Operation Manual EMGZ 490 

 

 

15.12.2015

 

 

22 

 

7.3

 

Limitations 

In order for the EMGZ490 to not reach system limitations, one should avoid the use of 
some services during operation. These services are: 

 

Port scanning 

 

Web services 

 

Stress tests 

 

As well as all other not-PROFINET related services and protocols 

 

The use of ring topology is not permitted. 

 

 

Caution

 

During operation the use of not-PROFINET related services and protocols should be 
avoided. There is the possibility of a system overload, if such a service is nonetheless 
used. The consequence is a connection interruption between EMGZ490 and PLC. The 

interruption usually lasts between 3-5 seconds. Afterwards, a new connection is 
automatically established again. 

 

 
 

7.4

 

Functional Blocks, Example 

Three functional blocks (FB1, FB2, FB3) were configured. These FBs were loaded to the 
controller 

 

Name 

Description 

Function 

FB1 FMS_READ_FB 

Reads a data package from the 
specified slot and index 

FB2 

FMS_WRITE_FB 

Writes a data package from the 
specified slot and index 

FB3 FMS_CYCLIC_FB 

Reads cyclic data and writes it to a DB 

 

The functional blocks are fetched cyclically, and if a read or write-instruction is required, 

it is carried out. In PROFINET usually the organisational block OB1 is used, which is 
fetched once every cycle. The sequence of function calls is shown in the following 
diagram

 

 

 

Содержание EMGZ 490

Страница 1: ...ersion V1 16 GSDML file V2 3 This operation manual is also available in German Please contact your local FMS representative Diese Bedienungsanleitung ist auch in Deutsch erh ltlich Bitte kontaktieren...

Страница 2: ...n 9 4 3 Calibration Procedure 10 4 4 Gain 10 4 5 Limit Violations 11 4 6 Description of Signal LEDs 12 5 Integration in a PROFINET network 13 5 1 PROFINET Interface 13 5 2 MAC Address 13 5 3 Assignmen...

Страница 3: ...8 8 3 Offset Compensation and Calibration over the Web Browser 29 8 4 Ethernet Settings 30 8 5 System Settings 31 9 Mechanical Dimensions 32 10 Technical Specification 34 10 1 PROFINET Characteristics...

Страница 4: ...igh risk for persons to get health injury or loss life It has to be followed strictly b Risk of damage of machines Caution This symbol refers to information that if ignored could cause heavy mechanica...

Страница 5: ...erature of the amplifiers that are mounted in a cabinet to a minimum a distance of at least 15mm 0 6 between the devices must be kept During operation the use of not PROFINET related services such as...

Страница 6: ...Description EMGZ 490 The microprocessor controlled amplifiers of EMGZ 490 series are used to amplify process and transmit force sensor signals to devices connected in a suitable network The measured f...

Страница 7: ...on ref to chapters 4 1 to 4 3 4 If required do additional settings chapter 8 2 5 In tegrate the amplifier in the PROFINET network chapter 5 3 3 Installation and Wiring Caution In order to improve the...

Страница 8: ...25mm2 AWG 23 shielded twisted pair cable The cable must be installed separate from power lines Fig 2 Wiring Diagram EMGZ 490 Color scheme IEC60757 and pin codes are valid for FMS components only Cauti...

Страница 9: ...the Gain adjusts the controller and load cells so that the display gives you the actual tension value There are two methods of calibrating the system The first method uses a defined weight The second...

Страница 10: ...prevailing force is not passed one to one to the sensors with the result that the measured material tension does not correspond to the effective force In order to account for this error the measured...

Страница 11: ...ost accurate results 4 5 Limit Violations The amplifier checks the analogue input and output on limit violations It checks whether the force sensor is mechanically overloaded overload test At the outp...

Страница 12: ...w The overflow is thus triggered at the output reaching the theoretically calculated value 10 05V For the underflow applies value of 0 05V Upon reaching one of these limits the corresponding Status Bi...

Страница 13: ...the network card of the corresponding device It is set at the factory for each EMGZ 490 device and subsequently it cannot be changed The MAC address is lost after a firmware update It must be re assig...

Страница 14: ...ce as a FMS product worldwide 5 4 TCP IP Configuration In order to enable data communication between amplifier and a PLC or a web browser the Ethernet settings must be known In a PROFINET network the...

Страница 15: ...mode For normal operation the assignment of the address over the PLC is required 5 5 System Start up At system start up the communication between IO controller PLC and IO devices is established and n...

Страница 16: ...Parameter Range Selection Default Min Max Hz 0 1 200 0 10 0 Analog Output Filter Use The amplifier provides a low pass filter to prevent noise and interferences being overlaid to the analogue output s...

Страница 17: ...Offset The offset value is used to compensate the weight of the measuring roller Unit Parameter Range Selection Default Min Max 8000 8000 0 Gain Use This parameter stores the value determined with th...

Страница 18: ...lue in Newton signed long signed 32 Bit 200 000 000 0 000 N Filtered feedback value re calculated in Newton Feedback Value in Pound signed long signed 32 Bit 200 000 000 0 000 lb Filtered feedback val...

Страница 19: ...0 Request Device Type 0x0 2 R Version unsigned int unsigne d 16 Bit 1 to 10000 0 00 Request Firmware Version 0x1 0 R W Low pass filter feedback active PROFIN ET byte unsigne d 8 Bit 0 bis 1 0 Switch f...

Страница 20: ...ow pass filter feedback PROFINET unsigned int unsigne d 16 Bit 1 to 2000 0 0 Hz Cut off frequency of PROFINET filter 0x2 5 R W Cut off frequency low pass filter Analogue output unsigned int unsigne d...

Страница 21: ...odel of the controller The controller will execute the read write instruction via PROFINET and send back the status or the data to the computer 7 2 Services and Protocols The EMGZ490 is certified in a...

Страница 22: ...ption between EMGZ490 and PLC The interruption usually lasts between 3 5 seconds Afterwards a new connection is automatically established again 7 4 Functional Blocks Example Three functional blocks FB...

Страница 23: ...were defined DB1 FMS_ACYCLIC_DB Name Type Start Value Comment Index INT 0 FMS specific index VALUE_READ DINT L 0 Input value VALUE_WRITE DINT L 0 Output value DB2 FMS_TRIGGER_DB Name Type Start Value...

Страница 24: ...an application in the controller Using a one time write trigger FMS_TRIGGER_DB READ_TRIGGER a read command can be forced The trigger is automatically reset If the read command was successful the data...

Страница 25: ...n t interfere with each other a new module in the PROFINET IO device configuration was introduced The graph Fig 8 shows the actual module configuration Fig 8 Module configuration EMGZ E490014 Each slo...

Страница 26: ...appear see Fig 10 Caution The web interface may only be used in the test mode since data communication can interfere with the PLC Moreover one link can be established via a web browser at the same tim...

Страница 27: ...rrent Reading E490016 The web page Current Reading shows the actual values of the amplifier The first line Tension shows the tension at the input in the configured unit of measure In the second line O...

Страница 28: ...5 28 8 2 Parameter Setting Fig 12 Parameter list E490017 The web page Parameters provides the possibility to configure the amplifier via the web interface It is to notice that in a PROFINET environmen...

Страница 29: ...owser For gain adjustment the page Offset Calibration is available This page offset compensation and calibration These functions are also available via the PLC If the offset and gain values known they...

Страница 30: ...0 15 12 2015 30 8 4 Ethernet Settings This page displays the actual TCP IP configuration It cannot be changed via the web interface Changes to this configuration have to be done over the PLC Fig 14 Et...

Страница 31: ...ration Manual EMGZ 490 15 12 2015 31 8 5 System Settings Via the page System Settings the internal firmware version is displayed Furthermore a new firmware can be up loaded Fig 15 System Settings E490...

Страница 32: ...is available in two different housing options Fig 16 Outline Drawing EMGZ309 R rail mount housing E490002e Ethernet connection RJ 45 connector 108 2 4 26 107 3 4 2 65 2 56 Fig 16 Outline Drawing EMGZ...

Страница 33: ...Operation Manual EMGZ 490 15 12 2015 33 Fig 17 Outline Drawing EMGZ309 W wall mount housing E490003e Ethernet connection M12 4 pole D coded...

Страница 34: ...ng of alarm information LLDP Link Layer Discovery Protocol for proximity detection DCP Discovery and Configuration Protocol request and config of IP Device name etc over network layer SNMP Simple Netw...

Страница 35: ...12 Bit Analogue Output 0 10V min 1 2k Resolution of D A Converter 0 4096 12 Bit Measuring Error 0 05 FS Cycle for Data Exchange 1ms Interface Connectors EMGZ 490 R 2x RJ 45 EMGZ 490 W 2x M12 4 pole D...

Страница 36: ...com FMS Italy Via Baranzate 67 I 20026 Novate Milanese Tel 39 02 39487035 Fax 39 02 39487035 fmsit fms technology com FMS USA Inc 2155 Stonington Ave Suite 119 Hoffman Estates IL 60169 USA Tel 1 847 5...

Отзывы: