www.fmiproducts.com
125325-01A
7
vENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide
two permanent openings: one within 12" (30.5
cm) of the ceiling and one within 12" (30.5 cm)
of the floor on the wall connecting the two
spaces (see options 1 and 2, Figure 2, page
7). You can also remove door into adjoining
room (see option 3, Figure 2, page 7). Follow
the
National Fuel Gas Code, ANSI Z223.1/
NFPA 54
, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills
or ducts. You must provide two permanent
openings: one within 12" (30.5 cm) of the ceil-
ing and one within 12" (30.5 cm) of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the
Na-
tional Fuel Gas Code, ANSI Z223.1/NFPA 54,
Air for Combustion and Ventilation for required
size of ventilation grills or ducts.
IMPORTANT:
Do not provide openings for inlet
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the
attic will activate the power vent.
AIR FOR COMBUSTION AND VENTILATION
Continued
Figure 2 - Ventilation Air from Inside
Building
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri
-
mary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualified ser
-
vice person must install heater.
Follow all local codes.
CHECK GAS TYPE
Use only the correct gas type (natural
or propane/LP) for your unit. If your gas
supply is not correct, do not install heater.
Call dealer where you bought heater for
proper type heater.
WARNING: This appliance is
equipped for either natural gas or
propane/LP gas but not both. Gas
type is indicated on the rating plate.
Field conversion is not permitted.
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills into
Adjoining
Room,
Option 1
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic