Outputs
Analog output
Function
transmitting differential flow rate.
Accuracy
10 bit. Error < 0.05% - update 10 times a second.
Software function to calibrate the 4.00mA and 20.00mA levels precisely within set-up.
Load
max. 1 kΩ
Type AA
Active 4-20mA output (requires type OA + PD, PF or PM).
Type AB
Active 0-20mA output (requires type OA + PD, PF or PM).
Type AF
Passive floating 4-20mA output for Intrinsically safe applications (requires PC or PD).
Type AI
Passive galvanic isolated output (requires PB, PD, PF, PL or PM).
Type AP
Passive 4-20mA output - output loop powered.
Type AU
Active 0-10V output (requires type OA + PD, PF or PM).
Switch outputs
Function
One pulse output - transmitting accumulated total.
Pulse output
Max. frequency 500Hz. Pulse length user definable between 0.001 up to 9.999 seconds.
Type OA
Active 24V DC transistor output; max. 50mA per output (requires type AA + PD, PF or PM).
Type OR
Isolated mechanic relay output; max. switch power 230V AC - 0,5A (requires type PF or PM).
Type OT
Passive transistor output - not isolated. Load max. 50V DC - 300mA.
Communication (option)
Protocol
bus-rtu; bus-asc
Speed
1200; 2400; 4800; 9600
Addressing
1 - 247
Type CB
RS232
Type CH
RS485 2-wire
Type CI
RS485 4-wire
Type CT
TTL Intrinsically safe communication.
Type CX
no communication.
Operational
Operator functions
Shown functions
Compensated differential total and/or compensated differential flow rate.
Compensated differential total and compensated differential accumulated total.
Inlet temperature and compensated flow rate.
Outlet temperature and compensated flow rate.
Compensated differential total can be reset to zero by pressing the CLEAR-key twice.
Total
Digits
7 digits.
Unit
L; m
3
; kg; lb; GAL; USGAL; bbl; no unit
Decimals
0000000; 111111.1; 22222.22; 3333.333
Total can be reset to zero.
Accumulated total
Digits
11 digits.
Unit / decimals
According to selection for total.
Flow rate
Digits
7 digits.
Unit
mL; L; m
3
; mg; g; kg; ton; gal; bbl; lb; cf; rev; - - - - (no unit); scf; nm
3
; nL; p
Decimals
0000000; 111111.1; 22222.22; 3333.333
Time units
/sec; /min; /hour; /day
Line temperature
Digits
6 digits.
Units
°C; °F; K
Decimals
1
Normal temperature
default: 273.15 K - any temperature can be set.
Flow equations
Type EL
Equations Liquid - flow computer for corrected liquid volume
Formula
Qnormal = Q * (1 +
(Tnormal - T)) where
= thermal expansion coefficient.