www.fmiproducts.com
112108-01F
29
5. Smell for gas, including near the floor. If
you smell gas, STOP! Follow “B” in the
safety information, page 28. If you don’t
smell gas, go to the next step.
6. Turn main burner wall switch to the ON
position for ignition. There will be a spark
at the electrode. The electrode is located by
the main burner.
7. Replace control access panel or louver once
there is a flame at the burner.
• If burner will not stay lit after several
tries, flip wall switch to OFF and call your
service technician or gas supplier.
OPERATING FIREPLACE
Continued
SPECIFICATIONS
E
A
O
L
H
I
L
PI OT
Inlet
Pressure
Figure 57 - Electronic Control Valve
Outlet
Pressure
Flame
Adjustment
Knob
From Gas
Supply
To
Main
Burner
Figure 58 - Electrode
Models (V)DVF36TCR and
(V)DVF36TCL
• Input Rating: 35,000/23,300 Btu/Hr
• Fuel: Natural Gas
• Manifold Pressure: 3.5" W.C.
• Minimum Supply Pressure: 4.5 W.C. **
• Maximum Supply Pressure: 10.5" W.C.
• Orifice Size (0-4500 ft.): #34 DMS
TO TURN OFF GAS
TO APPLIANCE
1. Turn off all electrical power to appliance if
service is to be performed.
2. Remove control access panel or louver.
3. Close gas valve.
Models (V)DVF36TCRP and
(V)DVF36TCLP
• Input Rating: 31,500/20,000 Btu/Hr
• Fuel: Propane/LP Gas
• Manifold Pressure: 10.0" W.C.
• Minimum Supply Pressure: 11.0 W.C. **
• Maximum Supply Pressure: 13.0" W.C.
• Orifice Size (0-4500 ft.): #51 DMS
Models (V)DVF36TCRE and
(V)DVF36TCLE
• Input Rating: 35,000
• Fuel: Natural Gas
• Manifold Pressure: 3.5" W.C.
• Minimum Supply Pressure: 4.5 W.C. **
• Maximum Supply Pressure: 10.5" W.C.
• Orifice Size (0-4500 ft.): #34 DMS
Models (V)DVF36TCRPE and
(V)DVF36TCLPE
• Input Rating: 31,500
• Fuel: Propane/LP Gas
• Manifold Pressure: 10.0" W.C.
• Minimum Supply Pressure: 11.0 W.C. **
• Maximum Supply Pressure: 13.0" W.C.
• Orifice Size (0-4500 ft.): #51 DMS
**For purpose of input adjustment.
**For purpose of input adjustment.