Default Acceleration and Deceleration times are listed below. 

Set 

 (Acceleration Time 1) and 

 

(Deceleration Time 1) to 

desired times.

Refer to the motor nameplate for FLA (Amps) when setting up the 
drive. For this example we will use a 

460V

 motor rated at 

1.5

 Full 

Load Amps. Refer to the motor nameplate for FLA required at the 
voltage in your application. An example nameplate is shown below:

1. Press MODE/PROG. 

Display shows 

+

2. Use navigation keys to 

go to 

3. Press and 

hold LEFT/ 
ENTER then 
use navigation 
keys to enter 
FLA of 

4. Press and hold 

LEFT/ENTER to save. 
Display shows 

+

5. Press 

MODE/PROG 
twice. Display 
shows motor 
frequency.

Commonly Used Parameters

I.D.

Default

Function

Setting Range

00-02

0

Main Run Command 
Source Selection

0: Keypad 
1: External Terminal (Control 

Circuit)  

2: Comm. Control (RS-485)

00-04

0

Operation Modes for 
External Terminals

0: Forward/Stop-Reverse/Stop 
1: Run/Stop- Reverse/Forward 
2: 3 Wire Control Mode Run/Stop

00-05

1

Main Frequency 
Command Source

0: UP/DOWN from Keypad 

1: Potentiometer on Keypad 

2: External AVI Analog Input 

3: External ACI Analog Input 

4: External Up/Down Frequency 

5: Communication Setting Freq. 

6: PID Output Frequency

00-12

60

Frequency Upper Limit

0.01–599.00 Hz

00-13

0

Frequency Lower Limit

0.01–598.99 Hz

00-14

10.0

Acceleration Time 1

0.1–6000.0 s

00-15

10.0

Deceleration Time 1

0.1–6000.0 s

01-00

4

Volts/Hz Patterns

1-7

02-01

Rated Current of Motor 1 
(Amps)

Setting range is dependent on AC 
drive model

07-09

0

Stop Mode

0: Deceleration to Stop 

1: Coast to Stop

I.D.

Default

Function

Setting Range

00-14

10.0

Acceleration Time 1

0.1–6000.0 s

00-15

10.0

Deceleration Time 1

0.1–6000.0 s

Set Accel. / Decel. Times (Optional)

STEP  

6

Check Motor Direction

STEP  

4

Set Motor FLA

STEP  

5

 

 

Internal capacitors hold a charge after power supply has been removed. 
After disconnecting power, wait at least 10 minutes before touching any 
wiring, circuit boards, or components. 
 
Make sure it is safe to operate the AC Drive and motor before testing 
motor direction.

WARNING

4. If motor does not turn in the desired direction: Remove power from 

AC Drive and wait at least ten minutes for the capacitor charge to 
drain completely. Swap T1 and T2 output leads at the AC Drive. 
Repeat steps 1 and 2 to re-check the motor direction.

This test is to be performed solely 
from the AC Drive keypad. Following 
procedures assume all AC Drive 
parameters are at default values and 
all motor and input wiring has been 
completed correctly. 
 
1. Apply input power to the AC Drive. 

The display blinks, showing the 
current output frequency setting. 
(Set using the keypad potentiometer 
by default) 

 

 
2. Press the 

       

 key. Motor will 

operate at the speed set. Frequency 
display on the keypad will be solid.  

 

 
3. Press the 

       

 key to stop the 

motor.

PH

FRAME

HP(kW)

RPM

ENCL

TYPE

PF

IP55

SF

INS CL

CODE

HZ

NEMA NOM EFF

3/4 LOAD EFF

DES

VOLTS

AMPS

DUTY

SFA

MAX AMB

INVERTER DUTY MOTOR

3

56

1(0.75)

3470

TEFC

0.88

1.25

F

K

60

86.5

86.5

B

208-230/460

3.3-3.0/1.5

Cont

40C

 

Keypad Potentiometer 

(Default Frequency Source)

Example Motor Nameplate

Example Procedure