UNVENTED NATURAL GAS LOG HEATER

FIREPLACE MANUFACTURERS INCORPORATED

12

105191

Tee Joint

Pipe
Nipple

Cap

3" Minimum

Sediment
Trap

Gas
Regulator

From Gas
Meter (5"
W.C.** to
10.5" W.C.
Pressure)

A.G.A. Design-Certified
Manual Shutoff Valve With
1/8" NPT Tap

Approved Flexible Gas
Hose (if allowed by
local codes)

Figure 13 - Gas Connection

* Minimum inlet pressure for purpose of input adjustment.

INSTALLATION

Continued

CONNECTING TO GAS
SUPPLY

 WARNING: A qualified ser-

vice person must connect heater
to gas supply. Follow all local
codes.

Installation Items Needed

Before installing heater, make sure you have
the items listed below.

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• manual shutoff valve *

• test gauge connection *

• sediment trap

• tee joint

• pipe wrench

*  An A.G.A. design-certified manual shutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection.

 CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

 WARNING: Never connect

heater to private (non-utility) gas
wells. This gas is commonly
known as wellhead gas.

 CAUTION: Avoid damage to

regulator. Hold gas regulator with
wrench when connecting it to gas
piping and/or fittings.

Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
heater (see Figure 13).

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

 CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

Содержание Heat Majic FVF18N

Страница 1: ...e gas supplier s instructions If you cannot reach your gas sup plier call the fire department Installation and service must be performed by a qualified installer ser vice agency or the gas supplier WARNING Improper installation ad justment alteration service or mainte nancecancauseinjuryorpropertydam age Refer to this manual for correct installationandoperationalprocedures For assistance or additi...

Страница 2: ...his heater with glass doors closed If you operate heater with doors closed heat buildup inside fireplace will cause glass to burst Also if fireplace open ing has vents at the bottom you must open the vents before operating heater 7 You must operate this heater with a fire placescreeninplace Makesurefireplace screen is closed before running heater 8 This log heater is designed to be smoke less If l...

Страница 3: ...ater has a piezo ignitor This system requires no matches batteries or other sources to light heater UNPACKING CAUTION Do not remove the metal Data Plates from the grate assembly TheDataPlatescontain important product information 1 Remove logs and heater base assem bly from carton Note Do not pick up heater base assembly by the burner This could damage heater Always handle base assembly by grate 2 ...

Страница 4: ...truction methods helpreduceheatlossinhomes Homeowners weather strip and caulk around windows and doors to keep the cold air out and the warm air in During heating months home owners want their homes as airtight as possible While it is good to make your home energy efficient your home needs to breathe Fresh air must enter your home All fuel burning appliances need fresh air for proper com bustion a...

Страница 5: ...bustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can support _________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 71 500 Btu Hr actual amount of Btu Hr used The space in the above example is a confined space ...

Страница 6: ...on the wall connecting the two spaces see options 1 and 2 Figure 2 You can also remove door into adjoining room see op tion 3 Figure 2 Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fr...

Страница 7: ...reeheatersaddmois ture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Com bustion and Ventilation pages 4 through 6 NOTICE Stateorlocalcodesmay onlyallowoperationofthisappli ance in a vented configuration Check your state or local codes INSTALLATION AND CLEARANCES Vent Free Operation Only ...

Страница 8: ...lace hood accessory HDABK or HDABR see Accessories page 21 18 Model Noncombustible material OK Less than 8 Noncombustible material must be extended to at least 8 See Between 8 and 12 above If you cannot extend material you must operate heater with flue damper open NOTICE Manual control heaters maybeusedasaventedproduct If so you must always run heater with chimney flue damper open If running heate...

Страница 9: ...required Followminimumclear ances shown in Figure 7 when using hood NOTICE If your installation does notmeettheminimumclearances shown you must do one of the following operate the logs only with the flue damper open raise the mantel to an accept able height remove the mantel Continued FLOOR CLEARANCES A If installing appliance on the floor level you must maintain the minimum dis tance of 14 to com...

Страница 10: ...l burning fireplace with a working flue and constructed of non combustible material Ifyourheaterisamanuallycontrolledmodel you may use this heater as a vented product There are three reasons for operating your heater in the vented mode 1 The fireplace does not meet the clear ance to combustibles requirements for vent free operation 2 State or local codes do not permit vent free operation 3 You pre...

Страница 11: ...PORTANT Hold gas regulator with wrench when connecting flexible gas hose 2 Locate two masonry screws in hard ware package 3 Place heater base in fireplace 4 Place logs in their proper position on heater base 5 Center heater base and logs front to back and side to side in fireplace 6 Carefully remove logs without moving heater base 7 Mark screw locations through one hole on each side of the mountin...

Страница 12: ... certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to heater If pipe is too small undue loss of pressure will occur WARNING Never connect heater to private non utility gas wells This gas is commonly known as wellhead gas CAUTION Avoid damage to regulator Holdgasregulatorwith wrenchwhenconnectingittogas piping and or fittings Installsedimenttrapinsu...

Страница 13: ...sures In Excess Of 1 2 PSIG 1 Disconnect heater and its individual manual shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where manual shutoff valve was connected 3 Pressurize supply piping system by ei ther using compressed air or opening main gas valve located on or near gas meter 4 Check all joints of gas su...

Страница 14: ...ailuretoposition thepartsinaccordancewiththese diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal injury INSTALLING LOGS INSTALLATION Continued CAUTION After installation andperiodicallythereafter check to ensure that no flame comes in contact with any log With the heater set to High check to see if flames contact any log If so re...

Страница 15: ...ow to vent smell Thiswillonlylastafewhours Note Home owners generally prefer to operate their heater with the chimney damper closed This will put all the heat into the room However there may be times you will desire the full flames of the High heat setting but will find the heat output excessive You can open the chim ney damper if you have one fully or partially to release some of the heat WARNING...

Страница 16: ... heater between PILOT and HIGH positions CAUTION Donottrytoadjust heating levels by using the manual shutoff valve The variable control valve can be set to anyheatsettingandflameheightdesired by simply turning the control knob until that setting is attained Even the lowest setting provides realistic dancing yellow flames Selectinghighersettingsproduces greater heat output This results in in crease...

Страница 17: ...nect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base panel 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace ignitor 7 Replace ignitor 1 Turn on gas supply or open manual shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILO...

Страница 18: ...atural gas company 3 Observe minimum installation clear ances see pages 7 through 9 4 Clean burners see Cleaning and Mainte nance page 20 or replace burner orifice 1 Refer to Air for Combustion and Venti lation requirements pages 4 through 6 1 Properly locate logs see Installing Logs page 14 2 Eliminate source of drafts around heater 3 Clean out air holes at burner inlet Peri odically repeat as ne...

Страница 19: ...h air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak SeeWarning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page OBSERVED PROBLEM Heater produces a clicking ticking noise just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS oper...

Страница 20: ...low the proper amount of air to mix with the gas This provides a clean burning flame Keep these holesclearofdust dirt andlint Cleanthese air inlet holes prior to each heating season Blocked air holes will create soot We rec ommend that you clean the unit every 2 500 hours of operation or every three months Wealsorecommendthatyoukeeptheburner tube and pilot assembly clean and free of dustanddirt To...

Страница 21: ... ready model number of your heater the replacement part number REPLACEMENT PARTS SPECIFICATIONS Heat Majic 18 Heat Majic 24 30 Variable Manually Variable Manually Controlled Controlled Btu Variable 16 000 27 000 16 000 31 500 Type Gas Natural Gas Only Natural Gas Only Ignition Piezo Piezo Piezo Pressure Manifold 3 5 W C 3 5 W C Inlet Gas Pressure in of water Maximum 10 5 10 5 Minimum 5 5 Shipping ...

Страница 22: ...ED NATURAL GAS LOG HEATER FIREPLACE MANUFACTURERS INCORPORATED 22 105191 ILLUSTRATED PARTS BREAKDOWN HEAT MAJIC FVF18N FVF24N FVF30N ODS Pilot 4 12 21 10 11 21 7 21 5 6 8 9 15 14 16 19 2 18 13 19 17 20 18 3 1 ...

Страница 23: ... 18 099056 18 Burner Orifice Injector 1 11 102843 01 102843 01 102843 01 Burner Clip 1 12 102963 01 102773 01 102773 01 Burner 1 13 102568 07 102568 07 102568 07 Control Valve 1 14 098508 01 098508 01 098508 01 Valve Retainer Nut 1 15 098354 01 098354 01 098354 01 Control Knob 1 16 102445 01 102445 01 102445 01 Piezo Ignitor 1 17 098249 01 098249 01 098249 01 Nut M5 2 18 099387 08 099387 08 099387...

Страница 24: ... MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transpo...

Отзывы: