background image

• Set 

 (Operation Modes for External Terminals) to 

 

for “3-wire program initialization”.  

• Set 

 (Main Frequency Command Source) to 

 for 

External AVI Analog Signal input. 

• See 

Diagram 3

 for 3-wire control.

S1

S2

S3 Forward/Reverse

selection

COM

Run (N.O.Momentary)

Stop

(N.C. Momentary)

Stop Command

Run Command

+10V: Max.  20mA

AVI: 0-10VDC Analog Input

AG ND: Analog Signal Common

(N.O.Maintained)

FOR / REV

Potentiometer:

2kΩ – 10kΩ

S1

S2

COM

Forward

Reverse

Setting 00: 2-Wire FWD/REV External Control (default)

2-Wire External Control Operation

Setting 02: 3-wire Control, FWD/REV Selector, with 

External Speed Pot.

REVERSE

FORWARD

STOP

RUN

REV

FOR

SPEED

100

1

100

100

0

2-Wire External Control Operation

2. Press MODE/PROG. 

Display shows 

3. Use navigation keys to 

go to 

+

4. Press and 

hold LEFT/ 
ENTER then 
use nav. keys 

to enter 

 

”External 
Terminal”

5. Press and hold 

READ/ENTER to save. 
Display shows 

8. Press MODE/PROG 

until display shows 
motor frequency.

Terminal S1

Terminal S2

Operation

Open

Open

Stop AC Drive

Closed

Open

Run Forward

Open

Closed

Run Reverse

Closed

Closed

Stop AC Drive, Display EF9 Alarm after 
500ms

Terminal S1

Terminal S2

Operation

Open

Open

Stop AC Drive

Closed

Open

Run Forward

Closed

Closed

Run Reverse

3-Wire External Control Operation

Terminal S1

Terminal S2

Terminal S3

Operation

Open

Open

Open

Stop AC Drive

Closed

Open

Closed

Stop AC Drive

Open

Closed

Open

Run Forward

Closed

Closed

Closed

Run Reverse

6. Set 

 to desired control mode below: 

      For default configuration (FWD/REV), go to Setting 00 
      For 2-wire RUN/STOP mode, go to Setting 01 
      For 3-wire control mode, go to Setting 02

Note:

 Terminal S1 must be closed for a minimum of 

50ms to activate operation. 

Set Main Command Source (Optional)

STEP  

7

STOP

RUN

REV

FOR

S1

S2

COM

Run / Stop

Forward / 
Reverse

Setting 01: 2-Wire RUN/STOP External Control

• Set 

 (Operation Modes for External Terminals) to 

 

• See 

Diagram 2

 for 2-wire RUN/STOP control.

Return to AC Drive Status Display

• The default value of 

 (Operation Modes for External 

Terminals) is 

 

“2-Wire FWD/REV External Control” 

• See 

Diagram 1

 for 2-wire FWD/REV control.

Diagram 1: 2-Wire FWD/REV External Control (default)

Diagram 2: 2-Wire RUN/STOP External Control

Diagram 3: 3-wire Control, FWD/REV Selector, with 

External Speed Pot.

1. Set 

 

to 

 

using the steps below.

7. Leave 

 (S1 Multi-function Input) as 

 and  

 (S2 Multi-function Input) as 

.

Example Procedure