DEBRIS COLLECTION SPACE

The mounting depth of this appliance is 108mm.

In accordance with BS 5871 part 2, minimum debris collection volumes are required behind the installed appliance. These are shown in the
table below and as dimension X on the fireplace diagram shown previously.

CLAY/CEMENT LINES OR BLOCK FLUE WHICH IS NEW, UNUSED, OR PREVIOUSLY ONLY USED WITH A GAS FIRE.

X Dimension = 20mm

UNLINED  FLUE OR CHIMNEY WHICH HAS BEEN PREVIOUSLY USED FOR A SOLID FUEL OR OIL BURNING APPLIANCE

X Dimension = 60mm

VENTILATION

No purpose provided ventilation is normally required for this appliance. The requirements of other appliances operating in the same room or
space must be taken into consideration when assessing ventilation.

If spillage is detected when commissioning the appliance, then amongst other problems there may be insufficient natural ventilation for cor-
rect operation of the flue. If the appliance does not spill with the windows open, but spillage is detected with the windows closed, this demon-
strates a lack of natural ventilation. If spillage is still detected with the windows open, the flue is at fault. Installation of an air brick is the best
solution to lack of ventilation. Any ventilation fitted must comply with BS 5871 part 2 and BS 5440 part 2. Vents fitted under or within the
immediate vicinity of the appliance must not be used as adverse effects to the operation of the ODS may occur.

Spillage detected during commissioning is almost always a result of poor flue performance that cannot be corrected by any amount of venti-
lation.

For Republic of Ireland ventilation may be required, see IS 813, ICP3, IS 327, and any other rules in force.

PREFABRICATED FLUE BOXES

This appliance can be fitted into a number of proprietary flue boxes provided that the minimum dimensions given in the diagram below are
complied with.

Constructional Note: The frame of the fire, any back panel or
other infill panels, and the flue box must be sealed together
so that there is no possibility of leakage between them.
Adequate clearances to combustible materials (e.g. false
chimney breast construction) must be maintained.

The manufacturers’ instructions for fitting the prefabricated
box shall be complied with at all times.

To fit the fire using the cable fixing kit, some minor adaption
may be necessary for certain flue boxes. A check should be
made to ensure the firebox does not obscure the flue box
outlet.

The firebox, base of the flue box, and hearth below may be
drilled to allow plugs and screws to secure installation.

It is important that the sealing requirements of the appliance
are met at all times and that the flue box is well sealed to any
back or infill panel.

Note: The DEPTH dimension is inclusive of any back or infill
panel.

UNPACKING THE APPLIANCE

Stand the carton the right way up, cut the strapping bands and remove the top endcap. Read 

all the instructions before continuing to unpack

or install this appliance.

Remove the box containing the cast front fret, and the bags containing the coals. Remove the cardboard packing pieces, and any other bags
or boxes containing fittings or other parts. When all loose parts have been removed, the outer sleeve may be lifted off to reveal the appliance.
Check that the components supplied correlate with the component checklist given in section 7.1. Please dispose of all the packaging materi-
als at you local recycling centre.

4

4.1

5.0

125mm min internal
dia twin wall flue

540mm min
opening height

350mm min
opening width

128mm
min depth

6.0

7.0

©

2008 Focal Point Fires plc.

Содержание BLENHEIM STYLE

Страница 1: ...ser for safekeeping Revision C 10 08 Country s of destination GB IE MULTIFLUE GAS FIRE RANGE BLENHEIM STYLE ELEGANCE LULWORTH Focal Point Fires plc Christchurch Dorset BH23 2BT Tel 01202 499330 Fax 01...

Страница 2: ...ad all these instructions before commencing installation This appliance must be installed in accordance with the rules in force and only used in a suf ficiently ventilated space The appliance is desig...

Страница 3: ...e installation and use of this appliance This appliance is free from any asbestos material Refractories and coal bed are constructed from ceramic fibre 1 Section 1 0 2 0 3 0 4 0 4 1 5 0 6 0 7 0 7 1 8...

Страница 4: ...more than one appliance i e not shared with a gas back boiler There must be no opening in the flue apart from the one that the appliance is installed into and the one venting the gases into the air A...

Страница 5: ...t at the back of the appliance must have a 50mm mini mum clearance between it and the back wall of the opening or any other obstruction The area immediately above the outlet must form a smooth path in...

Страница 6: ...FABRICATED FLUE BOXES This appliance can be fitted into a number of proprietary flue boxes provided that the minimum dimensions given in the diagram below are complied with Constructional Note The fra...

Страница 7: ...in the rubber to slip snugly around the outside of the supply pipe and sleeving Note DO NOT install or use the appliance without this seal in place If the hole is inadvertently opened reseal with an...

Страница 8: ...pe at its ends The open end of the gas supply pipe should be temporarily sealed to prevent ingress of dust and dirt during installation CABLE FIXING Drill four holes using a 8mm masonry bit to a depth...

Страница 9: ...d firefront will clear the supply route If the data control plate is not already fitted attach with two screws ensuring the control knob is free to be depressed fully FUEL BED LAYOUT Fit the tapered b...

Страница 10: ...t row of six pebbles on to the matrix Ensure the pebbles are firmly against the side cheeks as shown in the photograph If necessary pull the peb bles forward slightly to ensure their rear edges do not...

Страница 11: ...nition sequence as previously described and after turning the control knob through the spark position the knob should be held in and the pilot lit with a taper SETTING PRESSURE To commission the appli...

Страница 12: ...will emit a newness smell for a time after initial commissioning and that extra ventilation may be needed during this time Advise that the fire is fitted with a spillage safety device O D S If the fir...

Страница 13: ...e cleaning easier Do not damage or try to remove the pilot injector The unit is factory set and the only check necessary is to ensure the spark gap is correct See specifications for gap setting REMOVI...

Страница 14: ...or infirm are concerned Combustible items such as flooring and furniture and soft wall coverings such as blown vinyl or embossed paper may discolour if fitted too close to the fire See relevant sectio...

Страница 15: ...OT light position ensur ing the pilot has lit If not return the knob clockwise and repeat When the pilot lights after the spark keep the knob depressed for approximately ten sec onds Now release the k...

Страница 16: ...lue should be checked on an annual basis to ensure all of the product of combustion are entering the flue and that there is no excessive build up of soot The frequency of service will depend on usage...

Отзывы: