18
2.4.
Operating data
Burner pressures must be verified after a three minute boiler operation time.
KB 24
Fuel type
Max. CH
Input
[kW]
CH
output
(80-60°C) [kW]
CH
output
(50-30°C) [kW]
DHW
output
[kW]
Gas mains
pressure
[mbar]
Diaphragm
diameter
[mm]
Flue gas
CO
2
[%]
Kw
min
max
min
max
min
max
mbar
mm
%
Methane Gas G20
23.7
6.5
23.1
7.3
24.8
7.3
28.0
20
7.2
8.8 ÷ 9.1
Propane Gas G31
23.7
6.5
23.1
7.3
24.8
7.3
28.0
37
5.3
9.1 ÷ 10.1
Table 4
Instantaneous DHW supply ΔT 45 K = 9.9 l/min
Instantaneous DHW supply ΔT 40 K = 11.1 l/min
Instantaneous DHW supply ΔT 35 K = 12.7 l/min
Instantaneous DHW supply ΔT 30 K = 14.8 l/min
Instantaneous DHW supply ΔT 25 K = 17.8 l/mi
Table 3
Instantaneous DHW supply ΔT 45 K = 8.9 l/min
Instantaneous DHW supply ΔT 40 K = 10.0 l/min
Instantaneous DHW supply ΔT 35 K = 11.5 l/min
Instantaneous DHW supply ΔT 30 K = 13.4 l/min
Instantaneous DHW supply ΔT 25 K = 16.1 l/min
Note: DHW supply refers to instantaneous production (Aqua Premium system disabled).
KB 24
KB 28
Equipment category
-
II2H3P
II2H3P
Minimum CH system pressure
bar
0.5
0.5
Maximum CH system pressure
bar
3
3
Minimum DHW system pressure
bar
0.5
0.5
Maximum DHW system pressure
bar
8
8
DHW specific flow rate (Δt 30 °C)
l/10’
163
183
Electric power supply – voltage / frequency
V ~ Hz
230 ~ 50
230 ~ 50
Power mains supply fuse
A
2
2
Maximum power consumption
W
145
145
Electric protection rating
IP
X4D
X4D
Methane gas consumption at maximum CH input (*)
m3/h
2.51
2.77
Propane gas consumption at maximum CH input
kg/h
1.84
2.03
Maximum CH working temperature
°C
83
83
Maximum DHW working temperature
°C
62
62
Total capacity of expansion vessel
l
10
10
Maximum recommended CH system capacity (**)
l
200
200
Table 5
(*) Value refers to 15°C - 1013 mbar.
(**) Maximum water temperature = 83°C. Expansion vessel pressure pre-charge = 1 bar
2.5.
General characteristics
KB 28
Fuel type
Max. CH
Input
[kW]
CH
output
(80-60°C) [kW]
CH
output
(50-30°C) [kW]
DHW
output
[kW]
Gas mains
pressure
[mbar]
Diaphragm
diameter
[mm]
Flue gas
CO
2
[%]
Kw
min
max
min
max
min
max
mbar
mm
%
Methane Gas G20
26.2
5.4
25.55
6.1
27.4
6.1
31.0
20
7.2
8.8 ÷ 9.1
Propane Gas G31
26.2
5.4
25.55
6.1
2.74
6.1
31.0
37
5.3
9.8 ÷ 10.1