FNW FIGURE 751 Скачать руководство пользователя страница 5

DUCTILE IRON FLANGED GATE VALVE

FIGURE 751

FNW.COM

We reserve the right to modify or improve the designs or 

specifications of our products at any time without notice.

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

©2022 Ferguson Enterprises, LLC 0522 4108704

FREQUENT INSPECTION 

Frequent inspections are recommended for safe, uninterrupted operation of the valve. Frequent inspections should include:

 

Inspect packing gland areas, flange connections, bonnet flanges, threaded areas, body surfaces and any media fluid leakage. 

Packing gland, flange and bonnet flange leaks should be handled as described in the maintenance section. 

For leaks through the valve body surface, consult a valve repair specialist.

 

Listen for abnormal noise from the valve, loose bolts or pipe vibration. With frequent inspection, familiarity can better distinguish 

abnormal noise from normal noise. Loose bolts should be tightened immediately. Unusual noise or piping vibration should be brought 

to the attention of the piping engineer.

 

Visually confirm the correct operating position of the valve, whether the bolts are firm, and whether the valve stem has sufficient 

lubrication. The valve should be operated in the fully open or fully closed position as described in the operation section. 

Intermediate positioning is not recommended. If necessary, immediately tighten any loose bolts and grease around the valve stem.

PERIODIC INSPECTION

Valves should be inspected periodically to detect wear on the stem, stem nut, internal corrosion of the valve body or bonnet, and wear 

on the packing. Typically, packing and gaskets are replaced during periodic inspections as part of a basic maintenance program. Periodic 

inspections should include the following, which are described in more detail in the maintenance section:

 

Valve disassembly

 

Examination of valve components

 

Component repair and/or replacement

 

Valve reassembly

 

Test and inspections

MAINTENANCE

Valve components are subject to normal wear and tear and must be inspected and replaced as needed. The frequency of inspection and 

maintenance depends on the severity of the conditions of use.

WARNING

To avoid personal injury or property damage due to fluid leakage, before performing any maintenance do the following:

 

Shut off the pipeline.

 

Completely isolate the valve from the piping.

 

Release process pressure.

 

Drain the process fluid from the valve.

PRELIMINARY

Before removing from the pipe, mark the edges of the valve and pipe flange so that the valve can be returned to its original position. 

If multiple valves are to be inspected and they are not already marked, number the valves and flanges separately for proper matching 

during maintenance. 

 

Содержание FIGURE 751

Страница 1: ...ction to ensure that there is no water accumulation on or in the valve The valve comes with a protective end cap to prevent mechanical damage and prevent the intrusion of dust and foreign objects If a...

Страница 2: ...er the valve is installed re check all the bolts and nuts of the connecting flanges and re tighten them if they are found to be loose OPERATION Gate valves are not designed for throttling modulating s...

Страница 3: ...tightend Inadequate amount of packing rings Install additonal packing rings Packing is hard and dry Replace with new packing Leakage through the stem packing Packing was not properly cut and staggered...

Страница 4: ...Repair damaged area and install a new gasket Valve is not properly seated Check with hand wheel to see if the valve is tightly closed Leakage past the seat There is an obstruction between the seat and...

Страница 5: ...in the operation section Intermediate positioning is not recommended If necessary immediately tighten any loose bolts and grease around the valve stem PERIODIC INSPECTION Valves should be inspected p...

Страница 6: ...e or other foreign matter Wipe disc 4 with a cloth Clean body 5 and bonnet 2 inside and outside surfaces and all nuts and bolts Put packing 3 into the packing groove of bonnet 2 align and center the p...

Страница 7: ...e valve stem with a cloth soaked in solvent Count the original number of packing rings If replacing with new packing use a sharp tool to cut each ring at a 45 angle see Figure 2 stagger adjacent packi...

Страница 8: ...E DEFECTIVE PRODUCT S PURCHASED DURING THE PREVIOUS CONTRACT YEAR Labor Allowance Seller makes NO ADDITIONAL ALLOWANCE FOR THE LABOR OR EXPENSE OF REPAIRING OR REPLACING DEFECTIVE PRODUCTS OR WORKMANS...

Отзывы: