R404A ice machine charge specifications

Model

Charge

Refrigerant type

MCD425A, MFD425A, R425A, P425A (air-cooled)

15 oz. (425 g)

R404A

MCD425W, MFD425W, R425W, P425W (water-cooled)

9 oz. (255 g)

R404A

Refrigerant replacement requirements

1.  Non-contaminated refrigerant removed from any Follett refrigeration system can be recycled and returned 

to the same system after completing repairs. Recycled refrigerant must be stored in a clean, approved 

storage container. If additional refrigerant is required, virgin or reclaimed refrigerant that meets ARI 

standard 700-88 must be used.

2.  In the event of system contamination (for example, a compressor burn out, refrigerant leak, presence of 

non-condensibles or moisture), the system must be repaired, evacuated and recharged using virgin or 
reclaimed refrigerant that meets ARI standard 700-88.

3.  Follett Corporation does not approve of recovered refrigerants. Improper refrigeration servicing 

procedures will void the factory warranty.

Evacuation 

Evacuate the system to a level of 500 microns. When the 500 micron level is reached, close valves and both 

manifold and shut down the vacuum pump. Allow the system to sit for approximately 20 minutes. During this period 

the system pressure should not rise. If the system pressure rises and stabilizes there is moisture in the system and 

further evacuation is needed. If the pressure continues to rise check the system for leaks.

Ice capacity test
Ice machine production capacity can only be determined by weighing ice produced in a specific time period. 
Replace all panels on ice machine.

1.  Run ice machine for at least 15 minutes.
2.  Weigh and record weight of container used to catch ice.
3.  Catch ice for 15 or 20 minutes.
4.  Weigh harvested ice and record total weight.
5.  Subtract weight of container from total weight.
6.  Convert fractions of pounds to decimal equivalents (ex. 6 lb 8 oz. = 6.5 lb).
7.  Calculate production using following formula:

 

1440 min. x wt. of ice produced 

 

 

 

 

Production capacity/24 hr. period

 

Total test time in minutes

8.  Calculated amount per 24 hours should be checked against rated capacity for same ambient and water 

temperatures in Ice Production Tables.

  

MCD425A/W, R425A/W, MFD425A/W, P425A/W Ice Machines 25

Содержание MCD425A

Страница 1: ...moving all packing material Inspect the equipment for concealed shipping damage All freight is to be inspected upon delivery If visible signs of damage exist please refuse delivery or sign your delive...

Страница 2: ...s dictate 7 Service 9 Ice machine Operation all models 9 Water system 10 Electrical system 11 Electrical control system schematic 13 Electrical control system operation 13 Refrigeration system all mod...

Страница 3: ...lation Follett ice storage bins R Remote installation Symphony ice and water dispensers P Replacement icemaker Symphony ice and water dispensers Flake ice machine MFD Top installation Follett ice stor...

Страница 4: ...ent back flow do NOT connect drains Follett recommends a Follett water filter system be installed in the ice machine inlet water line standard capacity 00130229 high capacity 00978957 carbonless high...

Страница 5: ...33 36 Water cooled Water temperature at float 50 F 10 C 60 F 15 6 C 70 F 21 1 C 80 F 26 7 C 90 F 32 2 C 5 6A 5 6A 5 7A 5 8A 5 8A 50 10 280 27 280 27 280 27 70 21 285 29 285 29 285 29 90 32 290 31 290...

Страница 6: ...88 48 cm 18 88 48 cm 2 32 5 9 cm 4 40 11 2 cm 15 22 38 7 cm 11 03 28 0 cm 8 03 20 4 cm 5 03 12 8 cm 2 34 6 cm Dimensions and clearances Entire front of ice machine must be clear of obstructions connec...

Страница 7: ...hat this cleaning is performed according to the schedule below Service problems resulting from lack of preventive maintenance will not be covered under the Follett warranty Recommended cleaning interv...

Страница 8: ...quart until SafeCLEAN Plus solution completely fills the reservoir Place lid back on cup 6 CLEANER FULL light will turn on and machine will start cleaning cycle then rinse three times this process tak...

Страница 9: ...he water supply when the ice machine is not running When the ice machine is running a layer of ice forms on the interior surface of the evaporator This ice is continuously removed by a slowly rotating...

Страница 10: ...l until the Normal Low sensor is exposed triggering the water feed solenoid on Water will fill until the Normal High sensor is activated Note The potable water dissolved solids content must be greater...

Страница 11: ...initiating the time delay period When the time delay expires the machine will restart provided that the LOW BIN light is on DIP Switch Settings Sleep cycle dispense duration OFF ON 1 2 3 4 5 6 7 8 4 5...

Страница 12: ...the water be shut off to a running machine a soft error will occur The error sequence is as follows During operation the water level falls to the normal low sensor and when it does the water feed sole...

Страница 13: ...SET PROGRAM P5 ICE AUX WATER AUX D9 D8 D7 D6 D5 D4 D37 D3 D2 D18 D16 D15 D14 D13 D12 D11 D10 D1 T1 P18 P11 P13 P17 P12 P14 P16 P15 P4 T2 S1 S2 K1 P7 P8 P10 K3 1 2 6 5 P9 L1 L1 L1 N N N N N N N N N P2...

Страница 14: ...in the reservoir for continuity between the common probe B and the high probe C If continuity is not sensed the water fill valve P21 is energized 5 2 1 Start Run Compressor T O L MAINTENANCE LOW WATER...

Страница 15: ...5 6 7 8 BLACK N P15 I c e D i s p e n s e I n p u t Capacitor BLACK YELLOW OR NO CONNECT PSC Start winding energized through capacitor Normal operation Stage 3 After the initial high current draw dro...

Страница 16: ...BLACK YELLOW OR NO CONNECT Normal operation Stage 5 As the compressor comes up to normal running speed its start winding generates a voltage potential across the relay s coil This energizes the coil t...

Страница 17: ...YELLOW OR NO CONNECT Normal operation Stage 7 The fan motor continues for 10 minutes before shutting off The TIME DELAY LED remains on for 20 minutes The ice machine will not start while the TIME DEL...

Страница 18: ...Sensor P6 P21 P20 P19 P3 P22 P4 AUGER WATER LEVELS BIN P11 HI PRS L1 R S C RED WHITE WHITE BLACK BROWN BLUE RED BLACK YELLOW Compressor Electrical Box COMPRESSOR 1 2 3 4 5 6 7 8 BLACK N P15 I c e D i...

Страница 19: ...rs RESET Fill Valve Drain Valve 3 4 2 Bin T Stat Clean Switch Drain Clog Sensor P6 P21 P20 P19 P3 P22 P4 AUGER WATER LEVELS BIN P11 HI PRS L1 R S C RED WHITE WHITE BLACK BROWN BLUE RED BLACK YELLOW Co...

Страница 20: ...Start Relay Start Relay N L1 Fan A B C D Water Sensors RESET Fill Valve Drain Valve 3 4 2 Bin T Stat Clean Switch Drain Clog Sensor P6 P21 P20 P19 P3 P22 P4 AUGER WATER LEVELS BIN P11 HI PRS L1 R S C...

Страница 21: ...OR NO CONNECT High gearmotor amps Stage 3 If a second occurrence happens during the 60 minute monitoring period the HI AMPS LED will come on again and shut the machine down strike two The HI AMPS LED...

Страница 22: ...OW WATER LED will remain ON until the water level is satisfied 5 2 1 Start Run Compressor T O L MAINTENANCE LOW WATER TIME DELAY SLEEP CYCLE MAKING ICE LOW BIN POWER SERVICE HI AMPS HI PRESSURE DRAIN...

Страница 23: ...P6 P21 P20 P19 P3 P22 P4 AUGER WATER LEVELS BIN P11 HI PRS L1 R S C RED WHITE WHITE BLACK BROWN BLUE RED BLACK YELLOW Compressor Electrical Box COMPRESSOR 1 2 3 4 5 6 7 8 BLACK N P15 I c e D i s p e n...

Страница 24: ...0 70 80 90 100 C 16 21 27 32 38 50 460 425 390 355 320 lbs 10 208 193 177 161 145 kg 60 437 5 405 372 5 340 307 5 lbs 16 198 184 169 154 139 kg 70 415 385 355 325 295 lbs 21 188 175 161 147 134 kg 80...

Страница 25: ...a level of 500 microns When the 500 micron level is reached close valves and both manifold and shut down the vacuum pump Allow the system to sit for approximately 20 minutes During this period the sy...

Страница 26: ...0 Remove ice compression loop located at top of auger 11 Lift auger straight up and out of evaporator 12 Remove nut and lower vee band coupling from bottom of evaporator 13 Lift evaporator to clear bo...

Страница 27: ...ll upper bearing and seal assembly rotating bearing to slip pin into auger slot 13 Install upper vee band clamp and nut to 70 in lb 14 Install evaporator insulation 15 Install compression nozzle and t...

Страница 28: ...502781 2 Duct including gasket 01068188 3 Front panel 01068204 4 Spacer base 01068220 5 Panel right side 01068238 6 Panel left side and rear 1 piece 01068246 7 Bushing 01026152 8 Panel top 01068253 9...

Страница 29: ...condenser 00195966 2 Fitting water 01065375 3 Fitting drain 00109728 4 Panel front 01068261 5 Spacer base 01068220 6 Panel right side 01068238 7 Tube drain 01016948 8 Panel left side and rear 1 piece...

Страница 30: ...425A W MFD425A W P425A W Ice Machines Louvered docking station MCD425A W_T 1 2 3 4 Reference Description Part 1 Louver front 01006154 2 Cover front 01068279 3 Tube drain 01055185 4 Lovered docking sta...

Страница 31: ...Hz 01064708 4 Switch clean 01229418 Not shown Bin thermostat MCD425A WBT MCD425A WHT MFD425A WBT and MFD425A WHT only 500514 Not shown Board stand off control 8 required 00903005 Not shown Relay power...

Страница 32: ...D425A W R425A W MFD425A W P425A W Ice Machines Evaporator FOOD SERVICE HEALTHCARE FLAKER FLAKER COMPONENTS 27 15 17 25 1 3 4 5 20 19 7 6 8 10 11 12 16 9 22 21 1 17 18 18 26 24 2 28 23 32 3 4 29 13 13...

Страница 33: ...in 01064674 16 Drain pan evaporator 00181990 17 Tube compression nozzle vent 01148691 18 Tube compression nozzle single drain 01148675 Not shown Grease Chevron SRI 2 14 oz 501111 19 Bracket vent hoses...

Страница 34: ...34 MCD425A W R425A W MFD425A W P425A W Ice Machines Air cooled ice machines 2 15 21 3 20 7 6 10 22 17 16 9 13 1 14 8 18 19 5 4 4 11 23 12 4...

Страница 35: ...or assembly 115 V 60 Hz 502730 12 Capacitor start 01026145 13 Fan blade 500474 14 Motor fan 115 V 60 Hz 500672 15 Bracket fan motor 01067107 Not shown Overload compressor 115 V 60 Hz 01027572 16 Compr...

Страница 36: ...36 MCD425A W R425A W MFD425A W P425A W Ice Machines Water cooled ice machines 18 2 3 3 3 17 19 20 4 10 8 5 9 21 12 13 6 11 16 16 15 7 1 22 14 23...

Страница 37: ...ly 115 V 60 Hz 502730 10 Mounting bracket gearbox 01067693 11 Bracket electrical box mounting 01068139 Not shown Overload compressor 115 V 60 Hz 01027572 12 Compressor 115 V 60 Hz 01065259 13 Coil con...

Страница 38: ...onless high capacity water filter system one per ice machine Horizon and Mae stroPlus series ice machines 01050442 Not shown Carbonless high capacity water filter cartridge primary single 01050426 Not...

Страница 39: ...25W All VU300 series with air cooled ice machines MCD425A All VU300 series with water cooled ice machines MCD425W Freestanding dispensers with ice machines in the base 25FB425A P425A 25FB425W P425W 50...

Страница 40: ...Please review the installation instructions thoroughly It is important that the installation be performed to factory specifications so your equipment operates at its maximum efficiency Follett LLC wi...

Отзывы: