01441492R00 – REFVAC20/25 LB, PH, PD
Parameter
Default Value
Range
Description
Power Alarm
Relay
Yes
Yes, No
Defines if relay should open/close on power alarm .
Power Alarm
Timer
5 minutes
0 to 120 minutes
Delay before sounding the power alarm .
Battery Level
Battery Level
Data Storage
Yes
Yes, No
Overwrite circular data?
Data Full Alarm
No
Yes, No
Alarm when data memory is full?
Data log
Sample Rate
15 minutes
0 to 360 minutes
minutes between data sampling . 0 = Off
Data Duration
Data Storage
Yes
Yes, No
Overwrite circular data?
Data Full Alarm
No
Yes, No
Alarm when data memory is full?
Track Events
Yes
Yes, No
Track events with log
P1 Datalog
No
Yes, No
Log P1 to event log
P2 Datalog
No
Yes, No
Log P2 to event log
P4 Datalog
Yes
Yes, No
Log P4 to event log
Defrost
Manual Defrost
No
Yes, No
Force the unit into a defrost
Defrost Control
Manual only
"Power on, manual only,disable,
time of day, compressor on
time"
Defines tactic for initiating a defrost
Graphing
X Axis Range
(hrs)
168 hours
1 to 384 hours
Time span for x-axis
Y Axis Minimum
–1 C (30 F)
–46 to 121 C (–50 to 250 F)
Minimum temperature shown on graph
Y Axis Maximum
27 C (80 F)
–46 to 121 C (–50 to 250 F)
Maximum temperature shown on graph
Graph Show
Alerts
No
Yes, No
Determines whether alerts are displayed on the graph
P1 Graph Display NO
Yes, No
Determines whether to graph probe 1
P2 Graph Display No
Yes, No
Determines whether to graph probe 2