VENTING INSTALLATION

Continued

Pitch

Slope Opening 

"A" Max. 

Used Flashing 

Model No. 

Flat

15"

V6F-8DM

0-6/12

26.6°

16 

1

/

8

"

V6F-8DM

6/12- 12/12 45.0°

20 

3

/

8

"

V12F-8DM

4.  Remove shingles around opening mea

-

sured. Cut out this section.

5.  Add  next  sections  of  pipe  until  end 

penetrates  roof  line.  Check  to  see  that 

proper clearances are maintained. Extend 

chimney by adding sections of double wall 

pipe until pipe is minimum of 30" above 

highest point of roof cutout. Termination 

and chimney must extend a minimum of 

36" above highest point where it passes 

through roof.

Figure 14 - Roof Opening Measurements

FLASHING INSTALLATION (V6F-8DM 

OR V12F-8DM)

Determine flashing to be used with roof open

-

ing chart. Slide flashing over pipe until base is 

flat against roof. Replace as many shingles as 

needed to cover exposed area and flashing 

base. Secure in position by nailing through 

shingles (see Figure 15, page 11). DO NOT 

NAIL THROUGH FLASHING CONE.

Installing Flashing on a Metal Roof

When  installing  flashing  on  a  metal  roof,  it 

is required that putty tape be used between 

flashing and roof. Flashing must be secured 

to roof using #8 x 3/4" screws and then sealed 

with roof coating to prevent leakage through 

screw holes. A roof coating must also be ap

-

plied around perimeter of flashing to provide 

a proper seal.

FIRESTOP SPACERS (FS-8DM)

Firestop spacers are required at each point 

where  chimney  penetrates  a  floor  space. 

Their  purpose  is  to  establish  and  maintain 

required  clearance  between  chimney  and 

combustible  materials.  When  pipe  passes 

through a framed opening into a living space 

above, firestop must be placed onto ceiling 

from below as shown in Figure 12.
They also provide complete separation from 

one floor space to another or attic space as 

required by most codes. When double wall 

pipe passes through a framed opening into 

an attic space, firestop must be placed into 

an attic floor as shown in Figure 13.

Figure 12 - Firestop Spacer with Living 

Space Above Ceiling

Figure 13 - Firestop Spacer with Attic 

Space Above Ceiling

PENETRATING ROOF

To maintain a 2" clearance to pipe on a roof with 

a pitch, a rectangular opening must be cut.
1.  Determine  center  point  where  pipe  will 

penetrate the roof.

2.  Determine center point of the roof. Pitch 

is the distance the roof drops over a given 

span, usually 12". A 6/12 pitch means that 

the roof drops 6" for each 12" measure 

horizontally down from roof rafters.

3.  Use  roof  opening  chart  (Figure  14)  to 

determine  correct  opening  length  and 

flashing required.

If area above is a living space, install 

firestop below framed hole.

If area above is an attic or insulated area, 

install firestop above framed hole.

14 

3

/

8

"

(36.5 cm)

30"

(76.2 cm)

1"

(2.5
cm)

1"

(2.5
cm)

Minimum Measurements

1"

(2.5 cm)

Opening "A"

f i r e - p a r t s . c o m

Содержание C42MW-LS

Страница 1: ...ds or for use with a vent free gas logheaterapprovedtoANSZ21 11 2standard Ahoodmust be installed when using a vent free log heater see page 18 This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to dete...

Страница 2: ...or loss of life Refer to this manual for assistance or additional in formation Consult a qualified installer or local distributor IMPORTANT Check local codes before installing this fireplace Before beginning installation of this fireplace read these instructions through completely This FMI PRODUCTS LLC fireplace and its components are safe when installed according to this installation manual Unles...

Страница 3: ...O COMBUSTIBLE COMBUSTIBLE WALL BOARD 0 TO MATERIAL NO COMBUSTIBLE MATERIAL ON FACE GAS LINE KNOCK OUT AIR KIT KNOCK OUTS ROUND TOP TERMINATION GAS LINE KNOCK OUTS LEFT SIDE RIGHT SIDE NOT LESS THAN 14 TO PERPENDICULAR SIDEWALL SQUARE CHASE TOP TERMINATION 8 25 10 375 13 37 5 33 44 42 21 5 32 6 5 38 85 14 438 1 375 25 375 7 7 1 8 25 14 44 1 1 75 0 625 28 5 21 125 fire parts com ...

Страница 4: ...nt includes fireplace chimney sections and height of termination assembly at level of flue gas outlet see Figure 18 page 11 FRAMING 1 Frame opening for fireplace using dimen sions shown in Figures 1 and 2 2 If fireplace is to be installed directly on carpeting tile other than ceramic or any combustible material other than wood flooring fireplace must be installed upon a metal or wood panel extendi...

Страница 5: ...ed from manufacturer or supplier of noncombustible material If hearth extension is to be covered use noncombustible mate rial such as tile slate brick concrete metal glass marble stone etc Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material see Figure 3 WARNING Hearthextension is to be installed only as ...

Страница 6: ...l with this fireplace for circulating models only Use of blowers or fans other than those manufactured by FMI PRODUCTS LLC voids warranty Fan is operated by pressing rocker switch see Figure 6 in lower right hand corner of fireplace face Blower is operated by turning control knob not shown Fan blower kit electrical connections are made through electrical cover plate on side of fireplace a shown in...

Страница 7: ...Eyebrow Vented Crawl Space Check Local Codes Before Installing in a Vented Crawl Space VENTING INSTALLATION OPTIONAL OUTSIDE AIR KIT MODEL AK4 AK4F Installation of outside air kit should be per formed during rough framing of fireplace due to the nature of it s location Outside combus tion air is accessed through a vented crawl space AK4F or through a sidewall AK4 See Figure 24 on page 15 for instr...

Страница 8: ...obstructed Never use blown insulation to fill chimney enclosure Continue to assemble chimney sections as outlined making sure that both inner and outer pipe sections are locked together When installing double wall snap lock chimney to gether it is important to assure joint between chimney sections is locked Check by pulling chimney upward after locking Chimney will not come apart if properly locke...

Страница 9: ... 1 1 33 66 1 1 36 71 1 1 38 1 4 75 2 41 1 4 80 1 4 1 1 1 45 86 3 4 2 46 3 4 89 1 2 1 1 1 51 97 1 1 53 1 4 101 2 1 56 1 4 106 1 4 2 59 1 4 111 1 2 1 1 1 61 3 4 115 1 2 2 1 64 3 4 120 3 4 2 1 68 1 4 127 1 2 70 130 2 1 1 74 1 4 137 1 2 1 2 1 76 3 4 141 1 2 1 2 1 79 3 4 146 3 4 4 OFFSET CHART 22 50 FT SYSTEM HEIGHT 2 Min Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop See Det...

Страница 10: ...perimeter of flashing to provide a proper seal FIRESTOP SPACERS FS 8DM Firestop spacers are required at each point where chimney penetrates a floor space Their purpose is to establish and maintain required clearance between chimney and combustible materials When pipe passes through a framed opening into a living space above firestop must be placed onto ceiling from below as shown in Figure 12 They...

Страница 11: ...ion being used Flashing Cone VENTING INSTALLATION Continued Attach Bracket Tabs to Outer Pipe 3 Places Secure with Screws RTL 8DM Level of Flue Gas Outlet Caulk Collar Flashing Underlap Shingles Bottom Only Figure 17 Termination Overlap Shingles Top and Sides Terminations with 16 slip pipe sections are available RTT 8DM and RTTL 8DM are approved for flashing installations When needed these adjusta...

Страница 12: ...ct with sides and top around fireplace face It is important that combustible materials do not overlap face itself Brick glass tile or other noncombustible materials may overlap front face provided they do not obstruct essential openings such as louvered slots When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive 30E 8DM EFFECTIVE HEIGHT OF TERMINATION CA...

Страница 13: ...refractory knockout hole with refractory cement or commercial furnace cement Install gas appliance or cap off gas line if desired CAUTION Allgaspipingand connections must be tested for leaks after installation is com pleted After ensuring that gas valveison applysoapandwater solution to all connections and joints Bubbles forming show a leak Correct all leaks at once DO NOT USE AN OPEN FLAME FOR LE...

Страница 14: ...ORS Glass doors are standard with this fireplace When fireplace is in operation doors must be fully opened or fully closed position only or a fire hazard may be created see Figure 23 A fireplace equipped with glass doors oper ates much differently than a fireplace with an open front A fireplace with glass doors has a limited amount of air for combustion Exces sive heat within fireplace can result ...

Страница 15: ...amper Handle 1 2 3 1 2 3 Damper Weight To Close Damper To Open Damper Figure 25 Damper Rod TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting If so contact FMI PRODUCTS LLC at 1 866 328 4537 When calling please have your model and serial numbers of your heater ready You can also visit our web site at www fmiproducts com REPLACEMENT PARTS If this produc...

Страница 16: ...www fmiproducts com 126134 01A 16 PARTS WOOD BURNING FIREPLACE MODEL C42MW LS 11 27 30 23 22 24 10 14 25 4 17 3 2 1 5 20 28 12 7 15 9 16 13 8 26 6 29 19 18 21 fire parts com ...

Страница 17: ... 1 13 see page 18 Right Side Brick Liner 1 14 see page 18 Bottom Brick Liner 1 15 see page 18 Front Bottom Brick Liner 1 16 21198 Blower Access Plate 1 17 20027 Refractory Retainer 2 18 20060 Circulation Plate 1 19 21366 Insulation Retainer 1 20 106959 01 Top Standoff 4 21 20023 Chimney Starter Collar 1 22 20088 Door Stop 1 23 11418 Push On Nut 2 24 20090 Spring Clip 2 25 107001 02 Wood Burning Gr...

Страница 18: ...TABLE HOOD Antique Brass Finish GA6053 Black Painted Finish GA6050 Required when installing a vent free gas log in this fireplace STORM COLLAR SC1 1 For RT 8DM and RTL 8DM SC2 1 For RTT 8DM and RTTL 8DM BI FOLD GLASS DOOR Black Finished included on unit BD42B Brushed Brass BD42P Platinum PARTS Continued STANDARD BRICK LINER Left 106971 01 Right 106970 01 Rear 108310 01 Bottom Rear 108312 01 Bottom...

Страница 19: ...ARE CHASE TOP TERMINATION ET 8DM ETO 8DM ECONO TOP TERMINATION WITH SLIP SECTION ETL 8DM ETLO 8DM ACCESSORIES Continued VENT KIT DESCRIPTION MW8K 8 Vent Kit MW9K 9 Vent Kit 36 8DM 36 Double Wall Pipe 2 2 24 8DM 24 Double Wall Pipe 1 0 18 8DM 18 Double Wall Pipe 0 2 FST A Adjustable Firestop Thimble 1 1 V6F 8DM Roof Flashing 1 1 SC1 1 Storm Collar 1 1 RTL 8DM Round Cap Termination 1 1 Use for Most ...

Страница 20: ...126134 01 Rev A 01 12 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com fire parts com ...

Отзывы: