background image

Remove the burner unit as detailed in section 10.1, then remove the  lint arrestor and pilot unit by using a screwdriver to remove

the retaining screws. Clean the pilot assembly with a soft brush and blow through.  Check the aeration holes are free of any dirt

or lint.  Clean thoroughly internally, the connection can be removed from the base of the pilot unit using two spanners to make

cleaning easier.  Do not damage or try to dismantle the pilot injector.

The unit is factory set and the only check necessary is to ensure the spark gap is correct.  See specifications for gap setting.

NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE THE PILOT STAY ALIGHT

If the pilot will not stay lit there is a problem with dirt, the gas supply, or the thermocouple needs replacement. Modifications are

dangerous and can have a serious unseen effect on safety and therefore MUST not be done. Replacements must be original man-

ufacturers parts. Re-assembly is the reverse of removal. Ensure operating pressures are as stated in Section 2;  Appliance Data.

It is recommended that the catalysts are inspected for signs of damage and dirt during routine servicing procedures. The expect-

ed life of the catalysts is in excess of 11,000 hours (10 years of normal use).  After this time the catalysts should be replaced.

If there are any deposits of dirt or soot on the catalyst they should be cleaned with a soft brush and a vacuum cleaner. If removed

for cleaning ensure the seals are in good condition before replacing the catalyst. New seals will usually be required. The per-

formance of the catalysts may be checked using a combustion gas analyser as follows. Any analyser used should conform to EN

50379-3. Ignite the fire as per the operating instructions, and run at maximum setting for 15 minutes. Position gas sample probe

directly over the catalysts via the outlet grille, on top of the appliance. Record the carbon dioxide (CO2) concentration and then

the carbon monoxide (CO) concentration as displayed by the analyser - also noting the units in which the values are expressed.

Most analysers display carbon dioxide (CO2) concentrations in percentage (%) terms and carbon monoxide concentration in

parts per million (ppm) terms.

In order to calculate the combustion ratio for the appliance (CO/CO2) it is first necessary to express both gas concentrations

in terms of percentage. To convert from parts per million (ppm) to a percentage (%) divide the ppm figure by 10,000. Examples :

35ppm = 0.0035%, 15ppm = 0.0015%, 5ppm = 0.0005%. Now divide the concentration of carbon monoxide (CO) expressed in

percent by the concentration of carbon dioxide (CO2) to obtain the appliance combustion ratio.

The combustion ratio of the gasses emitted by the catalytic convertor should not exceed 0.0015.

If replacing, firstly, remove the decorative frame/glass facia (as described in section 8.3) and outer casing. The catalysts are locat-

ed on the top of the internal firebox and can be removed by unscrewing the retaining nuts securing the clamping plates. Remove

the catalysts their seals and discard. Refit the new catalysts and seals in reverse order, ensure the catalysts and the glass door have

good seals.  

Appliances that are several years old or have been extensively dismantled should be checked for soundness. It is important that

all the products of combustion pass through the catalytic converter at the top of the firebox before leaving the appliance. The

firebox is heated by lighting for a few minutes to provide a flow through the firebox. The burner is then shut off and a smoke pel-

let or match introduced at the base of the fire underneath the burner tray. Large quantities of smoke will emerge from the top

of the appliance, but none should emerge from the joints or gasket faces, especially around the door. It is important to note that

the appliance can never be expected to be 100% smoke tight and small quantities of smoke may be seen in corners of joints and

gasket faces etc without affecting safety when the fire is in operation.

10.3 CATALYSTS

10.2 PILOT ASSEMBLY

GB IE

CO (%)

CO2 (%) 

= ratio

10.4 TESTING FOR FIREBOX LEAKAGE

9

©

2016 Focal Point Fires plc.

Содержание L23 CHESHIRE

Страница 1: ...ages and layout of this booklet is owned by Focal Point Fires plc You are not permitted to copy or adapt any of the con tent without the prior written permission of Focal Point Fires plc Revision F 03...

Страница 2: ...should not be used in a room without some form of background heating present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the ro...

Страница 3: ...ection and installation of such device shall be in accor dance with the current edition of BSEN 50292 and the user must be briefed regarding the use and maintenance of such a device The appliance is d...

Страница 4: ...any vapour control bar rier is not damaged and that any structural members of the house frame are not damaged refer to section 7 0 The appliance must not be positioned vertically within 100 mm 4 of a...

Страница 5: ...eaf of a conven tional cavity brick wall or a solid wall then the wall plugs and fixing screws provided may be used Depending on the condition of the wall it may be necessary to use additional fixings...

Страница 6: ...e knob depressed in the nine o clock position for approximately ten seconds Now release the knob and the pilot should stay alight If the pilot is extinguished during use wait three min utes before rep...

Страница 7: ...e glass facia panel is supported by four M6 screws which protrude from the front of the outer casing Ensure each screw is unscrewed approximately one turn from the fully screwed in posi tion in order...

Страница 8: ...head Check the aeration holes are free from lint or dirt The pilot assembly can be removed if required by disconnecting the electrode HT lead gas pipe and unscrewing the mounting screws and lifting aw...

Страница 9: ...O concentration as displayed by the analyser also noting the units in which the values are expressed Most analysers display carbon dioxide CO2 concentrations in percentage terms and carbon monoxide co...

Страница 10: ...there is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thorou...

Страница 11: ...cess of 11 000 hours 10 years of normal use After this time the catalyst should be replaced Should any home improvements be carried out to the property after the fire is installed such as installation...

Страница 12: ...ntly fixed in position or can be moveable and can incorporate open fires including combination grates or closed fires including room heaters and stoves See figures 2 3 for fireguard examples The fireg...

Страница 13: ...low the appliance to be used until the appliance and installation is passed as safe If the pilot continues to be extinguished you must call your installer to check the operation of the complete applia...

Страница 14: ...ems such as any ceramics including coals pebbles the matrix front strips side cheeks rear panels and tapered rear panels are not covered by the 3 year guarantee For all Electric fires purchased the 3...

Отзывы: