FoamPRO MultiFlo Скачать руководство пользователя страница 11

11

Installation and Operation Manual

MultiFlo

5. Change the flow through the discharge and

determine the new flow rate based on the pitot

gauge reading. Compare this value with that on the

control module display. Adjust the reading on the

display to match the calculated Pitot flow by

pressing the lower right or left buttons until the

correct reading is shown on the display.

6. Repeat steps 2 through 5 for all discharges

equipped with paddlewheel flowmeters.

7. Exit Calibration mode as previously described to

lock the adjustments into the memory of the

microprocessor. Replace the o-ring and cover

screw to prevent water and dust from entering the

microprocessor case.

FoamPro Digital Display Control Module

Once the FoamPro MultiFlo has been calibrated, it will

be necessary to calibrate the FoamPro digital display

control module. The following procedures will be used to

calibrate the digital display control module:
1. Enter calibration and setup mode for the FoamPro

foam proportioning system using the procedures in

the appropriate FoamPro System Installation and

Operation manual.

2. Proceed with the FoamPro foam proportioner

system calibration per the applicable manual.

2. Replace the cover screw and o-ring.

NOTE: Always replace the cover screw and

o-ring to keep water and dirt from entering the

control module as it can cause serious damage

to the components.

Flow Method of Calibration

The flow method of calibration is being used when the

total indicator is NOT lit.

NOTE: It is critical that an accurate flow

measuring device be used to measure the

water flow to calibrate the flowmeter. Use a

suitable size smooth bore nozzle and an

accurate fixed pitot gauge instrument. Hand

held pitot gauges are usually not very accurate.

At the first available opportunity, make sure

the system is calibrated with an accurate flow

measuring device. Determine the water flow

normally expected from the flowmeter

discharge outlet. For example, actually

establish a flow of 150 GPM (568 LPM) of

water through a nozzle and Pitot system.

1. Enter calibration mode as previously described.
2. Select one of the flowmeter equipped discharges

and connect a smooth bore nozzle and pitot gauge

to the outlet. Establish water flow through the

nozzle and measure with the pitot gauge. Adjust

the measured water flow to a convenient rate, for

example, 150 GPM

(568 LPM).

3. Press the “B FLOW” button until the light under the

flowmeter being calibrated is illuminated, and note

the flow reading shown on the display.

4. Adjust the reading on the display to match the

calculated pitot flow by pressing the lower right or

left buttons on the FoamPro MultiFlo Control

Module until the correct reading is shown.

Содержание MultiFlo

Страница 1: ...ly inspected and tested In order to maintain the high quality of your unit and to keep it in a ready condition it is important to follow the instructions on care and operation Proper use and good prev...

Страница 2: ...OPERATION 13 6 DIAGNOSTIC PROCEDURES 14 7 PARTS IDENTIFICATION 15 8 INSTALLATION TEMPLATE 16 9 WARRANTY 20 NOTE TO SYSTEM INSTALLERS IMPORTANT Please provide a copy of the FoamPro manual to the end us...

Страница 3: ...it Improper handling and forcing connections can damage these cables which could result in other system damage 1 Always disconnect the power source before attempting to service any part of the FoamPro...

Страница 4: ...with foam concentrate by a single foam injection point Figure 1 FoamPro MultiFlo Control Module and Digital Display Control Module FoamPro MultiFlo Control Module Digital Display Control Module The F...

Страница 5: ...ortioner being used For example If the FoamPro 2001 foam proportioning system is used the maximum foam concentrate flow will be 2 6 GPM 9 8 LPM When the foam concentrate injection is set to 0 1 the am...

Страница 6: ...has five connectors on the back of the case see Figure 3 to connect the cables from the flowmeters and FoamPro Digital Display Control Module The FoamPro MultiFlo Control Module receives operating po...

Страница 7: ...lowmeter see Figure 5 10 times is even better the longer the straight run the lower the turbulence Here are some examples of required straight run Pipe Recommended Size Straight Run Pipe 11 2 38 mm 71...

Страница 8: ...mPro Digital Display Control Module Connect the cables from the flowmeter sensors to the connectors marked A B C or D on the back of the control module see Figure 3 If all connections are not used mak...

Страница 9: ...aking round coils see Figure 8 Install clamp on beads at the locations indicated in Figure 7 Use a small amount of RTV silicone electrical tape or heat shrink tubing to keep the beads from moving afte...

Страница 10: ...re 1 Remove the cover screw and the o ring to the left of the display readout panel on the MultiFlo Control 4 Calibration Procedures Module see Figure 9 Use a 3 32 allen wrench to remove the screw and...

Страница 11: ...e cover screw and o ring to keep water and dirt from entering the control module as it can cause serious damage to the components Flow Method of Calibration The flow method of calibration is being use...

Страница 12: ...dust from entering the control module 8 Proceed with the FoamPro foam proportioner system calibration per the applicable manual Total Volume Method of Calibration If a pitot gauge is not available th...

Страница 13: ...l match is when water or foam solution is flowing through one paddlewheel flowmeter equipped discharge The FoamPro MultiFlo Control Module constantly monitors the flow signals from the flowmeter senso...

Страница 14: ...control module display for any one of the paddlewheel flowmeters the flowmeter cable or flowmeter sensor could be defective and further diagnosis is required If no reading shows for any flowmeter the...

Страница 15: ...ng 3 2660 0030 11 2 NPT Paddle Wheel Flowmeter Assembly Note 1 Bore 2660 0031 11 2 NPT Paddle Wheel Flowmeter Assembly 2660 0032 2 NPT Paddle Wheel Flowmeter Assembly 2660 0033 21 2 NPT Paddle Wheel F...

Страница 16: ...ation and Operation Manual 8 4 25 2 75 4 25 78 3 50 3 70 10 24 x 44 DP 4 Holes Display requires a 3 875 inch 98mm diameter hole to be drilled in operator panel Additional space 3in 76mm required for c...

Страница 17: ...1 2 8 NPT 3 Pipe 5 3 8 137 mm 4 9 16 116 mm 20 750 8 900 2600 0033B 2 1 2 11 BSP 3 Pipe 5 3 8 137 mm 4 9 16 116 mm 20 750 8 900 2660 0034 3 8 NPT 4 Pipe 5 1 2 140 mm 4 7 8 124 mm 30 1150 12 1380 2600...

Страница 18: ...18 Installation and Operation Manual N O T E S...

Страница 19: ...19 Installation and Operation Manual MultiFlo N O T E S...

Страница 20: ...cts as above stated THERE ARE NO OTHER EXPRESS WARRANTIES ANY IMPLIED WARRANTIES INCLUDING IMPLIED WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO ONE YEA...

Отзывы: