32
0 means positive order; 1 means reverse
order
bit3: Channel current direction setting
0 means the direction is positive, 1 means
the current is reversed.
0x0000 by default;
0x0B17
2839
Retain
0x0B20
2848
Alarm function
management 1
Unsigned
short
Bit0 Bus arc,
bit1 Channel arc,
bit2 Low pressure,
bit3 Over pressure,
bit4 High temperature 1,
bit5 High temperature 2,
bit6 Channel current value is reversed,
bit7 Reverse total current is high,
bit9 The total current is high,
bit10 Channel current value is zero,
bit11 Channel current value is
undercurrent,
bit12 Channel current value is
overcurrent,
bit13 The channel current value is low,
bit14 The channel current value is high,
1: enable (open) alarm, 0: disable(close)
alarm
Default:0x0003
W/R
0x0B21
2849
Alarm function
management 2
Unsigned
short
Bit0 DI1
bit1 DI2
bit2 DI3
bit3 DI4
bit14: -
bit15: General alarm switch, (function is
forcibly turned on)
1: enable alarm, 0: disable alarm
Default value: 0x800F
W/R
0x0B23
2851
Retain
0x0B24
2852
Retain
System information configuration 2 (0x0C00-0x0C06)
W/R
0x0C00
3072
Clear power generation
history value record
Unsigned
short
Write 1 reset energy history record, read
always 0
W/R
System settings (0xFE00-0xFE54)
0xFE00
65024
Modbus address
Unsigned
short
Set range 1 ~ 247, default 247.
Set other values to restore the default
W/R