31
0x0B0D
2839
-
-
-
0x0B0E
2830
Channel arc intensity super
high alarm threshold
Short
The default is 70.Need to set according to
the site conditions or customer
requirements, you can call the company's
technical staff
W/R
0x0B0F
2831
Retain
0x0B10
2832
Retain
0x0B11
2833
Automatic current
calibration setting
Bool
Write 1 to enable automatic current
calibration, write 0 to disable, default is 0
W/R
0x0B12
2834
Manual current calibration
setting
Bool
Write 1 to start current calibration, write
0 to turn off, default is 0
Note: Make sure the channel has no
current when starting calibration.
W/R
0x0B13
2835
Channel 1~16 current
channel switch setting
Unsigned
short
bit0:Represents the switch setting for
channel 1
bit15:Represents the switch setting for
channel 16
0 means disabled, 1 means enabled
Default 0xFFFF
W/R
0x0B14
2836
Channel 17~32 current
channel switch setting
Unsigned
short
bit0:Represents the switch setting for
channel 7
bit7:Represents the switch setting for
channel 24
0 means disabled, 1 means enabled
Default 0xFFFF
W/R
0x0B15
2837
External power
management time setting
Unsigned
short
Unit M (min), default 120 minutes. When
the photovoltaic power supply stops, the
host can be powered by external 24
power sources, and the power supply
time can be set.
W/R
0x0B16
2838
Current UI display,
direction, reverse order
control
Unsigned
short
Bit0 ~ bit1: Y-axis scale setting of UI
interface
0 means the UI interface displays the
current up to 10A
1 means the UI interface displays the
current up to 20A
2 means the UI interface displays a
maximum current of 30A
bit2: current channel forward / reverse
sequence setting
(Positive sequence: 1 ~ 24 channels
arranged near the host Hall;
Reverse order: Calculate from 24 to 1
channel near the host Hall)
W/R