05: ECO voltage range settings
Interface
Setting
Parameter 2 & 3
:
Press the UP or Down key to choose the
acceptable high and low voltage values for the ECO mode.
HLS
: High line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
LLS
: Low line transfer in ECO mode as set in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
09: Backup time setting for outlets
00: Exit setting
3-6. Operation mode description
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 3
:
Use it to activate or cancel the Bypass mode.
ENA
: Bypass enabled
DIS
: Bypass disabled
07: Bypass voltage range setting
Interface
Setting
Parameter 2 & 3
:
Press the UP or Down key to choose the
acceptable high and low voltage values for Bypass operation
HLS:
High voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
230-264:
High voltage setting ranges from 230VAC to
264VAC as set in parameter 3. (Default: 264VAC)
LLS:
Low voltage adjustment in bypass mode. For
200/208/220/230/240 VAC:
170-220:
Low voltage setting ranges from 170VAC to
220VAC as set in parameter 3. (Default: 170VAC)
08: Backup time setting
Interface
Setting
Parameter 3
:
Sets the backup time limits for the
programmable outlets.
0-999
: Use this setting to define the programmable outlets
backup time in minutes, from 0-999, in order to connect
non-critical devices on battery mode.
Interface
Setting
Parameter 3
:
Sets up backup interval on battery mode
for default outlets.
0-999
: Use this setting to define the default outlets backup
interval in minutes, from 0-999, to operate on battery mode.
0
: When this parameter is set to “0”, the backup interval will
only last 10 seconds.
999
: When this parameter is set to “999”, the backup interval
will be disabled (Default).
Operating mode
Online mode
ECO mode
Battery mode
Bypass mode
Standby mode
Frequency
Converter mode
Description
LCD display
When the input voltage is within acceptable range, the UPS
will supply pure and stable AC power to connected loads.
The UPS will also charge the battery in online mode.
Energy saving mode:
When the input voltage is within the voltage regulation range,
the UPS will bypass voltage to loads for energy saving.
When input frequency is between 40 Hz and 70 Hz,
the UPS can be set at a constant output frequency,
50 Hz or 60 Hz. The UPS will still charge the battery when
operating in this mode.
When the input voltage exceeds the acceptable range or
during a power failure, the UPS will start supplying power
from the battery while the alarm will beep every 4 seconds.
When input is within acceptable voltage range but the UPS
is overloaded, the UPS will transfer to bypass mode or it can
be manually changed to bypass mode using the front panel
controls. The alarm will sound once every 10 seconds
in this case.
The UPS is powered off and there is no power supplied to
the loads, but batteries can still be charged.