background image

 

For more information, visit www.desatech.com

10 FOOT RULE: 

All flue gas outlet of chimney termination must extend a 
minimum of 3 feet in height above the highest point where it 
passes through the roof and must be at least 2 feet above the 
highest point of the roof that is within a horizontal distance of 
10 feet (see figure 18). 

 
FINISHING THE FIREPLACE: 

Combustible materials, such as wallboard, gypsum board, 
sheet rock, drywall, plywood, etc may make direct contact 
with sides and top periphery of the fireplace face. It is 
important that combustible materials do not overlap the face 
itself. Brick, glass, tile or other non-combustible materials 
may overlap the front face provided they do not obstruct 
essential openings like louvered slots or any other opening. 
When overlapping with a non-combustible facing material use 
only non-combustible mortar or adhesive. 

MANTELS: 

A mantel may be installed if desired (see figure 19). 
Woodwork such as wood trims, mantels, or any other 
combustible material projecting from the front face must not 
be placed within 9 inches of the fireplace opening (and within 
6 inches of the top louver opening). Combustible materials 
above 9 inches and projecting more than 1-1/2 inches from the 
fireplace face must not be placed less than 12 inches from the 
top of the opening of the fireplace (NFPA STD 211, Sec. 7-
3.3.3). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Mantels or any other combustible materials such as wallboard, 
sheet rock, drywall, plywood, etc. butt up to the side of the 
black metal face of the fireplace.  The clearances from the side 
of the fireplace to any combustible material and wall should 
fall within the limits shown in figure 20.   

 
*Example 1 (figure 20): The face of a mantel, bookshelf, etc. 
is made of combustible materials and protrudes 2-¾” from the 
wall the fireplace is installed in.  This combustible material 
must be a minimum of 4” from the side of the fireplace 
opening. 
*Example 2 (figure 20): The face of a mantel, bookshelf, etc. 
is made of combustible materials and protrudes 11/16” from 
the wall the fireplace is installed in.  This combustible material 
can butt up against the side of the fireplace (i.e. 1” from the 
fireplace opening). 

 
OPERATING GUIDELINES AND MAINTENANCE 
INSTRUCTIONS 
GLASS DOORS 

Glass doors are optional with the fireplace. When the fireplace 
is in operation, doors must be in the FULLY OPEN or 
FULLY CLOSED position only or a fire hazard may be 
created (see figure 21). 
A fireplace equipped with glass doors operates much 
differently than a fireplace with an open front.  A fireplace 
with glass doors has a limited amount of air for combustion.  
Excessive heat within the fireplace can result if too large a fire 
is built or if the combustion air gate is not completely open.  
The following tips should be followed to assure that both the 
fireplace and the glass door retain their beauty and function 
properly.  Both flue damper and the glass doors must be fully 
open before starting the fire. This will provide sufficient 
combustion air and maintain safe temperatures in the firebox. 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Figure 21 

FIREBOX

Minimum 14 inches from perpendicular side wall

TOP VIEW OF FIREPLACE

Figure 20                     

MINIMUM SIDE CLEARANCE

 

Figure 18 

Figure 19     

MINIMUM FRONT AND TOP CLEARANCES 

Содержание Baja II 36WIL

Страница 1: ...pproved to ANS Z21 60 Z21 84 or RGA 2 72 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard A DESA hood must be installed when using a vent free gas log heater see Accessories p 10 WARNING ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE SAVE THIS BOOK This book is valuable In addition to instructing you on how to install and m...

Страница 2: ...5 HEARTH EXTENSION PG 3 6 OUTSIDE AIR KIT INSTALLATION PG 4 7 FAN KIT ASSEMBLY PG 4 8 CHIMNEY PIPE INSTALLATION PG 4 5 6 9 TERMINATIONS PG 6 10 FINISHING YOUR FIREPLACE PG 7 11 MANTELS PG 7 12 GLASS DOORS PG 7 13 GAS LINE INSTALLATIONS PG 8 14 CHIMNEY OFFSET PG 9 15 DAMPER OPERATION PG 10 16 TECHNICAL SERVICE PG 10 17 REPLACEMENT PARTS AND ACCESORIES PG 11 ...

Страница 3: ...arances see page 7 Finishing your Fireplace Chimney Outer Pipe Surfaces 1 Min WARNING DO NOT PACK REQUIRED AIR SPACES WITH INSULATION OR OTHER MATERIALS MINIMUM MAXIMUM CHIMNEY HEIGHT The MINIMUM height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 11 5 feet for straight flue or a flue with one elbow set The maximum distance between elbows is 2...

Страница 4: ...r of non combustible inorganic material having a thermal conductivity of K 0 84 BTU IN FT HR F or less at 1 thick For example if the material selected has a K factor of 0 25 such as glass fiber the following formula would apply 0 25 0 84 x 1 0 0 30 thickness required Thermal conductivity K of materials can be obtained from the manufacturer or supplier of the non combustible material If the hearth ...

Страница 5: ... flue pipe section with the hemmed end up Press down on each pipe section until the lances securely engage the hem on the fireplace starter The wire will assure the proper spacing between the inner and outer pipe sections Continue to assemble chimney sections as outlined above making sure that both the inner and outer pipe sections are locked together When installing double wall snap lock chimney ...

Страница 6: ...hich the pipe will penetrate the roof STEP 2 Determine the center point of the roof Pitch is the distance the floor drops over a given span usually 12 inches A 6 12 pitch means that the roof drops 6 inches for each 12 inches one measure horizontally down the roof STEP 3 Use the roof opening chart figure 13 below to determine the correct opening length and flashing required STEP 4 Remove the shingl...

Страница 7: ... any case refer to the installation instructions supplied with the termination The terminations approved for this fireplace are the RT 8DM and RTL 8DM that can be used for flashing or chase and ET 8DM ETO 8DM ETL 8DM and ETLO 8DM for chase style termination only Figure 16 shows an RTL 8DM round top termination Terminations with 16 slip pipe sections are available The RTT 8DM and RTTL 8DM are appro...

Страница 8: ... the fireplace The clearances from the side of the fireplace to any combustible material and wall should fall within the limits shown in figure 20 Example 1 figure 20 The face of a mantel bookshelf etc is made of combustible materials and protrudes 2 from the wall the fireplace is installed in This combustible material must be a minimum of 4 from the side of the fireplace opening Example 2 figure ...

Страница 9: ... gas line to wood framing to provide rigidity for threaded end STEP 4 Repack insulation around gas line and into sleeve opening Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement Install the gas appliance or cap off gas line if desired The gas pipe is intended for connection to an unvented vent free or a decorative gas appliance vented g...

Страница 10: ...to lock it in place see figure 24 FOR FURTHER OPERATING GUIDELINES INSTRUCTIONS AND WARRANTY INFORMATION PLEASE REFER TO YOUR HOMEOWNERS GUIDE OR CONTACT YOUR AUTHORIZED DEALER TECHNICAL SERVICE You may have further questions about installation operations or troubleshooting If so contact The Technical Service Department at 1 888 427 8322 When calling have the model number of the fireplace ready Fi...

Страница 11: ...For more information visit www desatech com 10 REPLACEMENT PARTS ACCESSORY PARTS ...

Отзывы: