Circuit protection must be installed before AC drive. See section 2.3  
of the user manual for the appropriate circuit breaker for your drive. 
 
AC Drive and motor-side ground. Improper grounding could result  
in serious injury or death from contacting the motor case. 
Grounding impedance: 240V class - less than 100Ω,  
480V class - less than 10Ω  
Do not connect any other terminal to ground.  
 
Only the ground terminal with the          symbol should be  
connected to ground. 
 
MAIN CIRCUIT POWER SUPPLY TERMINALS MUST BE  
CORRECTLY WIRED  
 
Single Phase Input:  L1(L) and L3(N) 
Three Phase Input:  L1(L), L2, and L3(N) 
 
MOTOR CONNECTION ONLY: T1, T2, T3  
(input power connection here will destroy the AC Drive)

L1 (L)

L2

L3 (N)

AC Line 

Reactor

Circuit 

Protection

AC Input Voltage

Disconnect

3PH Input Models

1PH Input Models

Power Terminal Descriptions

Terminal

Function

L1(L)

Power input

Single phase

L1(L)/L3(N)

L2

Three phase

L1/L2/L3

L3(N)

T1

AC Drive output, connect to U/V/W terminals of motor

T2

T3

P

Externally connected braking resistor, 480V models only  
(Please see the braking resistors reference table in user manual)

BR

Ground terminal

Wiring the AC Drive

STEP  

3

WARNING

 

 
Depending on the AC drive model, terminal labels and layouts may be 
slightly different. Please see table below for details on terminal labels 
and their functions.

NOTE

 

 

1: Only 480V 1-3HP units have a built-in braking 

transistor. The braking resistor can be 
connected directly between P and BR. All 
others do not have external braking 
capabilities. 

2: Grounding impedance: 240V class - less than 

100Ω, 480V class - less than 10Ω  
Greater impedance indicates a poor ground.

 

NOTE

L1

L2

L3

T1

T2

T3

P

BR

3Ø Induction motor

10V: Max.  20mA

            

AVI: Multi-Function Analog Input

ACI: Multi-Function Analog Input

S1

AO

AG ND

Analog Output 

0 – 10 VDC

S2

S3

S4

S5

Multi-Functional Digital I nputs

(Default Settings)

Preset Speed 2

Preset Speed 1

FWD /  STOP

REV / STOP

Braking Connection

COM (NPN)

   

AG ND: Analog Signal Common

Multi-function

Relay Out put

Contact rating: 

• 250VAC < 1.0A 
• 30VDC < 1.0A

RA

RB

Reset

NO

 

Shielded wire 

Control circuit

Main circuit

Note: 1

AC Line 

Reactor

Circuit 

Protection

AC Input Voltage

Motor

External Analog Inputs

0 – 10V or

0 – 20mA

Potentiometer:

Disconnect

Note: 2

RS485 COM1

RJ45

1:RS485+

2:RS485-

7: 5V

8: GND

1

2

7

8

L1

L2

L3

AC Line 

Reactor

Circuit

Protection

AC Input Voltage

Disconnect