specification are subject to change without prior notice for product Improvement COOLING CAPACITY TABLE FP 238KM4 TAI DB25 WB17 8 TAI DB27 WB19 TAI DB27 WB19 5 TA...

Страница 10: ...ng water is 10 degree Celsius Design and specification are subject to change without prior notice for product Improvement HEATING CAPACITY TABLE FP 80KM4 TAI 18 TAI 20 TAI 22 TAI 24 Twi Qw 1 h DPw kPa...

Страница 11: ...incoming outgoing water is 10 degree Celsius Design and specification are subject to change without prior notice for product Improvement HEATING CAPACITY TABLE FP 102KM4 TAI 18 TAI 20 TAI 22 TAI 24 Tw...

Страница 12: ...oming outgoing water is 10 degree Celsius Design and specification are subject to change without prior notice for product Improvement HEATING CAPACITY TABLE FP 170KM4 TAI 18 TAI 20 TAI 22 TAI 24 Twi Q...

Страница 13: ...ing outgoing water is 10 degree Celsius Design and specification are subject to change without prior notice for product Improvement HEATING CAPACITY TABLE FP 238KM4 TAI 18 TAI 20 TAI 22 TAI 24 Twi Qw...

Страница 14: ...s cleaning coils filters and replacing filters Ensure that the electrical supply and frequency are adequate for the operating current required for this specific installation The manufacturer denies an...

Страница 15: ...ote the unit serial number SELECT LOCATION INSTALLATION LOCATION Fig 1 Fig 2 A B Do not install the unit in rooms where flammable gas or alkaline acid substances are present Aluminum copper coils and...

Страница 16: ...there is sufficient space around the unit to service it See Fig 3 INSTALLATION METHOD Using the installation template open ceiling panels and install the suspension bolts as in Fig 4 below 590 590 Di...

Страница 17: ...P 204KM4 FP 238KM4 Mark position of suspension rods water lines and condensate drain pipe power supply cables and remote control cable Supporting rods can be fixed depending on the type of ceiling as...

Страница 18: ...ken not to lift the unit by the drip tray which could be damaged Lift unit without the air panel with care by its four corners only Do not lift unit by the condensate drain discharge pipe or by the pi...

Страница 19: ...ixed to the unit body to avoid breaks when pipes are connected to valve assemblies it is advisable to tighten the connection with a spanner The upper coil connection is supplied with air purge screw t...

Страница 20: ...Do not install the unit where electromagnetic waves are directly radiated at the infrared receiver on the unit 3 Install the unit and components as far away as is practical at least 5 meters from the...

Страница 21: ...e two fasteners on the front panel Open the grille downward with care Pull the filter out along the slot Clean the filter and reassemble MOUNTING FRONT PANEL ASSEMBLY Remove return grille from front p...

Страница 22: ...e section filter removal Check the filter periodically and before the operating season clean or replace as necessary PROLONGED UNIT SHUT DOWN Prior to restarting the unit Clean or replace the air filt...

Страница 23: ...3 of 49 Ceiling cassette Fan Coil Unit 4 pipe system Model FP KM Fig 22 Condensate Drain Pan Removal Coil Drain Pan Drain Pan Fixture Fan blower Removal Fan Blower Fig 20 Fig 21 Condensate drain pan R...

Страница 24: ...ated dia 4 in with anti condensate material fiberglass 12 25 mm thickness Fresh air There is one 1 opening for connecting a fresh air duct for FP 68 80 85 102 136 170 204 238 KM4 There are two 2 openi...

Страница 25: ...Page 25 of 49 Ceiling cassette Fan Coil Unit 4 pipe system Model FP KM MODEL L S FP 68 80KM4 570 570 FP 85 102 136KM4 730 730 FP 170 204 238KM4 860 860 Fig 25...

Страница 26: ...Ceiling cassette Fan Coil Unit 4 pipe system Model FP KM BRANCH DUCT AND FRESH AIR DUCT INSTALLATION BRANCH DUCT FRESH AIR MODEL Dia mm QTY Dia mm QTY FP 68 80 85 102 136 170 204 238 KM4 100 2 100 1...

Страница 27: ...ook for the yellow sticker on the casing for location of branch duct or fresh air intake connections 2 The sticker is at the center of a knock out hole underneath the casing insulation Use a cutter an...

Страница 28: ...pipe system Model FP KM DIMENSIONAL DRAWINGS FP 68 80KM4 FRESH AIR DUCT MOTOR PANEL COVER BRANCH DUCT CHILLED WATER INLET FAN BLOWER CONTROL BOX WATER PURGE HOT WATER OUTLET HOT WATER INLET AIR VENT C...

Страница 29: ...it 4 pipe system Model FP KM FP 85 102 136KM4 MOUNTING BRACKETS FRESH AIR DUCT FAN BLOWER MOTOR PANEL COVER FRESH AIR DUCT TERMINAL BLOCK WATER PURGE HOT WATER OUTLET HOT WATER INLET CHILLED WATER INL...

Страница 30: ...Unit 4 pipe system Model FP KM FP 170 204 238KM4 FRESH AIR DUCT FAN BLOWER MOTOR MOUNTING BRACKET PANEL COVER TERMINAL BLOCK WATER PURGE HOT WATER OUTLET HOT WATER INLET CHILLED WATER INLET BRANCH DUC...

Страница 31: ...clip 5 Branch duct 6 Fan motor 6 1 motor capacitor 7 Fresh air outlet 8 Fan blower 9 Drain pump assembly 9 1 Drain pump fixture 9 2 Drain pump 9 3 Drainage tube 9 4 Float switch 10 Heat exchanger 11 D...

Страница 32: ...otor 7 1 Fan motor capacitor 8 Fan blower 9 Drain pump assembly 9 1 Pump fixture 9 2 Drain pump 9 3 Drainage tube 9 4 Float switch 10 Heat exchanger 11 Drain pan 12 Venturi 13 Inside control box 13 1...

Страница 33: ...motor 7 1 fan motor capacitor 8 Fan blower 9 Drain pump assembly 9 1 Pump fixture 9 2 Drain pump 9 3 Drainage tube 9 4 Float switch 10 Heat exchanger 11 Drain pan 12 Venturi 13 Inside control box 13 1...

Страница 34: ...f f i con w i l l bl i nk Then you pr ess TIM ER but t on t o set t i m er of f t i m e by 10 m i nut es st ep Press t he but t on agai n t i m er of f i s set Pr ess t he but t on agai n t i m er of...

Страница 35: ...1 to 31 by pressing Time up or down button all parameters appear on the wall pad will be sent to unit you selcted or all slave units when you press Enter Button 21 Timer ON OFF Button 1 Press TIMER bu...

Страница 36: ...or wired wall pad The master unit setting parameters are Unit ON OFF Mode Fan Speed Set Temperature Sleep Function and Swing function 2 A 2 SLAVE UNIT FUNCTION The slave unit runs according to master...

Страница 37: ...andset settings before the last power off 2 E COOL MODE If Tr Ts 1 C cool operation is activated MTV2 is turned on AUX2 is closed Indoor fan runs at set speed If Tr Ts cool operation is terminated MTV...

Страница 38: ...ned If 35 C Ti1 38 C when MTV1 is off AUX1 is opened Indoor fan keeps original state If Ti1 35 C when MTV1 is off AUX1 is opened Indoor fan stops If indoor coil temperature sensor is damages post heat...

Страница 39: ...SLEEP FUNCTION Sleep function can only be set in cool or heat modes In cool mode after sleep function is set the indoor fan will run at low speed and Ts will increase 2 C during 2 hours In heat mode...

Страница 40: ...t off 2 1 1 2 0 Ts 1 Ts 2 Hours since sleep set t hr Ts Tr 2 L AUTO FAN SPEED In cool mode the auto fan speed will operate as the following diagram Fan speed H M L ST ST 2 Tr ST 3 ST 5 In COOL mode th...

Страница 41: ...is on and will remain on for 5 minutes after the MTV closed The drain pump will keep running for 5 minutes after the mode is changed Warning If turn off the system by circuit breaker or main power su...

Страница 42: ...ion BLINK BLINK Coil Temperature sensor damaged ON BLINK BLINK Room Temperature sensor damaged BLINK BLINK Condensate pump damaged BLINK BLINK BLINK If the sensor malfunctions the red and yellow LED w...

Страница 43: ...en is slave JP1 Transformer JP2 Power supply JP3 2 way valve of Cooling JP4 Drainage pump JP5 Fan motor JP6 Remote receiver JP7 Stepping motor JP8 Stepping motor JP9 Stepping motor JP10 Stepping motor...

Страница 44: ...nsformer JP2 Power supply JP3 2 way valve of Cooling JP4 Drainage pump JP5 Fan motor JP6 Remote receiver JP7 Stepping motor JP8 Stepping motor JP9 Stepping motor JP10 Stepping motor JP11 Room TEMP sen...

Страница 45: ...Page 45 of 49 Ceiling cassette Fan Coil Unit 4 pipe system Model FP KM SHIELD WIRE SHIELD WIRE 4 2 2 4 4 2 Water Cassette Wiring Diagrams With Master and Slave Connection...

Страница 46: ...r and a main body The synchronous motor recovers by a spring and can be controlled by a handle The main body adopts the piston system 1 Technical data of solenoid valve Power supply 230VAC50Hz Input 4...

Страница 47: ...follow good working practice and legislation in force in the country concerned Reference values pH 6 8 Electrical conductivity Less than 200 mV cm 25 o C Chlorine ions Less than 50 ppm Sulphuric acid...

Страница 48: ...aulty room control Faulty fan Mash filter clogged Air flow obstructed Room control regulation Incorrect water temperature Air present Insufficient output Check for presence of voltage Check fuse on bo...

Страница 49: ...y monitoring Working parameters and timer can be set to all units each zone or to individual unit All fan coil units can be monitored in operation with their real running status Can be checked Error s...

Отзывы: