DUCTILE IRON FLANGED GATE VALVE

FIGURE 751

FNW.COM

We reserve the right to modify or improve the designs or 

specifications of our products at any time without notice.

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

©2022 Ferguson Enterprises, LLC 0522 4108704

Problem

Possible Causes

Remedy

Gland nuts are loose

Tighten gland nuts

Leakage through 

 the stem packing

Gland is binding against

the stem

Check to ensure that the gland is centered

and evenly tightend

Inadequate amount of

packing rings

Install additonal packing rings

Packing is hard and dry

Replace with new packing

Leakage through 

 the stem packing

Packing was not properly

cut and staggered

Replace with new packing

Stem is damaged

Repair or replace as required

Stem is binding

during travel

Remove dirt and lubricate stem with grease

Hand wheel is 

difficult to turn

Stem packing is exerting

excessibe force on stem

Check torque on gland nuts

Stem is damaged

Examine stem through full open and close action. 

Repair or replace as required.

Internal components

may be damaged

Disassemble the valve.

Inspect and repair as needed.

TROUBLESHOOTING

Содержание FIGURE 751

Страница 1: ...ction to ensure that there is no water accumulation on or in the valve The valve comes with a protective end cap to prevent mechanical damage and prevent the intrusion of dust and foreign objects If a...

Страница 2: ...er the valve is installed re check all the bolts and nuts of the connecting flanges and re tighten them if they are found to be loose OPERATION Gate valves are not designed for throttling modulating s...

Страница 3: ...tightend Inadequate amount of packing rings Install additonal packing rings Packing is hard and dry Replace with new packing Leakage through the stem packing Packing was not properly cut and staggered...

Страница 4: ...Repair damaged area and install a new gasket Valve is not properly seated Check with hand wheel to see if the valve is tightly closed Leakage past the seat There is an obstruction between the seat and...

Страница 5: ...in the operation section Intermediate positioning is not recommended If necessary immediately tighten any loose bolts and grease around the valve stem PERIODIC INSPECTION Valves should be inspected p...

Страница 6: ...e or other foreign matter Wipe disc 4 with a cloth Clean body 5 and bonnet 2 inside and outside surfaces and all nuts and bolts Put packing 3 into the packing groove of bonnet 2 align and center the p...

Страница 7: ...e valve stem with a cloth soaked in solvent Count the original number of packing rings If replacing with new packing use a sharp tool to cut each ring at a 45 angle see Figure 2 stagger adjacent packi...

Страница 8: ...E DEFECTIVE PRODUCT S PURCHASED DURING THE PREVIOUS CONTRACT YEAR Labor Allowance Seller makes NO ADDITIONAL ALLOWANCE FOR THE LABOR OR EXPENSE OF REPAIRING OR REPLACING DEFECTIVE PRODUCTS OR WORKMANS...

Отзывы: