FNW FIGURE 751 Скачать руководство пользователя страница 1

DUCTILE IRON FLANGED GATE VALVE

FIGURE 751

FNW.COM

We reserve the right to modify or improve the designs or 

specifications of our products at any time without notice.

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

©2022 Ferguson Enterprises, LLC 0522 4108704

INTRODUCTION

This instruction manual provides storage, installation, operation and maintenance information for ductile iron flanged gate valves. 

This manual describes 300PSI ductile iron valves. Valves are intended for use in water service. Do not use in steam or 

hydrocarbon service.

STORAGE

Be careful not to damage the valve stem while handling. If the valves are rack mounted for storage, their packing chambers should 

not be in direct contact with the rack. It is not recommended to place the valve directly on the ground or concrete floor.

TEMPORARY STORAGE

If the valve is to be temporarily stored prior to installation, the following rules should be followed: 

 

Always keep the valve wrapped and protected.

 

It is best to store the valve in a dust-free, well-ventilated and low-humidity area.

 

If stored outdoors, please ensure that the valve is protected by good environmental protection to ensure that there is no water 

accumulation on or in the valve.

 

The valve comes with a protective end cap to prevent mechanical damage and prevent the intrusion of dust and foreign objects. 

If an end cap is found to be missing after shipping, use the appropriate type of end protector immediately.

 

The valve should remain in the half-open position.

LONG TERM STORAGE

If the valve is to be stored for more than one year, it should be prepared following the rules above, as well as the following additional rules: 

 

Do not store the valve outdoors.

 

Remove packaging and apply preservative to exposed areas of the valve.

 

Do the following annually: 

   • Apply lubricant to exposed areas.

      • Apply a protective surface coating to the outside of the valve as required. Make sure the surface area is clean before applying 

        the protective spray.

INSTALLATION

WARNING

To avoid personal injury or property damage due to valve leakage, do the following before installation: 

• Shut off the pipeline.

• Completely isolate the valve from the piping.

• Relieve pipeline pressure.

• Drain water from the valve.

 

Remove protection cover of the valve.

 

Inspect the valve body ports and associated equipment for damage and any foreign objects that may have been present during 

shipping or storage. Blow compressed air into the valve, making sure the inside of the valve body is clean.

Содержание FIGURE 751

Страница 1: ...ction to ensure that there is no water accumulation on or in the valve The valve comes with a protective end cap to prevent mechanical damage and prevent the intrusion of dust and foreign objects If a...

Страница 2: ...er the valve is installed re check all the bolts and nuts of the connecting flanges and re tighten them if they are found to be loose OPERATION Gate valves are not designed for throttling modulating s...

Страница 3: ...tightend Inadequate amount of packing rings Install additonal packing rings Packing is hard and dry Replace with new packing Leakage through the stem packing Packing was not properly cut and staggered...

Страница 4: ...Repair damaged area and install a new gasket Valve is not properly seated Check with hand wheel to see if the valve is tightly closed Leakage past the seat There is an obstruction between the seat and...

Страница 5: ...in the operation section Intermediate positioning is not recommended If necessary immediately tighten any loose bolts and grease around the valve stem PERIODIC INSPECTION Valves should be inspected p...

Страница 6: ...e or other foreign matter Wipe disc 4 with a cloth Clean body 5 and bonnet 2 inside and outside surfaces and all nuts and bolts Put packing 3 into the packing groove of bonnet 2 align and center the p...

Страница 7: ...e valve stem with a cloth soaked in solvent Count the original number of packing rings If replacing with new packing use a sharp tool to cut each ring at a 45 angle see Figure 2 stagger adjacent packi...

Страница 8: ...E DEFECTIVE PRODUCT S PURCHASED DURING THE PREVIOUS CONTRACT YEAR Labor Allowance Seller makes NO ADDITIONAL ALLOWANCE FOR THE LABOR OR EXPENSE OF REPAIRING OR REPLACING DEFECTIVE PRODUCTS OR WORKMANS...

Отзывы: