background image

www.fmiproducts.com

116239-01M

36

KC42N. VKC42N, KCC42N and VKCC42N

•  Rating: 27,000/38,000 Btu/hr
•  Gas Type: Natural Gas Only
•  Ignition: Piezo
•  Manifold Pressure: 3.5" w.c.
•  Minimum Inlet Supply Pressure: 5.5" w.c.
•  Firebox Dimensions (HxWxD) (Flanges and 

Standoffs Not Included in Measurement): 

 

40" x 48" x 23 

1

/

2

" (102 x 122 x 60 cm)

KC42P, VKC42P, KCC42P and VKCC42P

•  Rating: 25,000/36,000 Btu/hr
•  Gas Type: Propane/LP Gas Only
•  Ignition: Piezo
•  Manifold Pressure: 10" w.c.
•  Minimum Inlet Supply Pressure: 11" w.c.
•  Firebox Dimensions (HxWxD) (Flanges and 

Standoffs Not Included in Measurement): 

 

40" x 48" x 23 

1

/

2

" (102 x 122 x 60 cm)

SPECIFICATIONS

KC42N-HA, VKC42N-HA, KCC42N-HA 
and VKCC42N-HA

•  Rating: 27,000/38,000 Btu/hr
•  Gas Type: Natural Gas Only
•  Ignition: Piezo
•  Manifold Pressure: 3.8" w.c.
•  Minimum Inlet Supply Pressure: 5.5" w.c.
•  Firebox Dimensions (HxWxD) (Flanges and 

Standoffs Not Included in Measurement): 

 

40" x 48" x 23 

1

/

2

" (102 x 122 x 60 cm)

REPLACEMENT PARTS

Note:  Use  only  original  replacement  parts. 
This will protect your warranty coverage for 
parts replaced under warranty.

Contact authorized dealers of this product. 
If  they  can’t  supply  original  replacement 
part(s),  call  FMI  PRODUCTS,  LLC  at 
1-866-328-4537.

When calling, have ready:
•  your name
•  your address
•  model and serial numbers of your heater
•  how heater was malfunctioning
•  purchase date
Usually, we will ask you to return the part to 
the factory.

SERVICE hINTS

When Gas Pressure Is Too Low

•  pilot will not stay lit
•  burners will have delayed ignition
•  fireplace will not produce specified heat
•  propane/LP gas supply might be low (pro

-

pane/LP units only)

You may feel your gas pressure is too low. If 
so, contact your local gas supplier.

TEChNICAL SERVICE

You may have further questions about installa

-

tion, operation, or troubleshooting. If so, contact 
FMI  PRODUCTS,  LLC  at  1-866-328-4537. 
When calling please have your model and serial 
numbers of your heater ready.
You can also visit FMI PRODUCTS, LLC’s web 
site at 

www.fmiproducts.com

.

Содержание KC42N series

Страница 1: ...se gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not...

Страница 2: ...c tive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble op erate or service this log set Improper use of this log set can cause serious injury or death from burn...

Страница 3: ...accessory not approved for use with this fire place WARNING This appliance is only for use with the type of gasindicatedontheratingplate Thisapplianceisnotconvertible for use with other gases unless a...

Страница 4: ...d pilot light before cleaning fireplace 6 Have venting system inspected annually by a qualified service person If needed have venting system cleaned or repaired See Cleaning and Maintenance page 30 7...

Страница 5: ...r proper operation You must follow the venting instructions very carefully for either vertical or horizontal applications This fireplace may be installed in any room of your house provided all local c...

Страница 6: ...to prevent accidental blockage of venting system When using snow blowers do not direct snow towards vent termination area For horizontal installations above 2 000 feet it is recommended that a 12 ext...

Страница 7: ...l Vent C B A D E F G Top of Louver Opening 3 2 1 4 5 6 7 Wall Figure 5 Framing Clearances for Corner Installation Ref Mantel Depth Ref Mantel from Top of Louver Opening 1 14 A 16 2 12 B 14 3 10 C 12 4...

Страница 8: ...n US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally...

Страница 9: ...inate on the out side of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance Adirect vent appliance must have its own venting syste...

Страница 10: ...on male ends of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until the sections are fully locked see Figure 8 Note Horizontal runs of vent...

Страница 11: ...screws provided see Figure 11 Siding standoff must sit flush against exterior fascia material 7 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before connecting hori...

Страница 12: ...uired NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downward as this may cause excessive temperatures which could cause...

Страница 13: ...Recommended Applications Installations requiring a vertical rise on building exterior Any installation using snorkel termination to achieve one foot above ground Snorkel terminations are available for...

Страница 14: ...for a horizontal system using two 90 elbows Figure 18 Horizontal Termination Configuration for Venting Using Two 90 Elbows with Termination at 90 with Fireplace 45 Elbow Venting with Two 90 Elbows Ve...

Страница 15: ...above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space instal...

Страница 16: ...High Wind Termination Shown 45 Elbow Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 2 max 6 min 4 max 7 min 6 max 8 min 8 max 20 max 8 max Note Install restrictor into inner...

Страница 17: ...elevations from 0 2000 feet Fireplaces for High Altitude models ending in HA are for installation above 4000 feet only These fireplaces are equipped with parts specific for higher altitudes When insta...

Страница 18: ...m Collar Roof Flashing 0 12 6 12 26 Screws VKC 58 Corner Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Wall Firestop Horizontal Termination 6 Pipe 90 Elbow 18 Screws HHTK 58 High Wind Rou...

Страница 19: ...ed upward Blower will fit inside back opening and be held in position against back wall by magnets see Figure 26 4 Be certain that all wire terminals are securely attached to terminals on blower motor...

Страница 20: ...ower cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connec tions DO NOT trim excessive length away Enable just enough to make all conne...

Страница 21: ...ue Variable Fan Switch Fan Switch N O Green White On 110 115 V A C Blower Motor Black Off 1 2 Black Installing Gas Piping to Fireplace Location WARNING A qualified service person must connect fireplac...

Страница 22: ...you install a sediment trap drip leg in supply line as shown in Figure 32 Locate sediment trap drip leg where it is within reach for cleaning Install in piping sys tem between fuel supply and fireplac...

Страница 23: ...gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air 4 Check all joints of gas supply piping sys tem Apply noncorrosive leak detection...

Страница 24: ...3 Connect one bare wire end to each termi nal of the GWMS2 wall switch 4 Install wall switch and cover in the wall Fireplace Installation Continued Figure 37 Connecting Wall Switch to Control Valve To...

Страница 25: ...screen door tabs with slot openings in upper face frame Swing door screen assembly in towards the bottom face 4 Remount new frame at hinge with five new screws before closing door This will ensure sea...

Страница 26: ...n and close louvers see Removing Glass Door steps 5 through 7 page 25 WARNING The glass door mustbesecurelyinplacebefore runningthisfireplace Donotrun this fireplace if glass is missing or broken Fire...

Страница 27: ...RE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to l...

Страница 28: ...Push in gas control knob slightly and turn clockwise to OFF 5 Close lower louver panel MANUAL LIGHTING PROCEDURE 1 Remove glass door see Removing Re placing Glass Door page 24 2 Follow steps 1 through...

Страница 29: ...osi tion blower will not operate Note for BKT Only If you are using BKT blower with optional thermostat wall mounted or remote control for fireplace your fireplace and blower will not turn on and off...

Страница 30: ...peration Thereafter clean the glass two or three times during each heating season depending on the usage and circumstances present Refer to Removing Replacing Glass Door page 24 of this manual when re...

Страница 31: ...lling Lava Rock and Glowing Embers page 26 to properly replace logs Use a vacuum cleaner to remove any carbon buildup on logs Replace log s if broken See Replacement Parts on page 36 Replace ember mat...

Страница 32: ...en in stalled 5 Depleted gas supply pro pane LP models only 6 Pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or t...

Страница 33: ...ny 2 Clean burner see Clean ing and Maintenance page 30 or replace burner orifice 1 Clean burner see Clean ing and Maintenance page 30 or replace burner orifice 2 Replace damaged burner 3 Replace gas...

Страница 34: ...log grate removal 2 Check vent configuration specifications see Venting Installation page 9 1 This is normal If noise is excessive contact qualified service person 1 Replace 9 volt batteries in receiv...

Страница 35: ...leak See Warning statement above 2 Control valve defective 1 Gas leak See Warning statement above OBSERVED PROBLEM Fireplace produces un wanted odors Fireplace shuts off in use Gas odor even when cont...

Страница 36: ...8 x 23 1 2 102 x 122 x 60 cm Replacement Parts Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Contact authorized dealers of this pr...

Страница 37: ...supply these accessories call FMI PRODUCTS LLC at 1 866 328 4537 for information You can also write to the ad dress listed on the back page of this manual Brick Liner kit BL42D A Textured Refractory...

Страница 38: ...www fmiproducts com 116239 01M 38 Parts Models V KC42 N P AND V KCC42 N P Series 6 7 20 17 18 13 2 12 19 8 1 4 24 11 9 14 3 16 5 15 21 10 23 25 26 22 27 28 28 29 29...

Страница 39: ...ssembly 1 6 Fireplace Top 1 7 Fireplace Top Insulation 1 8 Fireplace Surround 1 9 109082 01 Heat Shield 1 10 116542 01 Burner Assembly NG See page 40 1 116542 02 Burner Assembly LP See page 40 1 11654...

Страница 40: ...www fmiproducts com 116239 01M 40 PARTS Burner assembly models V KC42 N P AND V KCC42 N P Series 7 15 10 12 1 12 2 3 13 9 11 21 22 TPTH TP TH 6 12 14 18 17 17 18 19 20 16 14 8 4 5...

Страница 41: ...11288 02 Flex Gas Line 1 10 108084 02 Pilot Assembly NG 1 108084 03 Pilot Assembly LP 1 108084 05 Pilot Assembly HA Models 1 11 14389 Natural Gas Valve 1 14390 Propane LP Gas Valve 1 117370 01 Natural...

Страница 42: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 43: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 44: ...s product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic ma...

Отзывы: