Loss of water
During operation, the water level cycles between the normal low (D) and normal high (C) water probes - the
fill valve (P21) cycling on and off. If continuity is not detected between the common probe (B) and normal low
(D) within 10 seconds, the
LOW WATER and TIME DELAY LEDs will come on and the machine will shut down
for the one hour time delay period. After the time delay, the fill valve will re-energize and wait for continuity
between the common probe and normal high before restarting.
LOW WATER LED will remain ON until the
water level is satisfied.