1745
Users Manual
20
Connections in 3-Phase 3-Wire (Delta) Systems
Figure 5 shows the connections for logging 3-phase 3-wire (Delta) systems.
The test lead “N” can be left open or connected to ground potential.
L1
A
L2 B
L3 C
LOGGING S
TATUS
CURRENT INPUT
10 VRMS MAX
5 VA
45 -65 Hz
SUPPLY INPUT
100 -350V
660 V MAX
88 -660V
VOLTAGE INPUT
600 V CAT
300 V CAT
T
RS232
POWER QUALITY LOGGER
1745
830 V
480 V
MAX
L-L
L- N
/
START / STOP
/
L1
L2
L3
N
Power Supply
egc004.eps
Figure 5. Logging in a 3-Phase 3-Wire (Delta) System