HCD1010R/N, HMF1010R/N, HCD1410R/N, HMF1410R/N
5
Specifications
Electrical
Separate circuit and equipment ground required.
Evaporator unit
Standard electrical: 115/60/1
Maximum fuse: 15A
Amperage: 5A
Condensing unit
1010 Single-Phase
1010 3-Phase
1410 Single-Phase
1410 3-Phase
Electrical
208-230V, 60Hz
208-230V, 60Hz
208-230V, 60Hz
208-230V, 60Hz
Max Circuit HVACR breaker size
15A
15A
30A
25A
Min Circuit Ampacity
10.7A
9.9A
19.3A
14.2A
Evaporator plumbing
§
3/8" OD push-in water inlet (connection inside machine) - 3/8" OD tubing required.
§
Water shut-off recommended within 10 feet (3 m).
§
Follett recommends installation of Follett water filter system (part# 00130286) in ice machine inlet water line.
Flush drain plumbing
§
3/4" MPT flush drain connection at the rear of the machine.
§
Drain must slope 1/4" inch per foot (6 mm per 30.4 cm).
§
Drain line should not be shared with any other piece of equipment.
§
Drain line cannot be reduced to a size smaller than 1 inch.
§
Drain should be piped without a vent.
3/4" barb x 3/4" FPT
1" Stand pipe/Drain
2 ft. x 1" OD
silicone tubing
Minimum 8"
radius
3/4" MPT x 1" slip
1" PVC Drain
2 ft. x 1" OD
silicone tubing
3/4" MPT x 1" slip
3/4" barb x 3/4" FPT
1'
1/4" per foot
(6,4 mm per 0,3 m)
Ambient
Evaporator unit
Air temperature
100 F/38 C max.
50 F/10 C min.
Water temperature
90 F/32 C max.
45 F/7 C min.
Содержание Horizon Elite HCD1010R/N
Страница 2: ...2 HCD1010R N HMF1010R N HCD1410R N HMF1410R N...
Страница 8: ...8 HCD1010R N HMF1010R N HCD1410R N HMF1410R N Condensing unit 36 25 921 mm 25 5 648 mm 26 08 662 mm...
Страница 36: ...36 HCD1010R N HMF1010R N HCD1410R N HMF1410R N 2 12 1 4 9 5 3 8 13 14 7 11 6 10 15 16 Low side assembly...
Страница 38: ...38 HCD1010R N HMF1010R N HCD1410R N HMF1410R N Electrical box 1 7 4 3 2 8 6 5...
Страница 42: ...42 HCD1010R N HMF1010R N HCD1410R N HMF1410R N Skins assembly 10 5 4 3 6 8 7 11 9 2 1...
Страница 48: ...48 HCD1010R N HMF1010R N HCD1410R N HMF1410R N...
Страница 49: ...HCD1010R N HMF1010R N HCD1410R N HMF1410R N 49...