3.2.6.2. Ø 100/60 mm and Ø 125/80 mm air intake/flue gas coaxial duct system
The above data are referred to air intake/flue gas discharge systems which are implemented by means of smooth, rigid
manufacturer approved and supplied pipes.
Type C13
KB 24
Minimum permissible length of horizontal coaxial pipes is 1 meter, without accounting for the first elbow connected to the boiler.
Maximum permissible length of Ø 100/60 mm horizontal coaxial pipes is 9.5 meter not including the first elbow connected to the boiler.
Maximum permissible length of Ø 125/80 mm horizontal coaxial pipes is 14.5 meter not including the first elbow connected to the boiler.
For each additional 1 meter straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The wall terminal reduces maximum permissible length by 1.5 meters.
The air intake duct is to be tilted by 1% toward its exit, in order to avoid rain water to enter it.
KB 28
Minimum permissible length of horizontal coaxial pipes is 1 meter, without accounting for the first elbow connected to the boiler.
Maximum permissible length of Ø 100/60 mm horizontal coaxial pipes is 6.5 meter not including the first elbow connected to the boiler.
Maximum permissible length of Ø 125/80 mm horizontal coaxial pipes is 11.5 meter not including the first elbow connected to the boiler.
For each additional 1 meter straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The wall terminal reduces maximum permissible length by 1.5 meters.
The air intake duct is to be tilted by 1% toward its exit, in order to avoid rain water to enter it.
Type C33
KB 24
Minimum permissible length of vertical coaxial pipes is 1 meter.
Maximum permissible length of Ø 100/60 mm vertical coaxial pipes is 9.5 meters.
Maximum permissible length of Ø 125/80 mm vertical coaxial pipes is 14.5 meters.
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 1.5 meters.
KB 28
Minimum permissible length of vertical coaxial pipes is 1 meter.
Maximum permissible length of Ø 100/60 mm vertical coaxial pipes is 6.5 meters.
Maximum permissible length of Ø 125/80 mm vertical coaxial pipes is 11.5 meters.
For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 1.5 meters.