Default Acceleration and Deceleration times are listed below.
Set
(Acceleration Time 1) and
(Deceleration Time 1) to
desired times.
Refer to the motor nameplate for FLA (Amps) when setting up the
drive. For this example we will use a
460V
motor rated at
1.5
Full
Load Amps. Refer to the motor nameplate for FLA required at the
voltage in your application. An example nameplate is shown below:
1. Press MODE/PROG.
Display shows
+
2. Use navigation keys to
go to
3. Press and
hold LEFT/
ENTER then
use navigation
keys to enter
FLA of
4. Press and hold
LEFT/ENTER to save.
Display shows
+
5. Press
MODE/PROG
twice. Display
shows motor
frequency.
Commonly Used Parameters
I.D.
Default
Function
Setting Range
00-02
0
Main Run Command
Source Selection
0: Keypad
1: External Terminal (Control
Circuit)
2: Comm. Control (RS-485)
00-04
0
Operation Modes for
External Terminals
0: Forward/Stop-Reverse/Stop
1: Run/Stop- Reverse/Forward
2: 3 Wire Control Mode Run/Stop
00-05
1
Main Frequency
Command Source
0: UP/DOWN from Keypad
1: Potentiometer on Keypad
2: External AVI Analog Input
3: External ACI Analog Input
4: External Up/Down Frequency
5: Communication Setting Freq.
6: PID Output Frequency
00-12
60
Frequency Upper Limit
0.01–599.00 Hz
00-13
0
Frequency Lower Limit
0.01–598.99 Hz
00-14
10.0
Acceleration Time 1
0.1–6000.0 s
00-15
10.0
Deceleration Time 1
0.1–6000.0 s
01-00
4
Volts/Hz Patterns
1-7
02-01
–
Rated Current of Motor 1
(Amps)
Setting range is dependent on AC
drive model
07-09
0
Stop Mode
0: Deceleration to Stop
1: Coast to Stop
I.D.
Default
Function
Setting Range
00-14
10.0
Acceleration Time 1
0.1–6000.0 s
00-15
10.0
Deceleration Time 1
0.1–6000.0 s
Set Accel. / Decel. Times (Optional)
STEP
6
Check Motor Direction
STEP
4
Set Motor FLA
STEP
5
Internal capacitors hold a charge after power supply has been removed.
After disconnecting power, wait at least 10 minutes before touching any
wiring, circuit boards, or components.
Make sure it is safe to operate the AC Drive and motor before testing
motor direction.
WARNING
4. If motor does not turn in the desired direction: Remove power from
AC Drive and wait at least ten minutes for the capacitor charge to
drain completely. Swap T1 and T2 output leads at the AC Drive.
Repeat steps 1 and 2 to re-check the motor direction.
This test is to be performed solely
from the AC Drive keypad. Following
procedures assume all AC Drive
parameters are at default values and
all motor and input wiring has been
completed correctly.
1. Apply input power to the AC Drive.
The display blinks, showing the
current output frequency setting.
(Set using the keypad potentiometer
by default)
2. Press the
key. Motor will
operate at the speed set. Frequency
display on the keypad will be solid.
3. Press the
key to stop the
motor.
PH
FRAME
HP(kW)
RPM
ENCL
TYPE
PF
IP55
SF
INS CL
CODE
HZ
NEMA NOM EFF
3/4 LOAD EFF
DES
VOLTS
AMPS
DUTY
SFA
MAX AMB
INVERTER DUTY MOTOR
3
56
1(0.75)
3470
TEFC
0.88
1.25
F
K
60
86.5
86.5
B
208-230/460
3.3-3.0/1.5
Cont
40C
Keypad Potentiometer
(Default Frequency Source)
Example Motor Nameplate
Example Procedure