1.2.3. Electronic timer programming

1

2

3

4
7

6

5

8

9

A) Initialization

When programming the timer for the first time, or re-programming it, 
it is advisable to perform a full reset of the timer by positioning se-
lector 2 to RUN and pressing the reset micro-button R: The time and 
start and stop programs will be reset (time display flashes 0:00).
In  order  to  set  the  week  day,  actual  time  and    start  and  stop  pro-
grams, see paragraph B and C.

B) Setting the day of the week and actual time

Position  selector 

to 

RUN

  and  at  the  same  time  press  buttons  h 

and m until the two dots, dividing hours and minutes stop flashing 
(If previously the reset micro-button 

R

 was pressed, the actual time 

display  stops  flashing  also);  press  button 

1…7

  in  order  to  set  the 

current week day ( shown by indicator 8), press button h to set actual 
hour, press button m to set actual minutes (by keeping button 

h

 or 

m

 

pressed the digits run faster).
Wait approximately ten seconds, until the two dots, dividing hours 
and minutes start flashing. The programming procedure of the day of 
the week and time is now completed.

C) Start and stop programs

Position selector 

2

 to 

P1

 in order to program channel 

1

, and to 

P2

 in 

order to program channel 

2

 ( indicator 

3

 shows the chosen channel, 

indicator 4 shows the symbol, indicating we are programming a start 
time, and indicator 

5

 shows digit 

1

 to indicate the first program is set; 

Up to 

8

 start periods and 8 stop periods can be set, a total of 16).

In order to set a start program, follow the instructions below: 
- press button 

1…7

 in order to set the desired week day ( or days (1));

- press button h and button m to set hour and minutes of the start 
program;
- press button 

 to memorize the programmed time and go to the 

stop program (indicator 

4

 is off showing we are programming a stop 

time, and indicator 

5

 shows digit 

2

 indicating we are in the second 

time of the program).
Perform again the above procedure in order to set the stop time, and 
at the end press button 

.

Now we have set a heating unit operation period, by setting a start 
and stop time, indicator 

5

  shows digit 

3

; Follow the above instruction 

to program an additional heating unit operation period, otherwise po-
sition selector 

2

 to 

RUN

 to terminate the programming procedure.

(1) The following periods are available in order to automatically repeat 
the programmed heating unit operation periods during the week:
Period no.1: single week day
Period no.2: day 1-2-3-4-5 of the week (Mon-Tue-Wed-Thu-Fri)
Period no.3: day 6-7 of the week (Sat-Sun)
Period  no.4:  day  1-2-3-4-5-6  of  the  week  (Mon-Tue-Wed-Thu-Fri-
Sat)
Period no.5: day 1-2-3-4-5-6-7 of the week (Mon-Tue-Wed-Thu-Fri-
Sat-Sun)

When programming a start time by using a multiple day period (e.g. 
period no.2), the stop time is to be programmed in the same multiple 
day period for it to be effective every day of the period.

pic. 3

1

 Mode selector   

 

2

 Program selector 

 

3

 Channel indicator 

4

 Channel activation  indicator

5

 Programmed period indicator

6

 Skip function button

7

 Skip function indicator

8

 Week days indicator

9

 Actual time

Содержание CAPRI B

Страница 1: ...CAPRI B R IST 03 C 217 01 INSTALLATION USE AND MAINTENANCE GB...

Страница 2: ...Dear Customer thank you for choosing our boilers Please read these installation use and maintenance instructions with care...

Страница 3: ...es All the packaging materials can be recycled and should be sent to specific waste management sites Keep the packaging out of the reach of children as it constitutes a serious hazard In the event of...

Страница 4: ...imensions page 14 2 3 Heating unit layout page 15 2 4 Technical data of the heating units page 16 2 5 Technical data of the burner page 16 3 Instructions for the installer page 17 3 1 Installation reg...

Страница 5: ...d is flashing B and BV models only the temperature probe 2 cylinder is faulty inter rupted or out of range The heating unit keeps operating in CH mode DHW supply is halted As soon as the faulty probe...

Страница 6: ...nd BV models or through the adjustable thermo stat on the cylinder Temperature range is 35 C 65 C in B and BV models in R and RV models it is depending on the type of cylinder optional equipment The p...

Страница 7: ...s the boiler is active The unit heats the cylin der up to the temperature set via knob 12b B and BV models or via the adjustable thermostat on the cylinder when a cylinder was installed R and RV model...

Страница 8: ...h Comfort position All functions are active CH DHW ANTI FROST PUMP ANTI LOCKING ANTI LEGIONELLA Channel 1 of the programmable timer is considered always ON re gardless of the set program therefore CH...

Страница 9: ...r the bottom of the chart NOTE TO THE FITTER The fictitious room temperature set by the user through knob 13b is more precise when the SLIDING TEMPERATURE curves are set correctly Such curves are to b...

Страница 10: ...eriods can be set a total of 16 In order to set a start program follow the instructions below press button 1 7 in order to set the desired week day or days 1 press button h and button m to set hour an...

Страница 11: ...UTO It is possible to permanently activate one channel and permanently de activate the other Proceed as follows position selector 1 to I press button 6 once to select channel 1 twice for channel 2 the...

Страница 12: ...ssure by acting upon the loading tap pic 5 located in side the heating unit In order to restore proper water pressure proceed as follows turn the main switch 16 pic 1 to O the green light turns off re...

Страница 13: ...tem and 24 kW thermal output TFD 33 sealed chamber heating unit with split air ue gas system and 33 kW thermal output TFD 43 sealed chamber heating unit with split air ue gas system and 43 kW thermal...

Страница 14: ...NI01 VA version 5 LOW TEMP FLOW VA version G1 M 10 FUEL INLET Models R and RV Models B and BV D mm TF 150 TFD 120 1 FLOW G1 M 6 HIGH TEMP FLOW BV version G1 M 2 RETURN G1 M 7 HIGH TEMP RETURN BV versi...

Страница 15: ...ater Domestic hot water REMOTE CONTROL or CYLINDER PROBE ZONA 1 HIGH TEMPERATURE TS S1 MODEL B PR CH PUMP PS DHW PUMP TS LIMIT THERMOSTAT TA1 ROOM THERMOSTAT OPTIONAL TA 1 TS HEATING UNIT PROBE EXTERN...

Страница 16: ...0 5 0 5 0 5 CH temperature range C 50 82 50 82 50 82 Max CH operating pressure bar 3 3 3 CH expansion vessel capacity l 12 12 12 DHW expansion vessel capacity l 5 5 5 DHW temperature range C 35 57 35...

Страница 17: ...securing the base to the wooden pallet in order to remove the wooden pallet from the heating unit it is necessary to raise it proceed carefully insert two ropes or cables under the base front rear wis...

Страница 18: ...minal Types and classi cation of air intake and ue gas discharge systems Type B23 Discharge through the wall when allowed by applicable installation standards or through the roof or via chimney system...

Страница 19: ...y earth the system The DHW CH and fuel pipes are not suitable for grounding purposes 3 2 9 Hydraulic connections CENTRAL HEATING Before installing the heating unit we recommend you clean the sy stem t...

Страница 20: ...ted together with the power main cables Position the external probe on an outside wall facing North North East Do not install the probe in the windows areas near ventilation openings or heat sources I...

Страница 21: ...OM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS TA1 TA2 ZONE 1 ROOM THERMOSTAT AND ZONE 2 ROOM THERMOSTAT BOTH OPTIONAL EQUIPMENT TSM LOW TEMPERATURE ZONE THERMOSTAT SE EXTE...

Страница 22: ...D ZONE 2 ROOM THERMOSTAT BOTH OPTIONAL EQUIPMENT TSM LOW TEMPERATURE ZONE THERMOSTAT SE EXTERNAL PROBE CODE 0SAODAES01 CT PHONE PROGRAMMER OPTION FUSE 2AF 250Vac FUSE P4 POTENTIOMETER FOR HIGH TEMPERA...

Страница 23: ...V 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE ROOM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS TA1 TA2 ZONE 1 ROOM THERMO...

Страница 24: ...MODEL BV with REMOTE CONTROL 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE ROOM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS...

Страница 25: ...BE WITH CYLINDER MODEL R 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE ROOM THERMOSTATS M6 CONNECTOR FOR TELE METERING M1 M24 AVAILABLE CONNECTIONS TA1...

Страница 26: ...E METERING M1 M24 AVAILABLE CONNECTIONS TA1 TA2 ZONE 1 ROOM THERMOSTAT AND ZONE 2 ROOM THERMOSTAT BOTH OPTIONAL EQUIPMENT TSM LOW TEMPERATURE ZONE THERMOSTAT SE EXTERNAL PROBE CODE 0SAODAES01 CT PHONE...

Страница 27: ...djustement set a value between 3 and 4 NOTE SET THE BOILER JUMPER TO CM3 TO ON EXTERNAL CYLINDER MODEL RV 0CIRCSTA05 MAIN ELECTRONIC BOARD M TERMINAL BOARD FOR CONNECTION TO POWER MAINS EXTERNAL PROBE...

Страница 28: ...RATURE CN4 OFF 2 C THE REMOTE MANAGES ZONES 2 WHEN THE REMOTE CONTROL IS CONNECTED BOTH CHANNELS CH1 AND CH2 OF THE DIGITAL TIMER ARE ALWAYS TO BE ELECTRICALLY CLOSED MODEL RV with REMOTE CONTROL 0CIR...

Страница 29: ...datory to install a lter on the fuel oil supply pipe The burner pump is designed to operate in a twin pipe system In order to supply via a single pipe unscrew cap 2 and remove the grub screw 3 Afterwa...

Страница 30: ...ire adjustment Combustion air can be adjusted by turning the socket screw A shown in pic 15 The setting is shown on the relevant graduated scale B The oil pressure can be adjusted by turning screw 5 i...

Страница 31: ...18 pic 17 4 8 Burner ignition cycle The burner ignition cycle is shown in pic 19 chart In the event of shutdown the red light 7 on the control panel pic 1 comes on and the reset button C on the burner...

Страница 32: ...Optical resistence Solenoid valve Motor and condenser Burner earth Safety thermostat Limit thermostat Remote shutdown light 230V 0 5A max Ignition electrodes Optical resistence Solenoid valve Motor an...

Страница 33: ...terminal connections The burner performs pre purge correctly and then shuts down The optical resistance is dirty Clean it The optical resistance is faulty Replace it The flame goes out or does not lig...

Страница 34: ...rvice technicians T accurately trained personnel 6 1 Maintenance schedule Routine maintenance is to include the following general check and inspection of the heating unit check for leaks of the oil su...

Страница 35: ...isconnected Reconnect it Flow probe is faulty Replace it The heating unit has shut down the red shutdown light no 6 is flashing The unit will automatically resu me operation once the problem is solved...