Icemaker troubleshooting chart
Indicators/possible cause
1. Kink in ice transport tube.
2. Bin level control remains in closed
position.
3. Ice transport tube ruptured internally.
4. Worn evaporator bearings.
5. Faulty gearmotor start relay. Icemaker
torques out within 5 seconds of start-up.
6. Torque out occurs when storage bin fi lls
to capacity.
1. Gearmotor running but no output
rotation.
2. Float reservoir empty.
3. Air bubble in water supply line. Water
in reservoir but not in evaporator.
1. Compressor start relay in wrong
position.
2. High pressure cutout open due to high
head pressure.
3. Clogged or dirty condenser coil.
4.
Improper
ventilation.
5.
Defective
compressor.
1. Clogged or dirty condenser coil.
2. Compressor not pumping.
3. Low refrigerant charge.
1. Compressor switch in OFF position.
2. No output on compressor and fan motor
terminals on control board.
3. Failed fan motor causes high pressure
cut-out to open.
1. Mineral build-up on evaporator surface.
Corrective action
1. Eliminate kink and check that tube
routing complies with Follett icemaker
installation manual.
2. Adjust or replace control.
3. Replace complete run of ice transport
tube.
4. Inspect bearings for roughness or
binding and replace if necessary.
5. Replace gearmotor start relay.
6. Ensure that ice contacts bin thermostat
before backing ice up in transport tube.
Refer to dispenser manual for proper
thermostat and ice tube mounting.
1. Check for broken gearmotor output shaft
or damaged gearbox.
2. Check for defective water sensor (water
OK (WTR) LED remains on even when
fl oat empty or probe removed from
water).
3. Purge air from line.
1. Position relay with arrow or word “top”.
2. Check discharge pressure and adjust
water regulator valve.
3. Clean condenser coil.
4. Provide inlet and exhaust air provisions
per Follett icemaker installation manual.
5. Replace compressor.
1. Clean condenser coil.
2. Replace compressor.
3. Check for leaks; repair, evacuate, and
weigh in correct charge.
1. Turn compressor switch on.
2. Replace control board.
3. Replace fan motor.
1. Clean evaporator with liquid icemaker
cleaner.
Problem
6. Icemaker runs
for short period
of time and shuts
down on torque
error.
System
status:
20M or 2nd LED
are lit.
7.
Evaporator
is
iced up on the
outside. No ice
production.
System
status:
compressor,
gearmotor
and fan motor
running.
8. Compressor
cycles
intermittently.
System
status:
gearmotor and
fan motor run.
9. Unit runs but not
making ice.
System
status:
compressor,
gearmotor & fan
motor running.
10. Compressor and
fan motor will not
run. Gearmotor
runs.
11. Intermittent
noises from
evaporator.