HEARTH EXTENSION

A hearth extension projecting a minimum of 

16" in front of and a minimum of 8" beyond 

each side of fireplace opening is required to 

protect combustible floor construction in front 

of  fireplace.  Fabricate  a  hearth  extension 

using  a  material  which  meets  the  following 

specifications:  a  layer  of  noncombustible, 

inorganic material having a thermal conductiv

-

ity of K=0.84 BTU IN/FT, HR. F (or less) at 1" 

thick. For example, if material selected has 

a  K  factor  of  0.25,  such  as  glass  fiber,  the 

following formula would apply:

 

0.25 x 1.0" = 0.30" thickness required

 

0.84

Thermal conductivity "K" of materials can be 

obtained  from  manufacturer  or  supplier  of 

noncombustible material. If hearth extension 

is to be covered, use noncombustible mate

-

rial such as tile, slate, brick, concrete, metal, 

glass, marble, stone, etc. Provide a means 

to prevent hearth extension from shifting and 

seal gap between fireplace frame and hearth 

extension  with  a  noncombustible  material 

(see Figure 3).

 WARNING: Hearth extension 

is to be installed only as shown 

in Figure 3.

FIREPLACE INSTALLATION

Figure 3 - Hearth Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front 

Raised Hearth

Fireplace Front 

Elevated

Ember Protector

Ember Protector

Seal Gap

Hearth 

Extension

Seal Gap

Fireplace Front

Ember Protector

Fireplace Front 

Elevated

Do Not Block Louver

Ember Protector

Seal Gap

Hearth 

Extension

Hearth Extension, Circulating Modes

Hearth Extension, Noncirculating Models

NO

Содержание CCAT36 Series

Страница 1: ...s com CATALYTIC FIREPLACE OWNER S OPERATION AND INSTALLATION MANUAL PFS US C This fireplace is approved for use as a wood burning fire place or for use with a vented gas log approved to ANS Z21 60 and Z21 84 standards or for use with a vent free gas logheaterapprovedtoANSZ21 11 2standard AFMIPROD UCTS LLC hood must be installed when using a vent free log heater see Accessories page 21 This wood bu...

Страница 2: ...s manual for assistance or additional in formation Consult a qualified installer or local distributor IMPORTANT Check local codes before installing this fireplace Before beginning installation of this fireplace read these instructions through completely This FMI PRODUCTS LLC fireplace and its components are safe when installed according to this installation manual Unless you use FMI PRODUCTS LLC c...

Страница 3: ...DEWALL 1 AIRSPACE TO COMBUSTIBLE MATERIAL COMBUSTIBLE WALL BOARD 0 TO TOP SPACERS NO COMBUSTIBLE MATERIAL ON FACE GAS LINE KNOCK OUTS AIR KIT KNOCK OUT GAS LINE KNOCK OUTS ELECTRICAL OUTLET LEFT SIDE RIGHT SIDE 9 125 11 435 14 437 41 250 37 41 35 21 33 813 8 32 5 14 25 22 3 5 8 717 1 11 217 3 5 9 125 7 092 8 717 12 5 41 1 2 313 0 625 29 21 SQUARE CHASE TOP TERMINATION ROUND TOP TERMINATION ...

Страница 4: ...measure ment includes fireplace chimney sections and height of termination assembly at level of flue gas outlet see Figure 19 page 12 FRAMING 1 Frame opening for fireplace using dimen sions shown in Figures 1 and 2 2 If fireplace is to be installed directly on carpeting tile other than ceramic or any combustible material other than wood flooring fireplace must be installed upon a metal or wood pan...

Страница 5: ...an be obtained from manufacturer or supplier of noncombustible material If hearth extension is to be covered use noncombustible mate rial such as tile slate brick concrete metal glass marble stone etc Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material see Figure 3 WARNING Hearthextension is to be instal...

Страница 6: ...d within 9 of fireplace opening and within 6 of top louver opening Combustible materials above 9 and projecting more than 1 1 2 from fireplace must not be placed less than 12 from top opening of fireplace NFPA STD 211 Sec 7 3 3 3 Figure 5 Mantel Clearances to Combustible Material without Louver 12 1 4 Ref 1 1 2 Max Upper Section of Circulating Fireplace 6 Ref 6 Min 33 3 Nom Note Drawing Not To Sca...

Страница 7: ...tion with Slip Section 8 1 2 to 21 1 2 ET 8DM Square Chase Top 12 ETO 8DM Square Chase Top with Mesh 12 ETL 8DM Square Chase Top with Slip Section 7 to 15 ETLO 8DM Square Chase Top with Mesh Slip Section 12 to 25 1 2 The lineal gain for the terminations is measured to the flue gas outlet height VENTING INSTALLATION Continued ASSEMBLY AND INSTALLATION OF DOUBLE WALL CHIMNEY SYSTEM Each double wall ...

Страница 8: ...f properly locked It is not necessary to add screws to keep chimney to gether exception see Figure 10 page 9 USING ELBOW OFFSETS 30E 8DM 1 To achieve desired offset you may install combinations of 12 18 24 36 and 48 length of double wall pipe see offset chart and Figure 8 Note For systems with 2 elbow sets mini mum height is 22 feet Maximum height for any system is 50 feet 2 Chimney weight above o...

Страница 9: ...HIMNEY LENGTH A B 48 36 24 18 12 4 3 8 16 3 8 ELBOW SET ONLY 9 3 4 25 1 2 1 12 3 4 30 3 4 1 15 34 3 4 1 18 40 1 1 21 1 4 46 1 4 1 23 3 4 49 1 4 1 1 27 3 4 56 3 4 1 30 60 3 4 1 1 33 66 1 1 36 71 1 1 38 1 4 75 2 41 1 4 80 1 4 1 1 1 45 86 3 4 2 46 3 4 89 1 2 1 1 1 51 97 1 1 53 1 4 101 2 1 56 1 4 106 1 4 2 59 1 4 111 1 2 1 1 1 61 3 4 115 1 2 2 1 64 3 4 120 3 4 2 1 68 1 4 127 1 2 70 130 2 1 1 74 1 4 13...

Страница 10: ... around perimeter of flashing to provide a proper seal FIRESTOP SPACERS 3600FS 8DM 1 Firestop spacers are required at each point where chimney penetrates a floor space Their purpose is to establish and maintain required clearance between chimney and combustible materials When pipe passes through a framed opening into a living space above firestop must be placed onto ceiling from below as shown in ...

Страница 11: ...tallation instructions provided with the termination being used VENTING INSTALLATION Continued Attach Bracket Tabs to Outer Pipe 3 Places Secure with Screws RTL 8DM Level of Flue Gas Outlet Caulk Collar Flashing Underlap Shingles Bottom Only Figure 16 Termination Overlap Shingles Top and Sides Terminations with 16 slip pipe sections are available RTT 8DM and RTTL 8DM are approved for flashing inst...

Страница 12: ...ct contact with sides and top around the fireplace face It is important that combustible materials do not overlap face itself Brick glass tile or other noncombustible materials may overlap front face provided they do not obstruct essential openings such as louvered slots When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive 30E 8DM EFFECTIVE HEIGHT OF TE...

Страница 13: ...ither side of fireplace and pull out insu lation from gas line conduit sleeve Save insulation for reuse Note Secure incoming gas line to wood framing to provide rigidity for threaded end 4 Repack insulation around gas line and into sleeve opening Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement Install gas appliance or cap off gas line...

Страница 14: ... WARNING Whenusingadec orative vented gas log damper mustberemovedorpermanently locked in fully open position and glassdoorsmustbeinfullyopen position The following tips should be used to assure that both fireplace and glass door retain their beauty and function properly Both flue damper and glass doors must be fully opened before starting a fire This will provide sufficient combustion air and mai...

Страница 15: ...ner Cleaning Glass Clean glass with any commercial glass cleaner or soap and water Do not use any abrasive material to clean glass Do not clean glass with any cool water if glass is still hot from fire and smoke A gas line or gas log lighter may be installed for the purpose of installing a vented or vent free decorative gas appliance incorporating an automatic shutoff device and complying with the...

Страница 16: ...e fireplace grate must always be secured to the retaining brackets provided The position of the grate must be centered against the back wall of the firebox Burn only dry seasoned cured wood with less than 20 moisture Avoid the use of treated painted and laminated wood Never burn garbage or other foreign materials Do not use artificial logs colored newspaper or petroleum based fire starters Avoid w...

Страница 17: ... burned If visible smoke continues the combustor has ceased to function or there is thermal crumbling Call FMI PRODUCTS LLC at 1 866 328 4537 for replacement parts WARRANTY FMI PRODUCTS LLC warranty obligations for the PureFire Emissions Control System are limited to the terms set forth below FMI PRODUCTS LLC warrants to the consumer who purchases a new solid fuel burning fireplace containing a Pu...

Страница 18: ... 01B 18 PARTS WOOD BURNING FIREPLACE MODELS V CCAT36 V CCAT36I V CCAT36H V CCAT36L V CCAT36LI V CCAT36LH 9 4 32 33 19 12 25 20 30 17 8 1 5 21 2 34 18 11 14 3 13 22 10 6 31 7 36 37 38 39 40 41 35 42 28 29 15 26 16 27 16 27 23 24 ...

Страница 19: ...eplace Top Insulation 1 22 Access Panel 1 23 107854 01 Right Refractory Bracket 1 24 107854 02 Left Refractory Bracket 1 25 125186 01 Grate 1 26 11418 Push On Nut 2 27 12105 Screen 2 28 Collar Insulation 1 29 20023 Chimney Starter Collar 1 30 20027 Refractory Retainer 2 31 23534 Grate Retainer 2 32 20088 Door Stop 1 33 20090 Spring Clip 2 34 20280 Top Standoff 4 35 21171 Conduit Plate Cover 4 36 2...

Страница 20: ...CCAT36 I VCCAT36L I Left 106658 01 Right 106659 01 Rear 106660 01 Bottom Rear 106661 01 Bottom Front 106662 01 CCAT36 I CCAT36L I Left 106658 02 Right 106659 02 Rear 106660 02 Bottom Rear 106661 02 Front Rear 106662 02 EMBER PROTECTOR 20093 TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting If so contact FMI PRODUCTS LLC at 1 866 328 4537 When calling ...

Страница 21: ...LD Round Top Termination Only ADS 8DM 30 OFFSET AND RETURN 30E 8DM ANTI DRAFT SHIELD Round Top Termination Only ADS 8DM STORM COLLAR SC1 1 For RT 8DM and RTL 8DM SC2 1 For RTT 8DM and RTTL 8DM FIRESTOP SPACER 3600FS 8DM 1 ROUND TOP TERMINATIONS RT 8DM RTL 8DM ROUND TOP TERMINATIONS WITH SLIP SECTION RTT 8DM RTTL 8DM SQUARE CHASE TOP TERMINATION ET 8DM ETO 8DM ECONO TOP TERMINATION WITH SLIP SECTIO...

Страница 22: ...A6053 Black Painted Finish GA6050 Required when installing a vent free gas log in this fireplace BI FOLD GLASS DOOR BD36 Black BD36B Brushed Brass BD36P Platinum OUTSIDE AIR KIT FOR SIDE WALL INSTALLATION AK4 OUTSIDE AIR KIT FOR FLOOR INSTALLATION AK4F ACCESSORIES Continued ...

Страница 23: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________...

Страница 24: ...125183 01 Rev B 12 10 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Отзывы: